Amana PTAC Air Conditioner Error Codes

CODE: FP.
RESULT: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.
FIX: No Action required. This setting will disengage when the room temperature rises above 43°F.

CODE: Fd.
RESULT: Front Desk switch is closed. All outputs are switched off.
FIX: Open front desk switch to allow occupant unit operation.

CODE: Eo.
RESULT: Un-Configured Service Board - All operation held awaiting configuration.
FIX: Enter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.

CODE: EH.
RESULT: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
FIX: Open front emergency hydronic switch to allow occupant unit operation.

CODE: LS.
RESULT: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.
FIX: Open load shedding switch to allow occupant unit operation.

CODE: On.
RESULT: Control is configured to respond to a wired thermostat.
FIX: No action if a wired thermostat is being used.Otherwise, see Configuration Settings.

CODE: oP.
RESULT: Open Door Lockout (DS1 & DS2 open; wireless).
FIX: Close Room Door. Unit will not condition space with door open.

CODE: nP.
RESULT: Window Switch Lockout - (LS & INN open).
FIX: Close Room Door or Window. Unit will not condition space with door or window open.

CODE: HP.
RESULT: Heat Sentinel - (WIAT > u3).
FIX: No action required. This setting will disengage when the room temperature falls.

CODE: Ur.
RESULT: Un-Rented Status (EHH & INN or wireless).
FIX: Front Desk needs to set to Rented mode (if applicable).

CODE: F1.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.

CODE: F2.
RESULT: Wireless Remote Thermostat failure.
FIX: Replace Wireless Thermostat.

CODE: F3.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor.

CODE: F4.
RESULT: Indoor Coil Thermistor either above or below operating tolerances.
FIX: Replace Red Indoor Coil Thermistor.

CODE: F5.
RESULT: Wireless Thermostat failure.
FIX: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.

CODE: F6.
RESULT: Indoor Discharge Thermistor either above or below operating tolerances.
FIX: Replace Yellow Indoor Discharge Thermistor.

CODE: Fb.
RESULT: Low Remote Battery Warning.
FIX: Replace Batteries in Wireless Devices.

CODE: H1.
RESULT: High Voltage Protection engaged. Power supply voltage is to high.
FIX: Check for incoming power at correct voltage.

CODE: br.
RESULT: Brown Out Protection engaged. Power was lost or voltage is low.
FIX: Check for incoming power at correct voltage.

CODE: L6.
RESULT: Discharge Air Too Hot.
FIX: Clean Filter or Remove Air Blockage.

CODE: LC.
RESULT: Outdoor Coil Thermistor temperature high.
FIX: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.

CODE: C2.
RESULT: Indoor Air Recirculation. Large delta between thermostat and return.
FIX: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.

CODE: C5.
RESULT: Outdoor Coil temperature too high for outdoor ambient temperature.
FIX: Check for Blocked Outdoor Air or Clean Coil.

CODE: C1.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C3.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C4.
RESULT: Indoor Coil froze up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C6.
RESULT: Poor Unit Performance.
FIX: Check for blower motor, compressor, or electric heat operation.

CODE: C7.
RESULT: Indoor Freezing Lockout (ICT - IAT > 20) +10 Min.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


See What Our Customers Are Saying:

by Lousan, Ajax on Twintech Heating and Cooling

From quote, to installation, to follow up, Twintech provided excellent service. I would highly recommended their services.

by John, Pickering on Twintech Heating and Cooling

I had a really great experience with these guys. The salesman Bob was clearly very knowledgeable about everything to do with heating and cooling a home, spent a lot of time with us going over the details of the job, never rushed us and came back after the install to make sure we were happy. The installation crew was excellent, they covered the floors all the way from outside down to the basement furnace room, kept the place clean, got the work done on time and we’re very friendly. I’ve got 15 years in the contracting/ construction industry and these guys are one of the most professional company’s I’ve dealt with. Great company!

by Debra Robertson on Twintech Heating and Cooling

Had great service and clean-up was good. Was happy with my salesman. They were very friendly and helpful. I needed a new furnace as our was over 20 years old. The furnace and air-conditioner work great and they are very quiet. I am very pleased with the service and product I received.

by Private User on Twintech Heating and Cooling

Met with Dave for the sales process and he was great about explaining and going over everything to us. The install happened very quickly and the team were super professional and friendly. We are very happy with this company and their services and we definitely recommend them to others. Thankful my sister recommended them to me!

by Private User on Twintech Heating and Cooling

Reviews for Twintech were good, and they did not disappoint. After an initial visit to discuss the suitable AC unit for replacement, an installation date was available in just a couple of days, and everything was installed without a hitch. Highly recommended

by Private User on Twintech Heating and Cooling

Very pleased with the installation of our new furnace and A/C unit. From quotation stage to the completion of the job Twintech was very professional.
Thank you for a job well done.

by Darren, Pickering on Twintech Heating and Cooling

My old water heater quit on me. I called TwinTech. In less than 4 days, I had my new water heater installed and the old one taken away. The whole process was quick, easy, pleasant, and well done. This is the third time I've dealt with TwinTech and I've been satisfied each time.

by Private User on Twintech Heating and Cooling

I had them replace my furnace last year. When it came time for the air conditioner this year, I did not hesitate to call Twintech again. I will also have them perform regular maintenance on them.

by Robert, Ajax on Twintech Heating and Cooling

We required a new HVAC replacement after running the old
system for 18 years.
Dave understood our requirements and gave us a quote that
covered all the necessary items.
Installation was fast and very tidy. Everything works as
it should. Our thanks to Greg, Mitch and others for their
excellent work. Recommend this family owned business to
anyone else, considering HVAC or other work.

by John Armstrong, Pickering on Twintech Heating and Cooling

I needed a new furnace and A/C to replace my 21 yr. old units, and went to the internet to view potential companies in May, I received 3 quotes,
and chose Twintech based on their salesman Dave who was very detailed and covered off everything on what Twintech was all about,
an extremely dedicated company with so many years of experience, and after reading the on line reviews I was sold on Twintech, who did not disappoint as the installation team were top notch with Greg leading,
I would highly recommend this company without any doubts, in my books they are first class all the way. Our new Amana furnace and A/C are working perfectly !