In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.

rheem air conditioner error codes

rheem air conditioner codes


See What Our Customers Are Saying:

by Cibele Ceroni on Twintech Heating and Cooling

Great Team! Furnace broke in the weekend, Bob visited same day and Greg installed new one on Monday. Team was professional, respectful and knowledgeable. Installation went very well, Greg found solutions to challenges, like hiding new conduits in the ceiling. Looks nice and new furnace is working great. Five Stars.

by Jackie Graham on Twintech Heating and Cooling

I used Twintech to install a new furnace for my home. Bob was terrific in explaining the sizing options and why the 2 stage furnace was the best option for me. Greg did a great job installing, clean and on time. Finished work looks great but the best part is how it works. The 2 stage heating is so much more comfortable. I run the fan continuously to keep the indoor air clean. Great investment! Would highly recommendTwintech!

by Anthony Silva on Twintech Heating and Cooling

I’m going to start this by saying I’m a very particular customer. My background is in mathematics and mechanical engineering so I have an eye for detail and a respect for technical knowledge.
Greg had already done an AC inspection and replaced a water heater tank and there was no question in my mind who to deal with replacing my rickety old furnace after it got pooched.
Bob dropped in ahead of time and clearly (and knowledgeably) outlined all technical, price and operational options.
Greg showed up on time, on the agreed date and did a fantastic job. (The OLD furnace was a house of horrors and was installed in a keystone cops sort of way- careless.)
The work Greg did was HIGHLY PROFESSIONAL and FAR MORE FUNCTIONAL than what I had.
I’m also a musician with many instruments so maintaining predictable humidity/temperature is extremely important to me. Greg recognized this as did Bob. You NEVER feel like you’re being brushed off.
In summary, if you’re looking for PROFESSIONAL, QUALITY results by an EXPERIENCED, THOUGHTFUL team
(that also happen to be FRIENDLY and ATTENTIVE ) then you’ve come to the right page!!

by Karen Morgan on Twintech Heating and Cooling

Once again Twin Tech came through and fixed my furnace. A young man by the name of Mitch came by tonight and he was so nice explained everything he was quick he was clean he turned off the lights even when he left the furnace room it’s just above and beyond Twin Tech always delivers and I just found out about them last year and I will use no one else but thanks again Mitch you are fantastic

by Richard Liu on Twintech Heating and Cooling

I had a problem with the Furnace (Armstrong ultra V) and Greg diagnosed it on the phone. Even told me what the issue was and I was able to fix it. This level of service from a Business that is almost unknown today.

If you require service, reach out to Greg. I will definitely use them in the future!

by Tony Forde on Twintech Heating and Cooling

We have been shopping for a heat pump for our home. We had 3 reps come in and make recommendations and provide a quote. Of the 3, Bob was so clearly so much more qualified, thorough and informed than the other two that the decision was a no brainer. As soon as we get our audit results Twintech will be installing our heat pump.

by Private User, Pickering on Twintech Heating and Cooling

knowledgeable sales person, did not try to up-sell unneeded features,
and was easily contacted to ensure customer satisfaction.
Installation was expertly done by friendly guys, everything explained for use of the products. Old products were removed and returned to rental company as part of the service. Follow up call was received to check all was well. This is my second time using this company as I was fully satisfied with my previous air conditioning unit installation

by Private User, Courtice on Twintech Heating and Cooling

Twintech recently installed a new furnace for me. Bob did a great job assessing what I had and needed. All details well explained including the importance of proper sizing of furnace and the value of multi stage heating and the variable speed blower. As a nurse, indoor air quality is a high priority so the variable speed motor running continuous is so good. 24/7 air cleaning. Greg did a great job on install, attention to detail so appreciated. Already notice such an improved comfort and heat. Thank you Twintech! You come as advertised. I will recommend to anyone in need of heating or cooling!

by Walter, Whitby on Twintech Heating and Cooling

We received various quotes from 4 different companies and right away, the prompt and thorough communication from Bob from TwinTech stood out. He introduced himself, sent sample sites and information, and always confirmed any agreed to dates and times.

Bob was friendly and extremely knowledgeable about the topic of HVAC and it was clear he was passionate about his profession. He approached the job as if he was installing in his own home.

Prior to the new furnace & A/C installation, our old units were loud and inefficient - having several rooms feeling too cold in the winter and too hot in the summer. After installing the recommended units, all rooms stay at a consistent temperature- even the finished basement.

I highly recommend the TwinTech team - just an outstanding job at a reasonable price point.

by Private User on Twintech Heating and Cooling

The experience with Twintech was great from the start. Bob the sales manager was friendly and professional and did not use any pressure tactics. He was very knowledgeable.
The installation was completed by the twin owners in about 6-7 hours. Clean quiet easy going didn't mind when I poked my head in to see progress. Highly recommend

Related Links:
ac repair services, furnace repairs pickering, central air conditioner services, whitby air and heating, whitby heating and air, ajax hvac repair, air conditioner repair, hvac repairs, heating repair company, house air conditioner repair, ac repair and service, whitby air conditioning, residential air conditioner repair, residential ac repair, pickering air conditioners, oshawa air conditioners, nearby ac repair, furnace repair ajax, furnace repair pickering, furnace repair oshawa, furnace repairs, furnace repair, hvac repair service, central air conditioner, ajax furnace repair, ajax air conditioners,


rheem air conditioner error codes