McQuay Furnace error codes are seen in three colors, red, green, and amber/yellow. Each color will also flash a specific number of times to signify a specific error. Breaking down each color, and number of flashes, will help you solve the problem you are having with your York Furnace.


CODE: SLOW GREEN FLASH
RESULT: Normal operation

CODE: SLOW AMBER FLASH
RESULT: Normal operation with call for heat

CODE: RAPID RED FLASH
RESULT: Twinning error, incorrect 24V phasing.
FIX: Check twinning wiring. Flame sense current is below 1.5 microamps

CODE: RAPID AMBER FLASH
RESULT: Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

CODE: 4 AMBER FLASHES
RESULT: The control is receiving a "Y" signal from the thermostat without a "G" signal, indicating improper thermostat wiring.

CODE: 1 RED FLASH
RESULT: This indicates that flame was sensed when there was not a call for heat.
FIX: The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.

CODE: 2 RED FLASHES
RESULT: This indicates that the normally open pressure switch contacts are stuck in the closed position.
FIX: The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. This indicates the normally open pressure switch contact did not close after the inducer was energized.

CODE: 3 RED FLASHES
RESULT: This could be caused by a number of problems: faulty inducer, blocked vent pipe broken pressure switch hose or faulty pressure switch.

CODE: 4 RED FLASHES
RESULT: This indicates that the main limit switch has opened its normally closed contacts.
FIX: The control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 5 RED FLASHES
RESULT: This fault is indicated if the normally closed contacts in the rollout switch opens.
FIX: The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 6 RED FLASHES
RESULT: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat.
FIX: If the main blower is in a "Delay on" mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

CODE: 7 RED FLASHES
RESULT: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
FIX: Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

CODE: 8 RED FLASHES
RESULT: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle.
FIX: This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

CODE: 9 RED FLASHES
RESULT: Indicates reversed line voltage polarity or grounding problem.
FIX: Both heating and cooling operations will be affected. check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

CODE: 10 RED FLASHES
RESULT: Flame sensed with no call for heat.
FIX: Check gas valve and gas valve wiring This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes.

CODE: 11 RED FLASHES
RESULT: This condition is usually caused by a failed blower motor or blower wheel.
FIX: Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

CODE: 12 RED FLASHES
RESULT: This code indicates an open igniter circuit.
FIX: This could be a disconnected or loose wire or a cracked or broken igniter.

CODE: STEADY ON RED
RESULT: Control failure.
FIX: Replace control board.

CODE: 60-MINUTE AUTOMATIC RESET FROM LOCKOUT
RESULT: This control includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7, 8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.

CODE: IGNITION CONTROL FLAME SENSE LEVELS
RESULT: Normal flame sense current is approximately 3.7 microamps DC Low flame signal warning starts at 1.5 microamps. Low flame signal control lockout point is 0.1 microamps DC.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

Flawless transaction. They did exactly what they promised, showed-up on time, cleaned-up, and were highly professional. Highly recommended.

by Bill Edmondson on Twintech Heating and Cooling

Salesperson and 2 man installation team were all professional and
knew their stuff. All three were friendly and helpful, answering all
my questions. The quality of their work demonstrated their experience
and expertise in their field.

by Private User on Twintech Heating and Cooling

A dear late cousin of mine recommended this company and I have been happy with the service.

by Private User on Twintech Heating and Cooling

We are very pleased with the work done by Twintech. They were very professional from start to finish. Dave came to our home and gave us a very competitive quote for new high efficiency furnace and air conditioner. The installers were very courteous and professional. We would highly recommend them.

by W1n5t0n1987! on Twintech Heating and Cooling

Great experience getting an old furnace replaced.
Sales Guy (Dave) was great - honest, responsive, and friendly.
The work itself was done quickly and we are very happy with the outcome, thank you! We recommend TwinTech!

by Private User on Twintech Heating and Cooling

This review is late coming so my apologies to the amazing Twin Tech team! I contacted Dave at Twin Tech for a quote this past Feb (as I was collecting a few) and his recommendation was excellent. From the first meeting with Dave to the team installing the new furnace, not once did i feel uncomfortable . The team were extremely professional yet personable and clean and tidy. Decent companies still exist!
The new furnace just purrs and its just amazing the difference it has made!
(PS my sibling ended up getting a furnace from them as well)

by Private User on Twintech Heating and Cooling

The service was Twintech was excellent.
Dave our salesperson was easy to talk to and was professional. The unit recommended meets our needs and budget.
Greg and his team arrived on time for the installation and even got rid of the garbage the contractors left in our furnace.
Would definitely recommend Twintech.

by Steve V, Toronto on Twintech Heating and Cooling

Our old water tank was installed in 1997. Wasn't working as well as it should so we looked into a tankless as it is more efficient and a space saver! we had used Twintech in the past for a furnace cleaning and were satisfied with that so we decided to ask for a quote for the changeover. Gary arrived and provided the options and the quote fit within our budget so we decide to go with them after receiving a few alternative quotes from other companies. They did what the said would be done and it was completed within a reasonable time frame! Removal and cleanup of the old tank was seamless. We are now enjoying consistent and efficient Hot water! I recommend Twintech and would use them for future projects!

by New AC Unit + Humidifier on Twintech Heating and Cooling

One of the most honest HVAC companies out there! Dave was very helpful and informative in helping us choose a new AC unit. While they weren’t the lowest quote, we went with them because we trusted Dave and he was the most honest guy out of the companies that quoted us.
Greg and his crew who installed the unit were very professional and did a great job. If I could do it over again I would choose Twintech again.

by Private User on Twintech Heating and Cooling

Relocated and replaced our air conditioning unit. Fast, professional, and high quality service. We would definitely use them again for future projects!