The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by Todd Whyte on Twintech Heating and Cooling

My existing 15-yr old A/C went down on me during the first major heatwave of the season. Researched my options, as well as a few different installers, and decided on Twintech.

They gave me confidence right from the beginning. Extremely knowledgeable. Their communication was excellent - always responded to questions quickly. Given we were in a heatwave, they were fully booked. However, within days they were able to fit me in due to a cancellation. Upon learning that the Amana unit I was getting installed was on backorder, TwinTech went to bat for me with the manufacturer and was able to get me the next model up within a day, for the same price - Amazing!

As far as the installation was concerned, I couldn’t be more impressed. These guys were clearly very experienced and did a fantastic job. Very clean, polite, timely & informative. They even thoroughly sealed all the exposed gaps in my ductwork. I’ve had plenty of heating and cooling work done in the past and have never used the same contractor twice because I’ve never been very impressed. However, from now on, I’ll always be contacting Twintech first!

by Jordan Arnott, Courtice on Twintech Heating and Cooling

They were very friendly and took care of everything. The install looks great (and works great), they were very knowledgeable. Installed our a/c efficiently despite the difficult install location both inside and outside and they made it work.

by Lori Ellis on Twintech Heating and Cooling

Phenomenal service, so glad I found these guys a few years back after being "hosed" badly by 3 other companies. I've recommended them to so many, and they all are so thankful.

by Jonathan Rogoza on Twintech Heating and Cooling

This company is fantastic. Dave came out and gave me a very honest and reasonable quote, unlike a quote received from another company. I had a bunch of questions that were easily answered and when I had questions regarding heating/cooling a previously unheated room above the Garage, Dave arranged for Greg to come out for an assessment of this new space and gave me his recommendation along with his professional thoughts on all of my options.

These guys have been nothing but Professional, honest and helpful along the way. I can't recall the two other guys doing the install, but they were great as well. Good workmanship, everything was cleaned up and everything functions as promised. I could go on and on about my experience, but it's all positive so what more could you want?

Give them a call, see for yourself. If I had to buy another furnace/AC or heat pump, they'd be my first call.

by Private User on Twintech Heating and Cooling

I hired twin tech to convert my townhouse heating from electric to gas and install a furnace and a/c unit. I had talked with many other vendors, and received several quotes, but chose them, and very happy I did. Here are some of the reasons why:
1. They were realistic about the timeline for the work, when they could start and how long it would take. (They said upfront, it was their busy season and would need to get back to me in 3 weeks, which they did):
2. They had a quote with options for me. They were clear about the entertainment of what they would and would not do (they’d build duct work, id need another contractor to box in ductwork). This allowed me to plan as I was my own general contractor for my renovations).
3. They spoke to me in a language I understood, neither too technical nor too simple. They answered all my questions as I had them. Everyone is so lovely to work with, the sales team and the contractors who are worked in my home.
4. It’s been 4 m since the work was complete. They still answer my emails and my furnace is working very well!

I unabashedly recommend! Price, customer care and quality workmanship were all amazing!

by Anna Chin, Ajax on Twintech Heating and Cooling

On one of the coldest days of winter, our furnace stopped working. Our regular furnace company came and told us we had a CO2 leak and shut us off. Their quote for a new furnace was way too high and they couldn't even install it on the same day. TwinTech was recommended to us by a friend. We called and spoke to Dave who was very nice and knowledgeable. Grant showed up a short time later and a new furnace was installed the same day with no troubles at all. Best of all, we received a higher-end furnace than what was offered by our previous company and at a cheaper price. I would recommend TwinTech with no hesitation at all.

by Hiba, Pickering on Twintech Heating and Cooling

I installed a new furnace and Air conditioner with them. The installation is of high quality and according to standards. The guys are professional and reasonably priced.. I highly recommend them.

by Robert, Pickering on Twintech Heating and Cooling

Had new furnace installed and ran into some difficulties but the contractor responded in a timely and efficient manner - after further service calls were made, a reasonable resolution was found.

by Brian Burns, Whitby on Twintech Heating and Cooling

The work was done quickly efficiently neatly and professionally. Pleased with the service, information, product, and the company.

by Geoff, Port Perry on Twintech Heating and Cooling

Great sales member named Dave came in told us some amazing items and how they would be priced installed an all. We couldn’t believe it! The next day the ac was installed, that day one employee named Greg told us that our furnace was working way to hard and was causing us to use way too much gas. So two days later they came in an installed a new furnace!