The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.


CODE: On solid, no flash.
RESULT: None.
FIX: Normal operation.

CODE: Rapid continuous flashing.
RESULT: Standard Thermostat Control 288ANA/180ANA only.
FIX: Unit being controlled by standard thermostat inputs instead of Evolution Control. Only high stage operation is aveliable. This operating mode should be used in emergency situations only.

CODE: 1 pause.
RESULT: None.
FIX: Normal operation.

CODE: 2 pause.
RESULT: None.
FIX: Normal operation.

CODE: 16.
RESULT: System Communications Failure.
FIX: Communication with User Interface lost. Check wiring to UI, indoor and outdoor units.

CODE: 25.
RESULT: Invalid Model Plug.
FIX: Control does not detect a model plug or detects an invalid model plug. Unit will not operate without correct model plug.

CODE: 31.
RESULT: High Pressure Switch Open.
FIX: High - pressure switch trip. Check refrigerant charge, outdoor fan operating and coils for airflow restrictions.

CODE: 32.
RESULT: Low Pressure Switch Open.
FIX: Low - pressure switch trip. Check refrigerant charge and indoor air flow.

CODE: 45.
RESULT: Control Fault.
FIX: Outdoor unit control board has failed. Control board needs to be replaced.

CODE: 46.
RESULT: Brown Out (230v).
FIX: Line voltage < 187v for at least 4 seconds.

CODE: 47.
RESULT: No 230v at Unit Measured at L1 and L2 on circuit board.
FIX: There is no 230v at the contactor when indoor unit is powered and cooling/heating demand exists.

CODE: 53.
RESULT: Outdoor Air Temp Sensor Fault.
FIX: Outdoor air sensor not reading or out of range.

CODE: 55.
RESULT: Outdoor Coil Sensor Fault.
FIX: Coil sensor not reading or out of range. Ohm out sensor and check wiring.

CODE: 56.
RESULT: Thermistors out of range.
FIX: Improper relationship between coil sensor and outdoor air sensor. Ohm out sensor and check wiring.

CODE: 71.
RESULT: Low Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 72.
RESULT: High Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 73.
RESULT: Contactor Shorted.
FIX: Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring error.

CODE: 74.
RESULT: No 230v at Compressor.
FIX: Compressor voltage not sensed when compressor should be starting. Contactor may be stuck open or there is a wiring error.

CODE: 75.
RESULT: Low Stage Did Not Start.
FIX: Specified start voltage at VR terminal was not achieved in low stage. Start relay was de-energized after 1 second.

CODE: 76.
RESULT: Low Stage Did Not Start 3 times.
FIX: For 3 consecutive low stage starts, the specified start voltage at VR terminal was not achieved and start relay was de-energized. Low stage locked out for 30 minutes.

CODE: 77.
RESULT: High Stage Did Not Start.
FIX: Specified start voltage at VS terminal was not achieved in high stage. Start relay was de-energized after 1 second.

CODE: 78.
RESULT: High Stage Did Not Start 3 times.
FIX: For 3 consecutive high stage starts, the specified start voltage at VS terminal was not achieved and start relay was de-energized. High stage locked out for 30 minutes.

CODE: 81.
RESULT: Low Stage Thermal Lockout.
FIX: Thermal cutout occurs in three consecutive low/high stage cycles. Low stage locked out 4 hours or until 24v power recycled.

CODE: 82.
RESULT: High Stage Thermal Lockout.
FIX: Thermal Lockout occurs in three consecutive high/low stage cycles. High stage locked out for 4 hours or until 24V power recycled.

bryant air conditioner error codes

bryant air conditioner codes


See What Our Customers Are Saying:

by Cibele Ceroni on Twintech Heating and Cooling

Great Team! Furnace broke in the weekend, Bob visited same day and Greg installed new one on Monday. Team was professional, respectful and knowledgeable. Installation went very well, Greg found solutions to challenges, like hiding new conduits in the ceiling. Looks nice and new furnace is working great. Five Stars.

by Jackie Graham on Twintech Heating and Cooling

I used Twintech to install a new furnace for my home. Bob was terrific in explaining the sizing options and why the 2 stage furnace was the best option for me. Greg did a great job installing, clean and on time. Finished work looks great but the best part is how it works. The 2 stage heating is so much more comfortable. I run the fan continuously to keep the indoor air clean. Great investment! Would highly recommendTwintech!

