daikin air conditioner error codes

24 / 7 Emergency Service Available. Call Us Now: 1.844.894.6832

Durham Region Air Conditioning Repair, Service and Installation

daikin air conditioner error codes
CLICK HERE FOR A FREE QUOTATION

daikin air conditioner codes

If you're looking for help fixing your daikin air conditioner, look no further! Our comprehensive daikin air conditioner repair guide will explain common issues, provide troubleshooting tips, and show you how to read your model's error codes.


CODE: A0.
RESULT: External protection device activated. External protection device connected to the terminal strip T1-T2 of indoor unit is activated.

CODE: A1.
RESULT: Malfunction of indoor unit PCB Malfunction due to noise Defect of indoor unit PCB.

CODE: A3.
RESULT: Malfunction of drain level control system Drain piping clogging, improper drain piping work Defect of drain pump. Defect of float switch.

CODE: A4.
RESULT: Malfunction of freezing protection Shortage of water volume Low water temperature setting Defect of 26WL. Defect of water temperature thermistor.

CODE: A5.
RESULT: High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor.

CODE: A6.
RESULT: Fan motor locked, overload, overcurrent Defect of connector contact Defect of indoor unit PCB Defect of fan motor.

CODE: A7.
RESULT: Malfunction of swing flap motor Failure of swing flap motorm, Defect of indoor unit PCB Jammed swing mechanism/blade.

CODE: A8.
RESULT: Malfunction of power supply Overcurrent of AC input, Defect of power supply voltage.

CODE: A9.
RESULT: Malfunction of electronic expansion valve drive Defect of electronic expansion valve coil, Defect of indoor unit PCB, Defect of connector contact.

CODE: AA.
RESULT: Heater overheat 26WH is activated.

CODE: AF.
RESULT: Malfunction of a humidifier system Water leakage of humidifier (option), Failure of swing float switch. Improper drain piping incline.

CODE: AH.
RESULT: Malfunction of dust collector of air cleaner Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB.

CODE: AJ.
RESULT: Malfunction of capacity setting (Indoor unit PCB) Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB.

CODE: C1.
RESULT: Failure of transmission (between indoor unit PCB and fan PCB) Defect of transmission of fan motor control driver.

CODE: C4.
RESULT: Malfunction of liquid pipe thermistor for heat exchanger Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger.

CODE: C5.
RESULT: Malfunction of gas pipe thermistor for heat exchanger Defect of connector contact. Defect of gas pipe thermistor for heat exchanger.

CODE: C6.
RESULT: Malfunction of fan motor control driver Defect of fan motor sensor system Defect of fan motor control driver.

CODE: C7.
RESULT: Front panel driving motor fault Defect of front panel driving motor Defect of limit switch.

CODE: C9.
RESULT: Malfunction of suction air thermistor Defect of connector contact Defect of thermistor for suction air.

CODE: CA.
RESULT: Malfunction of discharge air thermistor Defect of connector contact. Defect of thermistor for discharge air.

CODE: CC.
RESULT: Malfunction of humidity sensor system Defect of connector contact Defect of humidity sensor.

CODE: CJ.
RESULT: Malfunction of thermostat sensor in remote controller Defect of remote controller thermistor Malfunction due to noise Defect of remote controller PCB. Outdoor Unit.

CODE: E0.
RESULT: Protection devices actuated (unified) Protection device connected to outdoor PCB actuated Defect of protection device connector contact.

CODE: E1.
RESULT: Defect of outdoor unit PCB Malfunction due to noise Defect of outdoor unit PCB?.

CODE: E3.
RESULT: Actuation of high pressure switch (HPS) Dirty outdoor unit heat exchanger and suction filter Defect of HPS Clogged refrigerant piping Defect of connector contact.

CODE: E3.
RESULT: System No.1. Actuation of high pressure switch (HPS). Dirty outdoor unit heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact Outdoor Unit.

CODE: E4.
RESULT: Actuation of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connecting connector Defect of outdoor unit PCB.

CODE: E5.
RESULT: Overheat of inverter compressor motor Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: E5.
RESULT: Inverter compressor motor lock Inverter compressor lock Incorrect wiring.

CODE: E6.
RESULT: STD compressor motor overcurrent/lock Closed stop valve STD compressor lock.

CODE: E6.
RESULT: System No.1 Compressor overcurrent Defect of EXP. valve Defect of compressor Shortage of refrigerant amount.

