Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Lousan, Ajax on Twintech Heating and Cooling

From quote, to installation, to follow up, Twintech provided excellent service. I would highly recommended their services.

by John, Pickering on Twintech Heating and Cooling

I had a really great experience with these guys. The salesman Bob was clearly very knowledgeable about everything to do with heating and cooling a home, spent a lot of time with us going over the details of the job, never rushed us and came back after the install to make sure we were happy. The installation crew was excellent, they covered the floors all the way from outside down to the basement furnace room, kept the place clean, got the work done on time and we’re very friendly. I’ve got 15 years in the contracting/ construction industry and these guys are one of the most professional company’s I’ve dealt with. Great company!

by Debra Robertson on Twintech Heating and Cooling

Had great service and clean-up was good. Was happy with my salesman. They were very friendly and helpful. I needed a new furnace as our was over 20 years old. The furnace and air-conditioner work great and they are very quiet. I am very pleased with the service and product I received.

by Private User on Twintech Heating and Cooling

Met with Dave for the sales process and he was great about explaining and going over everything to us. The install happened very quickly and the team were super professional and friendly. We are very happy with this company and their services and we definitely recommend them to others. Thankful my sister recommended them to me!

by Private User on Twintech Heating and Cooling

Reviews for Twintech were good, and they did not disappoint. After an initial visit to discuss the suitable AC unit for replacement, an installation date was available in just a couple of days, and everything was installed without a hitch. Highly recommended

by Private User on Twintech Heating and Cooling

Very pleased with the installation of our new furnace and A/C unit. From quotation stage to the completion of the job Twintech was very professional.
Thank you for a job well done.

by Darren, Pickering on Twintech Heating and Cooling

My old water heater quit on me. I called TwinTech. In less than 4 days, I had my new water heater installed and the old one taken away. The whole process was quick, easy, pleasant, and well done. This is the third time I've dealt with TwinTech and I've been satisfied each time.

by Private User on Twintech Heating and Cooling

I had them replace my furnace last year. When it came time for the air conditioner this year, I did not hesitate to call Twintech again. I will also have them perform regular maintenance on them.

by Robert, Ajax on Twintech Heating and Cooling

We required a new HVAC replacement after running the old
system for 18 years.
Dave understood our requirements and gave us a quote that
covered all the necessary items.
Installation was fast and very tidy. Everything works as
it should. Our thanks to Greg, Mitch and others for their
excellent work. Recommend this family owned business to
anyone else, considering HVAC or other work.

by John Armstrong, Pickering on Twintech Heating and Cooling

I needed a new furnace and A/C to replace my 21 yr. old units, and went to the internet to view potential companies in May, I received 3 quotes,
and chose Twintech based on their salesman Dave who was very detailed and covered off everything on what Twintech was all about,
an extremely dedicated company with so many years of experience, and after reading the on line reviews I was sold on Twintech, who did not disappoint as the installation team were top notch with Greg leading,
I would highly recommend this company without any doubts, in my books they are first class all the way. Our new Amana furnace and A/C are working perfectly !