CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Scott and Sandra in Ajax on Twintech Heating and Cooling

After receiving numerous quotes to replace my old furnace and AC unit (which was 20 years old) I went with Twintech. Dave, in sales, answered questions professionally and promptly and worked diligently in order to secure my business. Installation was scheduled the week after and Greg and Peter showed up, as scheduled, and did a fine job installing both units. The site was left tidy and neat. I would highly recommend Twintech for your furnace and AC work.

by Linda from Whitby on Twintech Heating and Cooling

I chose TwinTech because they installed my new furnace a few years ago and did a great job. When they installed my new A/C, they replaced all parts -- the copper pipes, the housing on top of the furnace and the wiring. (Apparently, the wiring for my old A/C was insufficient.) Their pricing was competitive. The sales representative came to see me within a few hours of my call. My new A/C was installed a few days later and I couldn't be happier with Twintech's professionalism and work. I would recommend TwinTech to any homeowner.

by george polychronis from Whitby on Twintech Heating and Cooling

Had a great experience with this company. Great price and great customer service. You wont be disappointed with twintech. Discussed the job with Greg while he was installing who was extremely informative and obviously enjoys the work he does.

by Nuzio in Markham on Twintech Heating and Cooling

I needed my AC unit relocated due to upcoming landscape work. I reached out to the Twintech team through Homestars. Dave connected with me immediately to discuss the project and various options. We decided the best option was to mount the unit on the wall. Greg was in touch with me the same day as well and we scheduled the work for later that same week. This was a small job so I did not think I would get immediate attention. The Twintech team exceeded my expectations in every respect. They were very knowledgeable and friendly. The team arrived exactly on time on the scheduled day and worked efficiently to get the job done quickly. I would definitely use Twintech again for any Heating and AC projects.

by Leslie B, Pickering on Twintech Heating and Cooling

I have used Greg Dainty for over 15 years in 3 different homes, for heating, cooling, pool heaters, appliances and bbq lines. Greg has always been so professional, friendly and the workmanship nothing short of fantastic. Greg has always discussed my options and fixing versus replacing, giving his honest opinion and what works best for me cost effective wise and long term. I have valued his opinion so much and have not trusted my gas needs with anyone since using him. I have also referred him to many of my friends and family and have always been so thankful with how well and quickly he looks after us all. I hold Greg in the highest regard and would recommend him to anyone with complete confidence!

by Marcel M, Whitby ON on Twintech Heating and Cooling

Really nice honest guys. It was a pleasure to do business with a company that does exactly what they say they’re going to do! My basement was cleaner after they installed my new furnace and AC. Thanks again Greg and Grant and for doing such a great job.

by George In Pickering on Twintech Heating and Cooling

5 star service!! I had twin tech install a high efficiency furnace and hot water tank at my home. I am taking time to write this review as a thanks for what I viewed as next level service that went above and beyond. Prior to installation they explained my specific options without pushy sales tactics and up front costs. Greg and Grant replaced a large portion of the duct work (built in their own shop) that had rusted over the years which resulted in a great looking job. It was a pleasure to work with people are passionate and take pride in their work. Following the installation they explained all aspects and maintenance of the new equipment. Products have worked flawlessly. Thanks again Greg and Grant! Highly recommend!!

by Donna J, in Ajax on Twintech Heating and Cooling

Twin Tech was great; they were honest, reliable and very thorough. I would recommend their services and will definitely be using them in the future.

by Sheila C. Pickering on Twintech Heating and Cooling

Hi Dave, Thank You Dave for coming to my aid this past summer when my AC quit. Your men did a great job installing and cleaning the area. The unit is working very well and i would highly recommend your company TwinTech. Dave you delivered what you sold and i truly appreciate it.

by Darin O. Whitby on Twintech Heating and Cooling

My experience with TWINTECH has been excellent, start to finish. While doing market research I made a list of several local companies and called them for some high-level information. Dave was the first to call me back, and the only one to book a meeting to see my place in order to give an informed, accurate estimate. He reviewed the different AC makes and models with me, explained the technology, and made a recommendation appropriate to my home. The installation went smoothly. I had one post-installation issue – there was moderate noise/vibrations coming from the duct system. I called about this, booked an appointment, and the technician resolved the issue during the service call. I feel assured having a 10-year warranty on parts & labour. I would recommend TWINTECH to anyone considering an AC or furnace for their home. Regards,