The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.


CODE: On solid, no flash.
RESULT: None.
FIX: Normal operation.

CODE: Rapid continuous flashing.
RESULT: Standard Thermostat Control 288ANA/180ANA only.
FIX: Unit being controlled by standard thermostat inputs instead of Evolution Control. Only high stage operation is aveliable. This operating mode should be used in emergency situations only.

CODE: 1 pause.
RESULT: None.
FIX: Normal operation.

CODE: 2 pause.
RESULT: None.
FIX: Normal operation.

CODE: 16.
RESULT: System Communications Failure.
FIX: Communication with User Interface lost. Check wiring to UI, indoor and outdoor units.

CODE: 25.
RESULT: Invalid Model Plug.
FIX: Control does not detect a model plug or detects an invalid model plug. Unit will not operate without correct model plug.

CODE: 31.
RESULT: High Pressure Switch Open.
FIX: High - pressure switch trip. Check refrigerant charge, outdoor fan operating and coils for airflow restrictions.

CODE: 32.
RESULT: Low Pressure Switch Open.
FIX: Low - pressure switch trip. Check refrigerant charge and indoor air flow.

CODE: 45.
RESULT: Control Fault.
FIX: Outdoor unit control board has failed. Control board needs to be replaced.

CODE: 46.
RESULT: Brown Out (230v).
FIX: Line voltage < 187v for at least 4 seconds.

CODE: 47.
RESULT: No 230v at Unit Measured at L1 and L2 on circuit board.
FIX: There is no 230v at the contactor when indoor unit is powered and cooling/heating demand exists.

CODE: 53.
RESULT: Outdoor Air Temp Sensor Fault.
FIX: Outdoor air sensor not reading or out of range.

CODE: 55.
RESULT: Outdoor Coil Sensor Fault.
FIX: Coil sensor not reading or out of range. Ohm out sensor and check wiring.

CODE: 56.
RESULT: Thermistors out of range.
FIX: Improper relationship between coil sensor and outdoor air sensor. Ohm out sensor and check wiring.

CODE: 71.
RESULT: Low Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 72.
RESULT: High Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 73.
RESULT: Contactor Shorted.
FIX: Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring error.

CODE: 74.
RESULT: No 230v at Compressor.
FIX: Compressor voltage not sensed when compressor should be starting. Contactor may be stuck open or there is a wiring error.

CODE: 75.
RESULT: Low Stage Did Not Start.
FIX: Specified start voltage at VR terminal was not achieved in low stage. Start relay was de-energized after 1 second.

CODE: 76.
RESULT: Low Stage Did Not Start 3 times.
FIX: For 3 consecutive low stage starts, the specified start voltage at VR terminal was not achieved and start relay was de-energized. Low stage locked out for 30 minutes.

CODE: 77.
RESULT: High Stage Did Not Start.
FIX: Specified start voltage at VS terminal was not achieved in high stage. Start relay was de-energized after 1 second.

CODE: 78.
RESULT: High Stage Did Not Start 3 times.
FIX: For 3 consecutive high stage starts, the specified start voltage at VS terminal was not achieved and start relay was de-energized. High stage locked out for 30 minutes.

CODE: 81.
RESULT: Low Stage Thermal Lockout.
FIX: Thermal cutout occurs in three consecutive low/high stage cycles. Low stage locked out 4 hours or until 24v power recycled.

CODE: 82.
RESULT: High Stage Thermal Lockout.
FIX: Thermal Lockout occurs in three consecutive high/low stage cycles. High stage locked out for 4 hours or until 24V power recycled.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

Flawless transaction. They did exactly what they promised, showed-up on time, cleaned-up, and were highly professional. Highly recommended.

by Bill Edmondson on Twintech Heating and Cooling

Salesperson and 2 man installation team were all professional and
knew their stuff. All three were friendly and helpful, answering all
my questions. The quality of their work demonstrated their experience
and expertise in their field.

by Private User on Twintech Heating and Cooling

A dear late cousin of mine recommended this company and I have been happy with the service.

by Private User on Twintech Heating and Cooling

We are very pleased with the work done by Twintech. They were very professional from start to finish. Dave came to our home and gave us a very competitive quote for new high efficiency furnace and air conditioner. The installers were very courteous and professional. We would highly recommend them.

by W1n5t0n1987! on Twintech Heating and Cooling

Great experience getting an old furnace replaced.
Sales Guy (Dave) was great - honest, responsive, and friendly.
The work itself was done quickly and we are very happy with the outcome, thank you! We recommend TwinTech!

by Private User on Twintech Heating and Cooling

This review is late coming so my apologies to the amazing Twin Tech team! I contacted Dave at Twin Tech for a quote this past Feb (as I was collecting a few) and his recommendation was excellent. From the first meeting with Dave to the team installing the new furnace, not once did i feel uncomfortable . The team were extremely professional yet personable and clean and tidy. Decent companies still exist!
The new furnace just purrs and its just amazing the difference it has made!
(PS my sibling ended up getting a furnace from them as well)

by Private User on Twintech Heating and Cooling

The service was Twintech was excellent.
Dave our salesperson was easy to talk to and was professional. The unit recommended meets our needs and budget.
Greg and his team arrived on time for the installation and even got rid of the garbage the contractors left in our furnace.
Would definitely recommend Twintech.

by Steve V, Toronto on Twintech Heating and Cooling

Our old water tank was installed in 1997. Wasn't working as well as it should so we looked into a tankless as it is more efficient and a space saver! we had used Twintech in the past for a furnace cleaning and were satisfied with that so we decided to ask for a quote for the changeover. Gary arrived and provided the options and the quote fit within our budget so we decide to go with them after receiving a few alternative quotes from other companies. They did what the said would be done and it was completed within a reasonable time frame! Removal and cleanup of the old tank was seamless. We are now enjoying consistent and efficient Hot water! I recommend Twintech and would use them for future projects!

by New AC Unit + Humidifier on Twintech Heating and Cooling

One of the most honest HVAC companies out there! Dave was very helpful and informative in helping us choose a new AC unit. While they weren’t the lowest quote, we went with them because we trusted Dave and he was the most honest guy out of the companies that quoted us.
Greg and his crew who installed the unit were very professional and did a great job. If I could do it over again I would choose Twintech again.

by Private User on Twintech Heating and Cooling

Relocated and replaced our air conditioning unit. Fast, professional, and high quality service. We would definitely use them again for future projects!