The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by Lousan, Ajax on Twintech Heating and Cooling

From quote, to installation, to follow up, Twintech provided excellent service. I would highly recommended their services.

by John, Pickering on Twintech Heating and Cooling

I had a really great experience with these guys. The salesman Bob was clearly very knowledgeable about everything to do with heating and cooling a home, spent a lot of time with us going over the details of the job, never rushed us and came back after the install to make sure we were happy. The installation crew was excellent, they covered the floors all the way from outside down to the basement furnace room, kept the place clean, got the work done on time and we’re very friendly. I’ve got 15 years in the contracting/ construction industry and these guys are one of the most professional company’s I’ve dealt with. Great company!

by Debra Robertson on Twintech Heating and Cooling

Had great service and clean-up was good. Was happy with my salesman. They were very friendly and helpful. I needed a new furnace as our was over 20 years old. The furnace and air-conditioner work great and they are very quiet. I am very pleased with the service and product I received.

by Private User on Twintech Heating and Cooling

Met with Dave for the sales process and he was great about explaining and going over everything to us. The install happened very quickly and the team were super professional and friendly. We are very happy with this company and their services and we definitely recommend them to others. Thankful my sister recommended them to me!

by Private User on Twintech Heating and Cooling

Reviews for Twintech were good, and they did not disappoint. After an initial visit to discuss the suitable AC unit for replacement, an installation date was available in just a couple of days, and everything was installed without a hitch. Highly recommended

by Private User on Twintech Heating and Cooling

Very pleased with the installation of our new furnace and A/C unit. From quotation stage to the completion of the job Twintech was very professional.
Thank you for a job well done.

by Darren, Pickering on Twintech Heating and Cooling

My old water heater quit on me. I called TwinTech. In less than 4 days, I had my new water heater installed and the old one taken away. The whole process was quick, easy, pleasant, and well done. This is the third time I've dealt with TwinTech and I've been satisfied each time.

by Private User on Twintech Heating and Cooling

I had them replace my furnace last year. When it came time for the air conditioner this year, I did not hesitate to call Twintech again. I will also have them perform regular maintenance on them.

by Robert, Ajax on Twintech Heating and Cooling

We required a new HVAC replacement after running the old
system for 18 years.
Dave understood our requirements and gave us a quote that
covered all the necessary items.
Installation was fast and very tidy. Everything works as
it should. Our thanks to Greg, Mitch and others for their
excellent work. Recommend this family owned business to
anyone else, considering HVAC or other work.

by John Armstrong, Pickering on Twintech Heating and Cooling

I needed a new furnace and A/C to replace my 21 yr. old units, and went to the internet to view potential companies in May, I received 3 quotes,
and chose Twintech based on their salesman Dave who was very detailed and covered off everything on what Twintech was all about,
an extremely dedicated company with so many years of experience, and after reading the on line reviews I was sold on Twintech, who did not disappoint as the installation team were top notch with Greg leading,
I would highly recommend this company without any doubts, in my books they are first class all the way. Our new Amana furnace and A/C are working perfectly !