CODE: E7.
RESULT: Malfunction of outdoor unit fan motor. Faulty contact of fan motor connector. Defect of fan motor, Defect of fan motor driver.

CODE: E8.
RESULT: Overcurrent of inverter compressor, Defect of compressor, Defect of outdoor unit PCB Defect of inverter main circuit capacitor Defect of power transistor.

CODE: E9.
RESULT: Malfunction of electronic expansion valve coil Defect of electronic expansion valve Defect of connector contact Defect of outdoor unit PCB.

CODE: EA.
RESULT: Malfunction of four way valve Defect of four way valve Defect of outdoor unit PCB Shortage of gas Defect of thermistor.

CODE: EC.
RESULT: Malfunction of entering water temperature Malfunction of cooling water temperature. Defect of thermistor. Defect of outdoor unit PCB.

CODE: EF.
RESULT: Malfunction of thermal storage unit Defect of electronic expansion valve of thermal storage unit Defect of thermal storage PCB.

CODE: F3.
RESULT: Malfunction of discharge pipe temperature Shortage of gas. Defect of connector contact. Clogged refrigerant piping Defect fo discharge pipe thermistor.

CODE: F6.
RESULT: Abnormal high pressure in cooling Defect of outdoor unit fan motor Defect of electronic expansion valve Defect of heat exchanger thermistor, Defect of outdoor unit PCB.

CODE: F6.
RESULT: Refrigerant overcharged Refrigerant overcharged Disconnection of heat exchanger thermistor Disconnection of outdoor air thermistor Disconnection of liquid pipe thermistor.

CODE: H0.
RESULT: Malfunction of sensor system of compressor, Harness is disconnected, or defective connection Defect of PCB.

CODE: H1.
RESULT: Malfunction of humidifier unit damper, Defect of limit switch Defect of damper.

CODE: H3.
RESULT: Malfunction of high pressure switch (HPS), Defect of high pressure switch. Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H4.
RESULT: Malfunction of low pressure switch (LPS), Defect of low pressure switch Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H5.
RESULT: Malfunction of compressor motor overload thermistor Defect of connector contact. Defect of compressor motor overload thermistor.

CODE: H6.
RESULT: Malfunction of position detection sensor, Faulty contact of compress or cable. Defect of compressor, Defect of outdoor unit PCB.

CODE: H7.
RESULT: Malfunction of outdoor fan motor signal Faulty contact of fan wiring Defect of fan motor driver Defect of fan motor.

CODE: H8.
RESULT: Malfunction of compressor input (CT) system Defect of power transistor. Defect of reactor. Faulty wiring of inverter system Defect of outdoor unit PCB.

CODE: H9.
RESULT: Malfunction of outdoor air thermistor. Defect of connector contact Defect of thermistor for outdoor air.

CODE: HC.
RESULT: Malfunction of (hot) water temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of thermistor for water temperature.

CODE: HF.
RESULT: Alarm in thermal storage unit with ice Thermal storage group defective wiring Defect of setting Excess of thermal storage tank numbers.

CODE: HJ.
RESULT: Malfunction of thermal storage tank water level Low water level Defect of switch setting Water level detecting sensor failure Defect of connector contact Outdoor Unit.

CODE: J1.
RESULT: Malfunction of pressure sensor Defect of pressure sensor connector contact. Defect of pressure sensor. Defect of outdoor unit PCB.

CODE: J2.
RESULT: Malfunction of current sensor of compressor Defect of current sensor Defect of outdoor unit PCB Defect of compressor.
CODE: J3.
RESULT: Malfunction of discharge pipe thermistor. Defect of connector contact Defect of outdoor unit PCB Defect of discharge pipe thermistor.

CODE: J4.
RESULT: Malfunction of low pressure equivalent saturated temperature sensor system Defect of connector contact Defect of thermistor Defect of outdoor unit PCB (Multi-split, Super-multi ).

CODE: J5.
RESULT: Malfunction of suction pipe thermistor Defect of connector contact Defect of outdoor unit PCB Defect of suction pipe thermistor.

CODE: J6.
RESULT: Malfunction of heat exchanger thermistor Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: J7.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J8.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J9.
RESULT: Malfunction of gas pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of gas pipe thermistor.

CODE: JA.
RESULT: Malfunction of high pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of high pressure sensor.

CODE: JC.
RESULT: Malfunction of low pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of low pressure sensor.

