mrcool air conditioner codes

With this A/C troubleshooting guide, you can find problems with your system, fix it yourself. We will guide you through the process of identifying the problem and repairing your air conditioner.


Fault Display on the Dual 8 Numeral Tube of Outdoor Mainboard

CODE: E1.
RESULT: Actuation of high pressure switch.
FIX: Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E3.
RESULT: Actuation of low pressure switch.
FIX: When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than 3sec and the system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E4.
RESULT: Air discharge high temperature protection of compressor.
FIX: The exhaust temperature is higher than 125C for more than 5sec, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5 sec, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: F2.
RESULT: Malfunction of condenser temperature thermistor.
FIX: Malfunction of condenser temperature thermistor is detected when there is a short circuit or an open circuit in the condenser temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F3.
RESULT: Malfunction of outdoor ambient temperature thermistor.
FIX: Malfunction outdoor ambient temperature thermistor is detected when there is a short circuit or an open circuit in the outdoor ambient temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F4.
RESULT: Malfunction of Exhaust Temp. Sensor.
FIX: If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 2 minutes or short circuit 5 seconds successively at any time .The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

CODE: ON.
RESULT: Normal operation.
FIX: Unit operating normally or in standby mode.

CODE: H1.
RESULT: Defrost operation.
FIX 1: Power problem. Check control transformer power (24V). If power is available to demand control board and LED(s) do not light, replace control board.
FIX 2: Actuation of high pressure switch. Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 3: Actuation of low pressure switch. When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than3sec and the system will be shut down..The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 4: Air discharge high-temperature protection of compressor. The exhaust temperature is higher than 125C for more than 5s, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5s, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 5: Malfunction of exhaust Temp. Sensor. If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 3 minutes or short circuit 5 seconds successively at any time The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

mrcool air conditioner error codes

mrcool air conditioner codes


See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

by Trevor Owens on Twintech Heating and Cooling

I returned from vacation to find my AC unit on the Fritz. After calling way too many places I connected with TwinTech. I’ve used the company in the past for my furnace so I was happy when I recognized Greg at my front door. He’s great and the service is always top notch. I’d highly recommend using twintech for honest, superior service in the Durham region. Thanks!

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

by Courtney Parkes on Twintech Heating and Cooling

Just hired TwinTech Heating & Cooling to do an A/C Unit removal & reinstall to allow for landscaping access on the side of my house, and they were wonderful!
Bob, Greg & Mitch make a great team! Quick appointment times, super knowledgeable, expert troubleshooting capabilities & very customer service oriented.
I would highly recommend them for all of your HVAC needs! Great job guys!!

by Jacqueline Graham on Twintech Heating and Cooling

Twintech Heating & Cooling installed my furnace in 2022 and in fall of 2023 installed my Panasonic Heat Pump. Greg and Mitch did a great job. Helped me through the rebate process. Super happy with the Heat Pump. Only used my furnace 5 times this winter. Energy bills lower, carbon emissions lower.Thank you Twintech. I recommend highly!

by Bill Grainger on Twintech Heating and Cooling

Just had a new furnace installed by Twintech. I can’t express how great these guys are at what they do. From the sales to installation they were professional all the way. Very reasonable pricing and courteous during the installation and willing to answer any questions I had. Highly recommended !!!

Related Links:
heating and cooling, oshawa heating and cooling, heating and cooling services, commercial heating and cooling,


mrcool air conditioner error codes

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Furnace Installation: The Basics You Need to Know

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 21, 2018

If you are planning on having a new furnace installed, then you should know beforehand that it is a big job. If you are planning on installing your new furnace on your own – trust us, DO NOT DO IT. You need to make sure that the installation job is

Read More

How Do I Safely Change My AC Air Filter?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 27, 2024

Changing your AC air filter is a straightforward task. Here's a step-by-step guide to safely change your AC air filter: Turn Off the AC Unit: Before you begin, switch off the power to your HVAC system. You can do this by turning off the

Read More

Why Isn't My Heat Pump Turning On?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 28, 2023

If your heat pump is not turning on, there could be several reasons for this issue. Here are some common troubleshooting steps to help you identify and potentially resolve the problem: Check the Thermostat: Ensure that the thermostat

Read More

Furnace: Inconsistent Air Flow

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 16, 2024

Inconsistent airflow from your furnace can lead to uneven heating in your home, making some rooms too warm while others remain cold. This issue can arise from various causes, ranging from simple maintenance needs to more complex mechanical problems.

Read More