Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Elizabeth and John L from Scarborough on Twintech Heating and Cooling

In October 2018, I contacted Greg at Twintech to do a furnace cleaning. Greg discovered that my furnace, installed in 2006 by another company, had been installed incorrectly, leading to restricted air flow. The heat exchanger was also defective. As well, my furnace was too large for the size of my house.

In my opinion, the biggest concern most of us have as consumers is that we have no idea of the quality or knowledge and experience of the technicians any heating and cooling company will send into our homes. I could have avoided having my 2006 furnace installed improperly (leading to early replacement), had I known about Twintech then.

With Twintech you get it all. Because Twintech is a smaller company you can rest assured that the only technicians who will work in your home are Greg and his twin brother Grant who are co-owners and fully licensed and certified with over 30 years of experience in installing and servicing heating and cooling equipment. They are both friendly and personable and answer all your questions. Their workmanship is outstanding. We had a 2 stage, variable speed Goodman furnace installed. My wife and I noticed a difference in the heating and even temperature of our 2 storey home almost immediately. Our old furnace always heated too much on the main floor and too little upstairs. We are also impressed with how quiet the furnace is.

Twintech's office manager, David Gergley, is equally friendly and not only gave us a competitive quote to replace our furnace (we sought other quotes), but also went above and beyond my expectations when he made arrangements with an energy audit company so that we would be considered for a grant from Enbridge and IESO.

Needless to say, I give Twintech a 10 out of 10 and highly recommend them!

by James, Ajax on Twintech Heating and Cooling

Clean, Fast and Efficient Work. Between all the quotes I received Twintech was a few dollars less and offered the best warranty.

by garysumnec360, Whitby on Twintech Heating and Cooling

They did an excellent job. Everything was very well explained. At the end of the job everything was very well cleaned up.

by Glade, Pickering on Twintech Heating and Cooling

Twintech offered me a competitive price but more importantly great sales and installation service. They did everything with attention to detail and quality workmanship that is hard to find in this day and age. Dave who first game to visit me answered most of my questions and probed about my needs. For the technical/install questions he was unable to answer he quickly had Greg and Grant the owners answer for me. They did not cut corners on the installation or do anything to simply save time. They stayed into the early evening to complete the job and removed all my old components and even fixed up mistakes other workers ahd made in the past. I would highly recommend them and use them again if the need arises in the future. If you are looking for service or new equipment I would highly recommend Twintech be on your list of Heating companies to get a quote from and ask your questions to.

by Anne of Major Oaks in Pickering on Twintech Heating and Cooling

The company epitomizes high quality service: from the initial client interaction with Dave to the installation and follow up with the technical team. One of the key features I look for is the ability of a technical person to talk to and not talk down to the customer when responding to questions and I had quite a few, all of which were very professionally addressed. I was also quite impressed with the follow up service, promptness, the obvious competence of the team who left no stone un-turned to ensure I was a satisfied customer. Thank you guys.

by Aileen Johnson in Toronto on Twintech Heating and Cooling

All staff concerned were total professionals. Sales rep Dave was like having an old friend at your house. No up selling or pressure, just good honest facts and figures. The owners and assistant who installed our unit worked quietly, efficiently and left our home clean. We could not have been happier with the service and attention we were given. We are so happy a family member recommended Twintech. She said "don't call anyone else, just call them...they are amazing". And they were!!! Thank you guys for the great work!!! A. Johnson

by Lynsey from Toronto on Twintech Heating and Cooling

We are completing a large project adding an addition on to our house and couldn’t be more pleased with our decision to trust Twintech with our hvac work. They removed and replaced the furnace, installed a new A/C unit, swapped our tank water heater for a tankless unit, and completed ducting and new A/C lines through the addition. Without hesitation we would recommend Twintech to anyone.

by Oldtown in Pickering on Twintech Heating and Cooling

Honest, very personable , men of their word ,workmanship xcellent ,showed up when promised ,They do not try to up sell ,rather give good advice instead . Price was very fair in my opinion .We have a family member with a medical condition and I think they made us a priority .Very happy with these guys . (Nice guys ) Stu Leffler Ajax.

by Mike B. Toronto on Twintech Heating and Cooling

Very professional, courteous, knowledgeable staff. Sales staff (David Gergley) excellent in knowledge and getting the job setup and installation was very prompt. Greg and Peter (technicians) knew their stuff and stuck around after completion to make sure it all worked properly and that I understood how it all was installed and how the unit worked. Would highly recommend them! Thanks for a great job-house is now cool and comfortable.

by Steve S in Toronto on Twintech Heating and Cooling

I had Twintech install a brand new air condition back in June of this year and I'm very happy with their service. I have a very busy schedule so I sent out an email to 7 or 8 HVAC companies just to get an idea of what it would cost. Dave at Twintech and only one other company were able to give me an approximate quote through email. Many of the companies I reached out to didn't even respond. I decided to meet with Dave and he was very friendly and professional. He gave me a good quote for a name brand/energy efficient AC with installation from their certified technicians. It was an easy decision to go with them.

Within a week I had the unit installed and working perfectly. Their technicians were very helpful and answered all of my questions. I'll definitely be calling them back for all of my HVAC needs in the future.