The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

Flawless transaction. They did exactly what they promised, showed-up on time, cleaned-up, and were highly professional. Highly recommended.

by Bill Edmondson on Twintech Heating and Cooling

Salesperson and 2 man installation team were all professional and
knew their stuff. All three were friendly and helpful, answering all
my questions. The quality of their work demonstrated their experience
and expertise in their field.

by Private User on Twintech Heating and Cooling

A dear late cousin of mine recommended this company and I have been happy with the service.

by Private User on Twintech Heating and Cooling

We are very pleased with the work done by Twintech. They were very professional from start to finish. Dave came to our home and gave us a very competitive quote for new high efficiency furnace and air conditioner. The installers were very courteous and professional. We would highly recommend them.

by W1n5t0n1987! on Twintech Heating and Cooling

Great experience getting an old furnace replaced.
Sales Guy (Dave) was great - honest, responsive, and friendly.
The work itself was done quickly and we are very happy with the outcome, thank you! We recommend TwinTech!

by Private User on Twintech Heating and Cooling

This review is late coming so my apologies to the amazing Twin Tech team! I contacted Dave at Twin Tech for a quote this past Feb (as I was collecting a few) and his recommendation was excellent. From the first meeting with Dave to the team installing the new furnace, not once did i feel uncomfortable . The team were extremely professional yet personable and clean and tidy. Decent companies still exist!
The new furnace just purrs and its just amazing the difference it has made!
(PS my sibling ended up getting a furnace from them as well)

by Private User on Twintech Heating and Cooling

The service was Twintech was excellent.
Dave our salesperson was easy to talk to and was professional. The unit recommended meets our needs and budget.
Greg and his team arrived on time for the installation and even got rid of the garbage the contractors left in our furnace.
Would definitely recommend Twintech.

by Steve V, Toronto on Twintech Heating and Cooling

Our old water tank was installed in 1997. Wasn't working as well as it should so we looked into a tankless as it is more efficient and a space saver! we had used Twintech in the past for a furnace cleaning and were satisfied with that so we decided to ask for a quote for the changeover. Gary arrived and provided the options and the quote fit within our budget so we decide to go with them after receiving a few alternative quotes from other companies. They did what the said would be done and it was completed within a reasonable time frame! Removal and cleanup of the old tank was seamless. We are now enjoying consistent and efficient Hot water! I recommend Twintech and would use them for future projects!

by New AC Unit + Humidifier on Twintech Heating and Cooling

One of the most honest HVAC companies out there! Dave was very helpful and informative in helping us choose a new AC unit. While they weren’t the lowest quote, we went with them because we trusted Dave and he was the most honest guy out of the companies that quoted us.
Greg and his crew who installed the unit were very professional and did a great job. If I could do it over again I would choose Twintech again.

by Private User on Twintech Heating and Cooling

Relocated and replaced our air conditioning unit. Fast, professional, and high quality service. We would definitely use them again for future projects!