CODE: JE.
RESULT: Malfunction of sub-tank thermistor Defect of connector contact Defect of outdoor unit PCB Defect of sub-tank thermistor.

CODE: JF.
RESULT: Malfunction of heating thermistor for heat exchanger Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: JH.
RESULT: Malfunction of oil temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of oil temperature thermistor.

CODE: L0.
RESULT: Malfunction of inverter system Shortage of power supply capacity Defect of inverter PCB Defect of power transistor.

CODE: L1.
RESULT: Malfunction of inverter PCB Defect of compressor wiring Blown fuse Defect of outdoor unit fan motor Defect of inverter PCB.

CODE: L3.
RESULT: Electrical box temperature rise Fin temperature rise due to short-circuit Defect of power transistor Defect of outdoor unit fan Defect of outdoor unit PCB.

CODE: L4.
RESULT: Malfunction of inverter radiating fin temperature rise Fin temperature rise due to short-circuit Defect of fin thermistor.

CODE: L5.
RESULT: Inverter instantaneous overcurrent (DC) Closed stop valve Defect of compressor.

CODE: L6.
RESULT: Inverter instantaneous overcurrent (AC) Overcharge of refrigerant amount Defect of compressor Shortage of power supply capacity Defect of inverter unit.

CODE: L8.
RESULT: Overcurrent of inverter compressor Abnormal high pressure rise due to clogged refrigerant circuit and others Defect of compressor.

CODE: L9.
RESULT: Malfunction of inverter compressor startup Faulty of pressure equalization Defect of compressor wiring Defect of compressor.

CODE: LA.
RESULT: Malfunction of power transistor Defect of power transistor Defect of inverter PCB Defect of compressor.

CODE: LC.
RESULT: Malfunction of transmission between outdoor unit PCB and micro-computer Defect of grounding connection Defect of outdoor unit PCB Malfunction due to noise.

CODE: LC.
RESULT: Malfunction of transmission between control and inverter PCB Defect of connector contact Defect of inverter PCB Malfunction due to noise Defect of outdoor unit control PCB.

CODE: P0.
RESULT: Shortage of refrigerant amount (thermal storage unit) Shortage of refrigerant Clogged refrigerant piping Outdoor Unit.

CODE: P1.
RESULT: Power voltage imbalance, open phase Open phase Voltage imbalance between phases Faulty main circuit capacitor. Defect of wiring contact.

CODE: P2.
RESULT: Automatic refrigerant charge operation stop Closed stop valve. Closed valve of refrigerant tank.

CODE: P3.
RESULT: Malfunction of thermistor in electrical box Electrical box temperature rise (ambient temperature rise) Defect of fin thermistor, Defect of outdoor unit PCB.

CODE: P4.
RESULT: Malfunction of radiating fin temperature sensor Defect of radiating fin thermistor Defect of wiring contact Defect of outdoor unit PCB.

CODE: P8.
RESULT: Heat exchanger freezing protection during automatic refrigerant charging (Close the refrigerant cylinder. Start again from step 1.).

CODE: P9.
RESULT: Malfunction of fan motor (humidifier unit) Defect of fan motor Broken relay harness Defect of outdoor unit PCB Defect of connector contact.

CODE: P9.
RESULT: Automatic refrigerant charge operation completed.

CODE: PA.
RESULT: Broken wire of heater (humidifier unit) Defect of heater unit Defect of outdoor unit PCB Defect of thermistor.

CODE: PA.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of master unit is empty.

CODE: PC.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 2 is empty.

CODE: PE.
RESULT: Automatic refrigerant charge operation nearly completed.

CODE: PH.
RESULT: Malfunction of temperature (humidifier unit) Defect of heater unit Defect of thermistor Defect of connector contact Defect of outdoor unit PCB.

CODE: PH.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 1 is empty.

CODE: PJ.
RESULT: Malfunction of capacity setting (Outdoor unit PCB) Capacity setting adaptor is not installed Improper capacity setting adaptor Defect of outdoor unit PCB.

CODE: PJ.
RESULT: Improper combination between inverter and fan driver Mistake of inverter PCB Mistake of control PCB Mistake of inverter fan PCB System.

CODE: U0.
RESULT: Shortage of refrigerant Shortage of refrigerant Closed stop valve Clogged refrigerant piping.

CODE: U1.
RESULT: Reverse phase, open phase Reverse phase, open phase of power wiring Wrong wiring. Defect of outdoor unit PCB.