by Anthony Silva on Twintech Heating and Cooling

I’m going to start this by saying I’m a very particular customer. My background is in mathematics and mechanical engineering so I have an eye for detail and a respect for technical knowledge.
Greg had already done an AC inspection and replaced a water heater tank and there was no question in my mind who to deal with replacing my rickety old furnace after it got pooched.
Bob dropped in ahead of time and clearly (and knowledgeably) outlined all technical, price and operational options.
Greg showed up on time, on the agreed date and did a fantastic job. (The OLD furnace was a house of horrors and was installed in a keystone cops sort of way- careless.)
The work Greg did was HIGHLY PROFESSIONAL and FAR MORE FUNCTIONAL than what I had.
I’m also a musician with many instruments so maintaining predictable humidity/temperature is extremely important to me. Greg recognized this as did Bob. You NEVER feel like you’re being brushed off.
In summary, if you’re looking for PROFESSIONAL, QUALITY results by an EXPERIENCED, THOUGHTFUL team
(that also happen to be FRIENDLY and ATTENTIVE ) then you’ve come to the right page!!

by Karen Morgan on Twintech Heating and Cooling

Once again Twin Tech came through and fixed my furnace. A young man by the name of Mitch came by tonight and he was so nice explained everything he was quick he was clean he turned off the lights even when he left the furnace room it’s just above and beyond Twin Tech always delivers and I just found out about them last year and I will use no one else but thanks again Mitch you are fantastic

by Richard Liu on Twintech Heating and Cooling

I had a problem with the Furnace (Armstrong ultra V) and Greg diagnosed it on the phone. Even told me what the issue was and I was able to fix it. This level of service from a Business that is almost unknown today.

If you require service, reach out to Greg. I will definitely use them in the future!

by Tony Forde on Twintech Heating and Cooling

We have been shopping for a heat pump for our home. We had 3 reps come in and make recommendations and provide a quote. Of the 3, Bob was so clearly so much more qualified, thorough and informed than the other two that the decision was a no brainer. As soon as we get our audit results Twintech will be installing our heat pump.

by Private User, Pickering on Twintech Heating and Cooling

knowledgeable sales person, did not try to up-sell unneeded features,
and was easily contacted to ensure customer satisfaction.
Installation was expertly done by friendly guys, everything explained for use of the products. Old products were removed and returned to rental company as part of the service. Follow up call was received to check all was well. This is my second time using this company as I was fully satisfied with my previous air conditioning unit installation

by Private User, Courtice on Twintech Heating and Cooling

Twintech recently installed a new furnace for me. Bob did a great job assessing what I had and needed. All details well explained including the importance of proper sizing of furnace and the value of multi stage heating and the variable speed blower. As a nurse, indoor air quality is a high priority so the variable speed motor running continuous is so good. 24/7 air cleaning. Greg did a great job on install, attention to detail so appreciated. Already notice such an improved comfort and heat. Thank you Twintech! You come as advertised. I will recommend to anyone in need of heating or cooling!

by Walter, Whitby on Twintech Heating and Cooling

We received various quotes from 4 different companies and right away, the prompt and thorough communication from Bob from TwinTech stood out. He introduced himself, sent sample sites and information, and always confirmed any agreed to dates and times.

Bob was friendly and extremely knowledgeable about the topic of HVAC and it was clear he was passionate about his profession. He approached the job as if he was installing in his own home.

Prior to the new furnace & A/C installation, our old units were loud and inefficient - having several rooms feeling too cold in the winter and too hot in the summer. After installing the recommended units, all rooms stay at a consistent temperature- even the finished basement.

I highly recommend the TwinTech team - just an outstanding job at a reasonable price point.

by Private User on Twintech Heating and Cooling

The experience with Twintech was great from the start. Bob the sales manager was friendly and professional and did not use any pressure tactics. He was very knowledgeable.
The installation was completed by the twin owners in about 6-7 hours. Clean quiet easy going didn't mind when I poked my head in to see progress. Highly recommend

Related Links:
ac repair services, furnace repairs pickering, central air conditioner services, whitby air and heating, whitby heating and air, ajax hvac repair, air conditioner repair, hvac repairs, heating repair company, house air conditioner repair, ac repair and service, whitby air conditioning, residential air conditioner repair, residential ac repair, pickering air conditioners, oshawa air conditioners, nearby ac repair, furnace repair ajax, furnace repair pickering, furnace repair oshawa, furnace repairs, furnace repair, hvac repair service, central air conditioner, ajax furnace repair, ajax air conditioners,


bryant air conditioner error codes