The Payne gas furnace has built in diagnostics and is designed to assist with the identification and correction of faults. The furnace utilizes an LED, to describe its condition.This can be viewed through a port on the blower access panel. You can take corrective action in response to any faults indicated by the LED.


The number of short flashes of the LED represents the first digit of the two digit fault code. The number of long flashes of the LED represents the second digit of the fault code.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 11.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY- Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 12.
RESULT: BLOWER CALIBRATION LOCKOUT- Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 13.
RESULT: LIMIT SWITCH LOCKOUT- Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 14.
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours. Refer to #34.

CODE: 21.
RESULT: INVALID MODEL SELECTION- Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 22.
RESULT: SETUP ERROR- Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 23.
RESULT: INVALID BLOWER AIRFLOW SELECTION- Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 24.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind.

CODE: 31.
RESULT: Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch - Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 33.
RESULT: LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 34.
RESULT: IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 41.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE- Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 42.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE- Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 43.
RESULT: PRESSURE SWITCH CALIBRATION FAULT- Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 44.
RESULT: BLOWER CALIBRATION FAULT- Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 45.
RESULT: CONTROL CIRCUITRY LOCKOUT -Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Bill P. Whitby on Twintech Heating and Cooling

Thank you for your attention to detail regarding my purchase of a new air conditioner. Twintech arrived at the appointed time and were totally professional on the installation process completing the job quickly. PS thanks for the assistance applying for the government rebate

by Sam C, Pickering on Twintech Heating and Cooling

Dave and the guys from Twintech did a great job of installing my AC. They came on time did a nice neat job and cleaned up after themselves! Do not waste your time call Twintech first.

by Mary W, Whitby on Twintech Heating and Cooling

My AC unit was not working at all and our furnace that was still working but not giving us any trouble was over 15 years old. So I had 3 heating companies come out to give us a quote on replacing both the AC and the furnace at the same time. Two companies right away recommended that I replace both units simply because they were old. Dave from twintech however suggested that we save some money and replace the AC only because it seemed to him that the furnace was still in great shape and was running fine. He told us that he would have his technicians inspect the furnace thoroughly when they had it apart to install the AC. My husband was at home when the furnace was apart and was very impressed when the tech took him downstairs to personally show him that the furnace was in excellent working condition. He also cleaned the furnace at no extra charge. So now I have an honest heating and AC company that I can highly recommend to other home owners. Great job Thank You!

by Scott B, Whitby on Twintech Heating and Cooling

I had made the decision to replace my furnace and AC earlier this year. After meeting with several HVAC contractors I decided to go with Dave and his company. Dave was on time, polite, friendly and very professional. He took the time to answer all my questions and to explain the scope of work that would be required to do the job. The technicians arrived on time did a professional installation and completed the job on schedule. They respected my home by putting down vinyl runners to protect my floors and did a very thorough clean up. I’m very pleased with my decision to go with Dave and his team. I would highly recommend them to anyone who is considering upgrading their furnace and air conditioner.

by Mel F, Oshawa on Twintech Heating and Cooling

I have no problem in recommending Dave and the TWINTECH team to any home owner who is looking for quality heating and AC products and expert service.

by Eric Y, Greenbank on Twintech Heating and Cooling

Dave was great in helping me get the proper units for my property, as well as getting them installed. The installers arrived when they said they would, and completed the project on time, and professionally. If I needed another furnace, I would use Dave again.

by Ed B., Whitby on Twintech Heating and Cooling

I have known Greg and Grant Dainty for many years and have used their company for my house and business. I recommended them also for my parents and sister and they all have been very satisfied with the quality of work for a reasonable price. I just recently had them install a new HVAC system in an older house and was very pleased with their work. Craig in Pickering. After meeting with various heating and air conditioning contractors I was referred to Twin Tech Heating and Cooling through a family member. Greg and Grant arrived at my home and provided me with an estimate and a plan as to how they were going to remove and replace my furnace and air conditioner. On the day of install Greg and Grant arrived at my home on time and were very professional and extremely courteous as to any questions or concerns that I had. The removal and install was truly professional and the attention to detail was exactly what I was looking for. I’ve seen many installs from other contractors and I couldn’t be any happier to have had such a clean looking install. The sheet metal work, ducting and venting all look fantastic. Upon completion Greg and Grant left me feeling extremely happy and very fortunate of a job well done. Thanks again Twin Tech!!

by Floreene in Whitby on Twintech Heating and Cooling

My old furnace had finally broken down for the last time when contacted twintech to have a new furnace installed…They were prompt, knowledgeable and very reasonably priced. They did such a great job i tell all my friends and family about this company.

by Damien McIsaac. Ajax on Twintech Heating and Cooling

To whom it may concern, I recently had TwinTech (Greg and Grant Dainty) replace my furnace and service both my gas fireplaces and air conditioning unit. They were professional, courteous and very fair in their pricing. I would gladly recommend TwinTech to anyone needing work done. I can be contacted at 905-626-XXXX.

by Blair N. - Toronto on Twintech Heating and Cooling

My Fiancé and I have relied on Twintech Heating and Cooling now for the better part of the last 10 years. In that time, Greg has installed a furnace, an air conditioner, and a heat-pump at our residence in Toronto. In each instance Greg and his team were a pleasure to deal with. They were courteous and professional throughout the whole process and the quality of their work is first rate. Our experiences have always been extremely positive and we have referred his services numerous times to our friends and family. Without hesitation, I would recommend Greg and TwinTech Heating and Cooling to anyone looking to service or replace their existing heat/AC equipment