CODE: U2.
RESULT: Defect of power supply voltage or instantaneous power failure. Defect of power supply voltage Instantaneous power failure Defect of wiring contact.

CODE: U3.
RESULT: Check operation not executed. Check operation not executed.

CODE: U3.
RESULT: Malfunction of transmission Malfunction due to noise Defect of outdoor unit PCB Wrong wiring.

CODE: U4.
RESULT: Malfunction of transmission between indoor and outdoor unit Defect or indoor-outdoor transmission wiring Malfunction due to noise Defect of indoor unit PCB and outdoor unit PCB.

CODE: U5.
RESULT: Malfunction of transmission between indoor unit and remote controller Defect of remote controller wiring Defect of indoor unit PCB Malfunction due to noise Defect of remote controller main/sub setting.

CODE: U6.
RESULT: Malfunction of transmission between indoor units Faulty wiring Defect of indoor unit PCB Malfunction due to noise.

CODE: U7.
RESULT: Malfunction of transmission between main body micro-computer. INV micro-computer Harness disconnection/broken wire between PCB Defect of outdoor unit PCB.

CODE: U7.
RESULT: Malfunction of transmission between outdoor units Defect of wiring between outdoor units Defect of outdoor unit switch setting Defect of wiring between outdoor thermal storage units.

CODE: U8.
RESULT: Malfunction of transmission between remote controllers Defect of remote controller main/sub setting Defect of remote controller wiring. Defect of remote controller PCB Others.

CODE: 77.
RESULT: System No. 1 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 78.
RESULT: System No. 2 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 7A.
RESULT: System No. 2 Malfunction of current sensor of compressor Defect of current sensor. Defect of compressor Defect of outdoor unit PCB.

CODE: 7C.
RESULT: System No. 2 Malfunction of pump inter lock Cooling water pump interlock actuated.

CODE: 80.
RESULT: Malfunction of entering water temperature thermistor. Defect of connector contact. Defect of entering water temperature thermistor.

CODE: 81.
RESULT: Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 82.
RESULT: System No. 1 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 83.
RESULT: System No. 2 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 84.
RESULT: System No. 1 Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 85.
RESULT: System No. 2. Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 86.
RESULT: System No. 2. Malfunction of discharge pipe thermistor. Defect of connecting connector Defect of discharge pipe thermistor.

CODE: 88.
RESULT: System No. 2. Malfunction of discharge pipe temperature. Shortage of gas. Defect of discharge pipe thermistor Defect of connector contact. Clogged refrigerant piping.

CODE: 89.
RESULT: Malfunction of brazed-plate heat exchanger freezing Dirty heat exchanger. Shortage of refrigerant amount Defect of thermistor.

CODE: 8A.
RESULT: System No. 2 Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 8E.
RESULT: System No. 1 Malfunction of suction pipe thermistor 1 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8F.
RESULT: System No. 1 Malfunction of suction pipe thermistor 2 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8H.
RESULT: Abnormal high hot water temperature Three-way valve malfunction. Defect of thermistor Defect of water temperature setting.

CODE: 90.
RESULT: Abnormal chilled water quantity, abnormal AXP. Shortage of water volume Disconnection of AXP.

CODE: 91.
RESULT: System No. 2 Malfunction of electronic expansion valve Defect of connector contact Defect of electronic expansion valve coil.

CODE: 92.
RESULT: System No. 2 Malfunction of suction pipe thermistor Defect of connector contact Defect of suction pipe thermistor.

CODE: 94.
RESULT: Malfunction of transmission (between heat reclaim ventilation unit and fan unit) Defect of fan unit PCB Defect of connecting wire between (1) and (2).

CODE: 95.
RESULT: System No. 1 Malfunction of inverter system Defect of fan inverter unit.

CODE: 96.
RESULT: System No. 2 Malfunction of inverter system Defect of fan inverter unit.

CODE: 97.
RESULT: Malfunction of thermal storage unit Defect of thermal storage unit.

CODE: 98.
RESULT: Malfunction of thermal storage brine pump Actuation of thermal storage brine pump overcurrent (OC).

CODE: 99.
RESULT: Malfunction of thermal storage brine tank Low water level of thermal storage brine tank System.

CODE: U9.
RESULT: Malfunction of transmission (other system) Defect of communication between other indoor unit and outdoor unit Other indoor unit electronic expansion valve failure.

