In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Elizabeth and John L from Scarborough on Twintech Heating and Cooling

In October 2018, I contacted Greg at Twintech to do a furnace cleaning. Greg discovered that my furnace, installed in 2006 by another company, had been installed incorrectly, leading to restricted air flow. The heat exchanger was also defective. As well, my furnace was too large for the size of my house.

In my opinion, the biggest concern most of us have as consumers is that we have no idea of the quality or knowledge and experience of the technicians any heating and cooling company will send into our homes. I could have avoided having my 2006 furnace installed improperly (leading to early replacement), had I known about Twintech then.

With Twintech you get it all. Because Twintech is a smaller company you can rest assured that the only technicians who will work in your home are Greg and his twin brother Grant who are co-owners and fully licensed and certified with over 30 years of experience in installing and servicing heating and cooling equipment. They are both friendly and personable and answer all your questions. Their workmanship is outstanding. We had a 2 stage, variable speed Goodman furnace installed. My wife and I noticed a difference in the heating and even temperature of our 2 storey home almost immediately. Our old furnace always heated too much on the main floor and too little upstairs. We are also impressed with how quiet the furnace is.

Twintech's office manager, David Gergley, is equally friendly and not only gave us a competitive quote to replace our furnace (we sought other quotes), but also went above and beyond my expectations when he made arrangements with an energy audit company so that we would be considered for a grant from Enbridge and IESO.

Needless to say, I give Twintech a 10 out of 10 and highly recommend them!

by James, Ajax on Twintech Heating and Cooling

Clean, Fast and Efficient Work. Between all the quotes I received Twintech was a few dollars less and offered the best warranty.

by garysumnec360, Whitby on Twintech Heating and Cooling

They did an excellent job. Everything was very well explained. At the end of the job everything was very well cleaned up.

by Glade, Pickering on Twintech Heating and Cooling

Twintech offered me a competitive price but more importantly great sales and installation service. They did everything with attention to detail and quality workmanship that is hard to find in this day and age. Dave who first game to visit me answered most of my questions and probed about my needs. For the technical/install questions he was unable to answer he quickly had Greg and Grant the owners answer for me. They did not cut corners on the installation or do anything to simply save time. They stayed into the early evening to complete the job and removed all my old components and even fixed up mistakes other workers ahd made in the past. I would highly recommend them and use them again if the need arises in the future. If you are looking for service or new equipment I would highly recommend Twintech be on your list of Heating companies to get a quote from and ask your questions to.

by Anne of Major Oaks in Pickering on Twintech Heating and Cooling

The company epitomizes high quality service: from the initial client interaction with Dave to the installation and follow up with the technical team. One of the key features I look for is the ability of a technical person to talk to and not talk down to the customer when responding to questions and I had quite a few, all of which were very professionally addressed. I was also quite impressed with the follow up service, promptness, the obvious competence of the team who left no stone un-turned to ensure I was a satisfied customer. Thank you guys.

by Aileen Johnson in Toronto on Twintech Heating and Cooling

All staff concerned were total professionals. Sales rep Dave was like having an old friend at your house. No up selling or pressure, just good honest facts and figures. The owners and assistant who installed our unit worked quietly, efficiently and left our home clean. We could not have been happier with the service and attention we were given. We are so happy a family member recommended Twintech. She said "don't call anyone else, just call them...they are amazing". And they were!!! Thank you guys for the great work!!! A. Johnson

by Lynsey from Toronto on Twintech Heating and Cooling

We are completing a large project adding an addition on to our house and couldn’t be more pleased with our decision to trust Twintech with our hvac work. They removed and replaced the furnace, installed a new A/C unit, swapped our tank water heater for a tankless unit, and completed ducting and new A/C lines through the addition. Without hesitation we would recommend Twintech to anyone.

by Oldtown in Pickering on Twintech Heating and Cooling

Honest, very personable , men of their word ,workmanship xcellent ,showed up when promised ,They do not try to up sell ,rather give good advice instead . Price was very fair in my opinion .We have a family member with a medical condition and I think they made us a priority .Very happy with these guys . (Nice guys ) Stu Leffler Ajax.

by Mike B. Toronto on Twintech Heating and Cooling

Very professional, courteous, knowledgeable staff. Sales staff (David Gergley) excellent in knowledge and getting the job setup and installation was very prompt. Greg and Peter (technicians) knew their stuff and stuck around after completion to make sure it all worked properly and that I understood how it all was installed and how the unit worked. Would highly recommend them! Thanks for a great job-house is now cool and comfortable.

by Steve S in Toronto on Twintech Heating and Cooling

I had Twintech install a brand new air condition back in June of this year and I'm very happy with their service. I have a very busy schedule so I sent out an email to 7 or 8 HVAC companies just to get an idea of what it would cost. Dave at Twintech and only one other company were able to give me an approximate quote through email. Many of the companies I reached out to didn't even respond. I decided to meet with Dave and he was very friendly and professional. He gave me a good quote for a name brand/energy efficient AC with installation from their certified technicians. It was an easy decision to go with them.

Within a week I had the unit installed and working perfectly. Their technicians were very helpful and answered all of my questions. I'll definitely be calling them back for all of my HVAC needs in the future.