Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Furnace And Humidifier Install on Twintech Heating and Cooling

Dealing with Bob and the installation crew was a pleasure. They took the time to explain everything. What would benefit us the most and the price difference. They were in and out in a reasonable time frame and fit us in within a couple days of original meeting. Quality of work is excellent as well.

by Private User on Twintech Heating and Cooling

A pleasure dealing with Bob ,Spencer and Mitch . They are professional and they also observe the covid 19 precautions . Bob explained the whole process and got the new furnace up the next day . Highly recommend

by Gary Monson, Ajax on Twintech Heating and Cooling

Would like to thank TwinTech for their quick response to our furnace repair. We used TwinTech to install a new furnace and AC a few years
back. Our furnace started to have problems early in the evening of extremely cold night. Contacted TwinTech and they were able make a service call later that evening. They got the furnace going and came the next day to replace a part. The part was under warranty and there was
no charge for either service call!
We are extremely happy with their customer service and would highly recommend them.
Gary & Kelly

by Paul, Toronto on Twintech Heating and Cooling

This is the second time we have had Twintech to our house. A couple of summers ago they were in for an issue with our air conditioning. This time it was our furnace having an issue. It was shutting off randomly and not coming back on. Greg came right away and took the time to investigate thoroughly and explain what was going with the furnace. Both times I have been thoroughly impressed with their speed, customer service, and quality of work. I HIGHLY recommend Twintech.

by Stan, Courtice on Twintech Heating and Cooling

Based on good reviews I hired Twintech to look at a small leak on my 5yr old water heater, they sent an employee to inspect and give a quote to repair which would total about $300. 100 for the initial call/inspection and another $200 for the repair. I agreed to the repair and they showed up on the agreed date to do the repair, it was to replace a dip tube but after removing the old one he couldn’t get the new one in. After about half an hour of trying he realized he had gotten the wrong part which he blamed his supplier for. Then told me it would be about a week to get this custom order part and would mean I would have no hot water for a week, so I went from a small insignificant leak to no water heater. I can’t believe that an experienced professional didn’t know these had custom order parts and basically left with my water heater disassembled and leaking water all over my basement. I would never hire this company for any projects ever again. I ended up having to buy a new water heater and didn’t even receive an apology from the company for their incompetence.

by Private User on Twintech Heating and Cooling

Based on good reviews I hired Twintech to look at a small leak on my 5yr old water heater, they sent an employee to inspect and give a quote to repair which would total about $300. 100 for the initial call/inspection and another $200 for the repair. I agreed to the repair and they showed up on the agreed date to do the repair, it was to replace a dip tube but after removing the old one he couldn’t get the new one in. After about half an hour of trying he realized he had gotten the wrong part which he blamed his supplier for. Then told me it would be about a week to get this custom order part and would mean I would have no hot water for a week, so I went from a small insignificant leak to no water heater. I can’t believe that an experienced professional didn’t know these had custom order parts and basically left with my water heater disassembled and leaking water all over my basement. I would never hire this company for any projects ever again. I ended up having to buy a new water heater and didn’t even receive an apology from the company for their incompetence.

by Private User on Twintech Heating and Cooling

Extremely happy.
So we were in no rush to replace our old units and took the time to do some research and get a number of quotes.
Twintech came in at around the middle of the pack for price but what convinced us to go with them was Bob, the representative that came to our house. Bob was by far the most professional of all the reps that we met with. He took the time to explain everything, what would work best for us and why. He really did seem very knowledgeable and enthusiastic about his stuff.
As promised on the day of install the crew showed up on time and got to work with minimal impact on us
..they were professional, clean, tidy and got the system up and running ahead of schedule...they made a couple of adjustments to the system to optimize it for our house.
The crew left the house clean and tidy.
Bob the rep showed up to check in and give us a few tips ..
It's been a week since install and all is good.
Our overall experience with Twintech has been excellent from start to finish and I wouldn't hesitate to recommend them.
Thank u.

by Private User on Twintech Heating and Cooling

It was a refreshing experience interacting with the Twintech team. From Bob, the sales consultant, who articulated in layman's terms all the options available and reasons for making any selection. This was done without the prevailing pressure tactics so commonplace today.

Before proceeding Mitch, the technician, at our request conducted a service check on our 30 yr old furnace. His report was positive indicating no urgency to replace it. Again no pressure tactics.

Three days after first meeting with Bob, the installation team of Greg and
Spencer completed the installation within the planned time frame.

A very professional, courteous and transparent team which delivered on their promise. I highly recommend Twintech.

by Private User on Twintech Heating and Cooling

Initial contact with sales resulted in an immediate response, which led to a timely installation. Both sales and installers were all very professional. I have no hesitation in recommending TWINTECH.

by Private User on Twintech Heating and Cooling

I had a great experience with TwinTech. The company offered a reasonable quote, and performed a quick and clean installation. The installer Greg was experienced, professional and courteous. He explained the services he performed and gave recommendations on maintain the new furnace.

The salesman Bob was honest
and professional and educated me on how to achieve optimal performance.

All communication from them was quick and they came the following day. I was pleased with the service and would recommend them.