CODE: UA.
RESULT: Defect of indoor/outdoor power supply Wrong model connections Wrong PCB connected Improper power supply Defect of PCB.

CODE: UA.
RESULT: Malfunction of field setting Malfunction of field setting by remote controller Defect of remote controller wiring Defective connection of optional device Defect of indoor unit PCB.

CODE: UA.
RESULT: Improper combination of indoor and outdoor units Excess of connected indoor units Malfunction of field setting Uncanceled service mode. Defect of outdoor unit PCB.

CODE: UA.
RESULT: Remote temperature setting wire disconnection Remote temperature setting wire disconnection Defect of connector contact.

CODE: UC.
RESULT: Malfunction of setting of centralized controller address. Address duplication of centralized controller.

CODE: UE.
RESULT: Malfunction of transmission between indoor unit and centralized controller Malfunction of wiring between indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB.

CODE: UF.
RESULT: Wiring and piping mismatch Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units.

CODE: UH.
RESULT: Malfunction of system Improper connection of transmission wiring between indoor- outdoor units and outdoor-outdoor units Defect of indoor and outdoor unit PCB (RA: Mismatching indoor and outdoor units, Defect of voltage, Freeze protection in other indoor unit (k).

CODE: UJ.
RESULT: Malfunction of transmission (Accessory devices) Defect of accessory devices Faulty wiring.

CODE: M1.
RESULT: Malfunction of centralized remote controller PCB. Defect of centralized remote controller PCB.

CODE: M8.
RESULT: Malfunction of transmission between optional controllers for centralized control Other centralized control power disconnection Centralized control reset switch ON Defect of transmission wiring. Central remote controller address change.

CODE: MA.
RESULT: Improper combination of optional controllers for centralized control Improper combination of optional controllers for centralized control More than one master controller is connected Faulty setting of centralized control Defect of centralized control.

CODE: MC.
RESULT: Address duplication, improper setting Address duplication of central remote controller.

CODE: 60.
RESULT: External protection device actuated Actuation of external protection device Defect of output signal wiring Defect of control PCB.

CODE: 64.
RESULT: Malfunction of indoor air thermistor Defect of connecting connector Defect of thermistor for indoor air Defect of control PCB.

CODE: 65.
RESULT: Malfunction of outdoor air thermistor Defect of connector contact Defect of control PCB Defect of outdoor air thermistor.

CODE: 6A.
RESULT: Malfunction of damper system Defect of connector contact Defect of damper motor Defect of limit switch Defect of control PCB.

CODE: 70.
RESULT: System No. 2 Compressor overload Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: 71.
RESULT: System No. 2 Compressor overcurrent Shortage of refrigerant amount Short-circuit Defect of compressor.

CODE: 72.
RESULT: System No. 2 Fan motor overcurrent Defect of fan motor connector contact Defect of fan motor Defect of PCB.

CODE: 73.
RESULT: System No. 2 Malfunction of high pressure (HPS) actuated Dirty heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact.

CODE: 74.
RESULT: System No. 2 Malfunction of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connector contact Defect of LPS.

CODE: 75.
RESULT: System No. 2 Malfunction of low pressure sensor Defect of connector contact Defect of PCB Defect of low pressure sensor.

CODE: 76.
RESULT: System No. 2 Malfunction of high pressure sensor Defect of connector contact Defect of PCB Defect of high pressure sensor.

daikin air conditioner error codes

daikin air conditioner codes


See What Our Customers Are Saying:

by Cibele Ceroni on Twintech Heating and Cooling

Great Team! Furnace broke in the weekend, Bob visited same day and Greg installed new one on Monday. Team was professional, respectful and knowledgeable. Installation went very well, Greg found solutions to challenges, like hiding new conduits in the ceiling. Looks nice and new furnace is working great. Five Stars.

by Jackie Graham on Twintech Heating and Cooling

I used Twintech to install a new furnace for my home. Bob was terrific in explaining the sizing options and why the 2 stage furnace was the best option for me. Greg did a great job installing, clean and on time. Finished work looks great but the best part is how it works. The 2 stage heating is so much more comfortable. I run the fan continuously to keep the indoor air clean. Great investment! Would highly recommendTwintech!

