The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.


CODE: On solid, no flash.
RESULT: None.
FIX: Normal operation.

CODE: Rapid continuous flashing.
RESULT: Standard Thermostat Control 288ANA/180ANA only.
FIX: Unit being controlled by standard thermostat inputs instead of Evolution Control. Only high stage operation is aveliable. This operating mode should be used in emergency situations only.

CODE: 1 pause.
RESULT: None.
FIX: Normal operation.

CODE: 2 pause.
RESULT: None.
FIX: Normal operation.

CODE: 16.
RESULT: System Communications Failure.
FIX: Communication with User Interface lost. Check wiring to UI, indoor and outdoor units.

CODE: 25.
RESULT: Invalid Model Plug.
FIX: Control does not detect a model plug or detects an invalid model plug. Unit will not operate without correct model plug.

CODE: 31.
RESULT: High Pressure Switch Open.
FIX: High - pressure switch trip. Check refrigerant charge, outdoor fan operating and coils for airflow restrictions.

CODE: 32.
RESULT: Low Pressure Switch Open.
FIX: Low - pressure switch trip. Check refrigerant charge and indoor air flow.

CODE: 45.
RESULT: Control Fault.
FIX: Outdoor unit control board has failed. Control board needs to be replaced.

CODE: 46.
RESULT: Brown Out (230v).
FIX: Line voltage < 187v for at least 4 seconds.

CODE: 47.
RESULT: No 230v at Unit Measured at L1 and L2 on circuit board.
FIX: There is no 230v at the contactor when indoor unit is powered and cooling/heating demand exists.

CODE: 53.
RESULT: Outdoor Air Temp Sensor Fault.
FIX: Outdoor air sensor not reading or out of range.

CODE: 55.
RESULT: Outdoor Coil Sensor Fault.
FIX: Coil sensor not reading or out of range. Ohm out sensor and check wiring.

CODE: 56.
RESULT: Thermistors out of range.
FIX: Improper relationship between coil sensor and outdoor air sensor. Ohm out sensor and check wiring.

CODE: 71.
RESULT: Low Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 72.
RESULT: High Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 73.
RESULT: Contactor Shorted.
FIX: Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring error.

CODE: 74.
RESULT: No 230v at Compressor.
FIX: Compressor voltage not sensed when compressor should be starting. Contactor may be stuck open or there is a wiring error.

CODE: 75.
RESULT: Low Stage Did Not Start.
FIX: Specified start voltage at VR terminal was not achieved in low stage. Start relay was de-energized after 1 second.

CODE: 76.
RESULT: Low Stage Did Not Start 3 times.
FIX: For 3 consecutive low stage starts, the specified start voltage at VR terminal was not achieved and start relay was de-energized. Low stage locked out for 30 minutes.

CODE: 77.
RESULT: High Stage Did Not Start.
FIX: Specified start voltage at VS terminal was not achieved in high stage. Start relay was de-energized after 1 second.

CODE: 78.
RESULT: High Stage Did Not Start 3 times.
FIX: For 3 consecutive high stage starts, the specified start voltage at VS terminal was not achieved and start relay was de-energized. High stage locked out for 30 minutes.

CODE: 81.
RESULT: Low Stage Thermal Lockout.
FIX: Thermal cutout occurs in three consecutive low/high stage cycles. Low stage locked out 4 hours or until 24v power recycled.

CODE: 82.
RESULT: High Stage Thermal Lockout.
FIX: Thermal Lockout occurs in three consecutive high/low stage cycles. High stage locked out for 4 hours or until 24V power recycled.


See What Our Customers Are Saying:

by Lousan, Ajax on Twintech Heating and Cooling

From quote, to installation, to follow up, Twintech provided excellent service. I would highly recommended their services.

by John, Pickering on Twintech Heating and Cooling

I had a really great experience with these guys. The salesman Bob was clearly very knowledgeable about everything to do with heating and cooling a home, spent a lot of time with us going over the details of the job, never rushed us and came back after the install to make sure we were happy. The installation crew was excellent, they covered the floors all the way from outside down to the basement furnace room, kept the place clean, got the work done on time and we’re very friendly. I’ve got 15 years in the contracting/ construction industry and these guys are one of the most professional company’s I’ve dealt with. Great company!

by Debra Robertson on Twintech Heating and Cooling

Had great service and clean-up was good. Was happy with my salesman. They were very friendly and helpful. I needed a new furnace as our was over 20 years old. The furnace and air-conditioner work great and they are very quiet. I am very pleased with the service and product I received.

by Private User on Twintech Heating and Cooling

Met with Dave for the sales process and he was great about explaining and going over everything to us. The install happened very quickly and the team were super professional and friendly. We are very happy with this company and their services and we definitely recommend them to others. Thankful my sister recommended them to me!

by Private User on Twintech Heating and Cooling

Reviews for Twintech were good, and they did not disappoint. After an initial visit to discuss the suitable AC unit for replacement, an installation date was available in just a couple of days, and everything was installed without a hitch. Highly recommended

by Private User on Twintech Heating and Cooling

Very pleased with the installation of our new furnace and A/C unit. From quotation stage to the completion of the job Twintech was very professional.
Thank you for a job well done.

by Darren, Pickering on Twintech Heating and Cooling

My old water heater quit on me. I called TwinTech. In less than 4 days, I had my new water heater installed and the old one taken away. The whole process was quick, easy, pleasant, and well done. This is the third time I've dealt with TwinTech and I've been satisfied each time.

by Private User on Twintech Heating and Cooling

I had them replace my furnace last year. When it came time for the air conditioner this year, I did not hesitate to call Twintech again. I will also have them perform regular maintenance on them.

by Robert, Ajax on Twintech Heating and Cooling

We required a new HVAC replacement after running the old
system for 18 years.
Dave understood our requirements and gave us a quote that
covered all the necessary items.
Installation was fast and very tidy. Everything works as
it should. Our thanks to Greg, Mitch and others for their
excellent work. Recommend this family owned business to
anyone else, considering HVAC or other work.

by John Armstrong, Pickering on Twintech Heating and Cooling

I needed a new furnace and A/C to replace my 21 yr. old units, and went to the internet to view potential companies in May, I received 3 quotes,
and chose Twintech based on their salesman Dave who was very detailed and covered off everything on what Twintech was all about,
an extremely dedicated company with so many years of experience, and after reading the on line reviews I was sold on Twintech, who did not disappoint as the installation team were top notch with Greg leading,
I would highly recommend this company without any doubts, in my books they are first class all the way. Our new Amana furnace and A/C are working perfectly !