armstrong air conditioner error codes
CLICK HERE FOR A FREE QUOTATION

armstrong air conditioner codes

Armstrong Air is the professional's choice in home heating & cooling. Including oil & gas furnaces, air conditioners, heat pumps, package units & air handlers.


CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

armstrong air conditioner error codes

armstrong air conditioner codes


See What Our Customers Are Saying:

by Linda, Toronto on Twintech Heating and Cooling

My 19 year old furnace stopped working when the cold weather hit in November, and I was left without heat. I interviewed several companies and found TWINTECH HEATING and COOLING to be very knowledgeable, quick to respond to my inquiries and very competitively priced.
Dave provided all of the information and pricing ahead of time and set up the appointment for the installation. Greg and Mitch arrived on time to do the installation and worked quickly and efficiently to complete the job.
After the completion of the installation, Dave followed up to ensure that everything was working well and that I didn't have any concerns.
Overall, this was a low-stress and flawless experience from start to finish. I would highly recommend TWINTECH HEATING and COOLING to anyone that requires a new furnace.

by Sean, Whitby on Twintech Heating and Cooling

Our 20 year old furnace broke down during the first cold weekend this past November and our usual HVAC company never returned our phone call. Their loss, missing out on a sale since we didn't want to spend much fixing an old furnace and our 40 year old air conditioner was also long overdue for replacement. We proceeded in obtaining three different quotes for furnace and air conditioner replacement, and proceeded with the one we received from Twintech.


Dave was friendly, knowledgable and accomodating to our schedule and provided with us with a price that fell in the middle of the three quotes that we had. We felt that the Amana furnace and air conditioner he quoted us on were the best products and value offered to us and felt most comfortable with the professionalism and reputation of Twintech.


Greg, Grant and Mitch were at our house for installation the day after we decided to proceed. The guys were friendly and informative, the job was completed efficiently and workmanship appears excellent. Our house is certainly much more comfortable with the new two-stage variable speed Amana furnace compared to the old clunker! And, we're looking forward to enjoying the new air conditioner once summer rolls around again. Thanks Twintech!

by Bill, Oshawa on Twintech Heating and Cooling

We are very happy with our new furnace. The service was excellent the guys worked 6 hours straight through and there was no mess at all they took the old furnace box’s etc with them they then explained everything to us they were very helpful and pleasant , when we need a new air conditioner we know who to call!

by Ken, Bomanville on Twintech Heating and Cooling

The crew from sales to installation was very professional and had great attention to detail

by Tracy, Pickering on Twintech Heating and Cooling

We couldn’t have been more impressed with Twintech - from our first service call with Mitch who took the time to thoroughly diagnose the issue with our furnace, to Dave who proposed a well thought out solution to meet our needs and finally Greg and team who acted quickly to install given we had no heat.


We did our due diligence by soliciting quotes from alternate providers and were shocked and disappointed by the aggressive and manipulative tactics used.


Twintech was honest in their approach, detailed in their product knowledge, reasonably priced, diligent in their follow-up and valued our business.


Well done Twintech! You made this a positive experience for us and our new furnace works beautifully!

by Skapoor, Ajax on Twintech Heating and Cooling

We recently purchased an Amana high efficiency furnace and humdifier through Twintech. The work was completed very professionally and the quality of the workmanship was high. There was some additional sheet metal work required to complete the installation, which they were able to complete themselves. Overall I am very pleased with the work and would highly recommend Twintech for a furnace replacement.

by Steve, Oshawa on Twintech Heating and Cooling

We were very pleased with every aspect of the work that was done. They were very professional and polite. They arrived when they said they would and job was completed on estimated time


We would highly recommend them to whoever needed a recommendation


We have a very large dog and they were very understanding and respectful of him being around

by Patrick, Toronto on Twintech Heating and Cooling

The blower on our furnace stopped working leaving us with a cold house. Dave from TwinTech responded immediately to our HomeStars service request. From beginning to end Dave was nothing but helpful, friendly and professional, he did a great job of walking us through the quote and scope of work.


The replacement of the furnace went smoothly. The Guys did a great job, everyone was very friendly and polite. There were no hiccups, or unexpected costs. The only surprise was they left the work area cleaner than it was before they started.


Was a great experience with the whole TwinTech team. Its been a couple of months since the new furnace has been installed and its working great!

by Ed, Whitby on Twintech Heating and Cooling

I heard about TwinTech when researching new furnaces at furnaceprices.ca. After contacting them about my broken down furnace, Dave came to my house the next day to assess my situation and requirements for a new furnace. He recommended one that had stainless steel heat exchangers which sold me since my previous furnace had issues with a rusted secondary heat exchanger that had to be replaced. Dave also set me up with an appointment with an energy audit company so that I could take advantage of a rebate to help improve the energy efficiency of my home and get some money back. A few days later, Greg, Grant, and Mitch came to install the new furnace and remove the old one. When delivering and removing the furnaces, they were very careful not to damage my floors and walls, and even laid out red carpeting to protect the floors. They were very friendly and professional. The installation was completed in the time they said it would take and they cleaned up their work areas. Within a week, Dave called to follow-up to see how everything was going. I have already recommended them to several friends and family members who may need new furnaces soon.

by Fred, Toronto on Twintech Heating and Cooling

Twintech did a great job, from Dave the Sales Rep to the Office staff and The Professional Technicians who did the installation. They were professional, courteous, knowledgable and informative. From beginning to follow up we were completely satisfied with everything. Thanks Again. Sincerely The Laytons

Related Links:
ac repair services, furnace repairs pickering, central air conditioner services, whitby air and heating, whitby heating and air, ajax hvac repair, air conditioner repair, hvac repairs, heating repair company, house air conditioner repair, ac repair and service, whitby air conditioning, residential air conditioner repair, residential ac repair, pickering air conditioners, oshawa air conditioners, nearby ac repair, furnace repair ajax, furnace repair pickering, furnace repair oshawa, furnace repairs, furnace repair, hvac repair service, central air conditioner, ajax furnace repair, ajax air conditioners,


armstrong air conditioner error codes