by Anthony Silva on Twintech Heating and Cooling

I’m going to start this by saying I’m a very particular customer. My background is in mathematics and mechanical engineering so I have an eye for detail and a respect for technical knowledge.
Greg had already done an AC inspection and replaced a water heater tank and there was no question in my mind who to deal with replacing my rickety old furnace after it got pooched.
Bob dropped in ahead of time and clearly (and knowledgeably) outlined all technical, price and operational options.
Greg showed up on time, on the agreed date and did a fantastic job. (The OLD furnace was a house of horrors and was installed in a keystone cops sort of way- careless.)
The work Greg did was HIGHLY PROFESSIONAL and FAR MORE FUNCTIONAL than what I had.
I’m also a musician with many instruments so maintaining predictable humidity/temperature is extremely important to me. Greg recognized this as did Bob. You NEVER feel like you’re being brushed off.
In summary, if you’re looking for PROFESSIONAL, QUALITY results by an EXPERIENCED, THOUGHTFUL team
(that also happen to be FRIENDLY and ATTENTIVE ) then you’ve come to the right page!!

by Karen Morgan on Twintech Heating and Cooling

Once again Twin Tech came through and fixed my furnace. A young man by the name of Mitch came by tonight and he was so nice explained everything he was quick he was clean he turned off the lights even when he left the furnace room it’s just above and beyond Twin Tech always delivers and I just found out about them last year and I will use no one else but thanks again Mitch you are fantastic

by Richard Liu on Twintech Heating and Cooling

I had a problem with the Furnace (Armstrong ultra V) and Greg diagnosed it on the phone. Even told me what the issue was and I was able to fix it. This level of service from a Business that is almost unknown today.

If you require service, reach out to Greg. I will definitely use them in the future!

by Tony Forde on Twintech Heating and Cooling

We have been shopping for a heat pump for our home. We had 3 reps come in and make recommendations and provide a quote. Of the 3, Bob was so clearly so much more qualified, thorough and informed than the other two that the decision was a no brainer. As soon as we get our audit results Twintech will be installing our heat pump.

by Private User, Pickering on Twintech Heating and Cooling

knowledgeable sales person, did not try to up-sell unneeded features,
and was easily contacted to ensure customer satisfaction.
Installation was expertly done by friendly guys, everything explained for use of the products. Old products were removed and returned to rental company as part of the service. Follow up call was received to check all was well. This is my second time using this company as I was fully satisfied with my previous air conditioning unit installation

by Private User, Courtice on Twintech Heating and Cooling

Twintech recently installed a new furnace for me. Bob did a great job assessing what I had and needed. All details well explained including the importance of proper sizing of furnace and the value of multi stage heating and the variable speed blower. As a nurse, indoor air quality is a high priority so the variable speed motor running continuous is so good. 24/7 air cleaning. Greg did a great job on install, attention to detail so appreciated. Already notice such an improved comfort and heat. Thank you Twintech! You come as advertised. I will recommend to anyone in need of heating or cooling!

by Walter, Whitby on Twintech Heating and Cooling

We received various quotes from 4 different companies and right away, the prompt and thorough communication from Bob from TwinTech stood out. He introduced himself, sent sample sites and information, and always confirmed any agreed to dates and times.

Bob was friendly and extremely knowledgeable about the topic of HVAC and it was clear he was passionate about his profession. He approached the job as if he was installing in his own home.

Prior to the new furnace & A/C installation, our old units were loud and inefficient - having several rooms feeling too cold in the winter and too hot in the summer. After installing the recommended units, all rooms stay at a consistent temperature- even the finished basement.

I highly recommend the TwinTech team - just an outstanding job at a reasonable price point.

by Private User on Twintech Heating and Cooling

The experience with Twintech was great from the start. Bob the sales manager was friendly and professional and did not use any pressure tactics. He was very knowledgeable.
The installation was completed by the twin owners in about 6-7 hours. Clean quiet easy going didn't mind when I poked my head in to see progress. Highly recommend

Related Links:
ac repair services, furnace repairs pickering, central air conditioner services, whitby air and heating, whitby heating and air, ajax hvac repair, air conditioner repair, hvac repairs, heating repair company, house air conditioner repair, ac repair and service, whitby air conditioning, residential air conditioner repair, residential ac repair, pickering air conditioners, oshawa air conditioners, nearby ac repair, furnace repair ajax, furnace repair pickering, furnace repair oshawa, furnace repairs, furnace repair, hvac repair service, central air conditioner, ajax furnace repair, ajax air conditioners,


daikin air conditioner error codes