In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Lousan, Ajax on Twintech Heating and Cooling

From quote, to installation, to follow up, Twintech provided excellent service. I would highly recommended their services.

by John, Pickering on Twintech Heating and Cooling

I had a really great experience with these guys. The salesman Bob was clearly very knowledgeable about everything to do with heating and cooling a home, spent a lot of time with us going over the details of the job, never rushed us and came back after the install to make sure we were happy. The installation crew was excellent, they covered the floors all the way from outside down to the basement furnace room, kept the place clean, got the work done on time and we’re very friendly. I’ve got 15 years in the contracting/ construction industry and these guys are one of the most professional company’s I’ve dealt with. Great company!

by Debra Robertson on Twintech Heating and Cooling

Had great service and clean-up was good. Was happy with my salesman. They were very friendly and helpful. I needed a new furnace as our was over 20 years old. The furnace and air-conditioner work great and they are very quiet. I am very pleased with the service and product I received.

by Private User on Twintech Heating and Cooling

Met with Dave for the sales process and he was great about explaining and going over everything to us. The install happened very quickly and the team were super professional and friendly. We are very happy with this company and their services and we definitely recommend them to others. Thankful my sister recommended them to me!

by Private User on Twintech Heating and Cooling

Reviews for Twintech were good, and they did not disappoint. After an initial visit to discuss the suitable AC unit for replacement, an installation date was available in just a couple of days, and everything was installed without a hitch. Highly recommended

by Private User on Twintech Heating and Cooling

Very pleased with the installation of our new furnace and A/C unit. From quotation stage to the completion of the job Twintech was very professional.
Thank you for a job well done.

by Darren, Pickering on Twintech Heating and Cooling

My old water heater quit on me. I called TwinTech. In less than 4 days, I had my new water heater installed and the old one taken away. The whole process was quick, easy, pleasant, and well done. This is the third time I've dealt with TwinTech and I've been satisfied each time.

by Private User on Twintech Heating and Cooling

I had them replace my furnace last year. When it came time for the air conditioner this year, I did not hesitate to call Twintech again. I will also have them perform regular maintenance on them.

by Robert, Ajax on Twintech Heating and Cooling

We required a new HVAC replacement after running the old
system for 18 years.
Dave understood our requirements and gave us a quote that
covered all the necessary items.
Installation was fast and very tidy. Everything works as
it should. Our thanks to Greg, Mitch and others for their
excellent work. Recommend this family owned business to
anyone else, considering HVAC or other work.

by John Armstrong, Pickering on Twintech Heating and Cooling

I needed a new furnace and A/C to replace my 21 yr. old units, and went to the internet to view potential companies in May, I received 3 quotes,
and chose Twintech based on their salesman Dave who was very detailed and covered off everything on what Twintech was all about,
an extremely dedicated company with so many years of experience, and after reading the on line reviews I was sold on Twintech, who did not disappoint as the installation team were top notch with Greg leading,
I would highly recommend this company without any doubts, in my books they are first class all the way. Our new Amana furnace and A/C are working perfectly !