Furnace Trade-In
Furnace Trade-In

mrcool air conditioner error codes

24 / 7 Emergency Service Available. Call Us Now: 1.844.894.6832

Durham Region Air Conditioning Repair, Service and Installation

mrcool air conditioner error codes
CLICK HERE FOR A FREE QUOTATION

mrcool air conditioner codes

With this A/C troubleshooting guide, you can find problems with your system, fix it yourself. We will guide you through the process of identifying the problem and repairing your air conditioner.


Fault Display on the Dual 8 Numeral Tube of Outdoor Mainboard

CODE: E1.
RESULT: Actuation of high pressure switch.
FIX: Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E3.
RESULT: Actuation of low pressure switch.
FIX: When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than 3sec and the system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E4.
RESULT: Air discharge high temperature protection of compressor.
FIX: The exhaust temperature is higher than 125C for more than 5sec, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5 sec, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: F2.
RESULT: Malfunction of condenser temperature thermistor.
FIX: Malfunction of condenser temperature thermistor is detected when there is a short circuit or an open circuit in the condenser temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F3.
RESULT: Malfunction of outdoor ambient temperature thermistor.
FIX: Malfunction outdoor ambient temperature thermistor is detected when there is a short circuit or an open circuit in the outdoor ambient temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F4.
RESULT: Malfunction of Exhaust Temp. Sensor.
FIX: If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 2 minutes or short circuit 5 seconds successively at any time .The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

CODE: ON.
RESULT: Normal operation.
FIX: Unit operating normally or in standby mode.

CODE: H1.
RESULT: Defrost operation.
FIX 1: Power problem. Check control transformer power (24V). If power is available to demand control board and LED(s) do not light, replace control board.
FIX 2: Actuation of high pressure switch. Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 3: Actuation of low pressure switch. When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than3sec and the system will be shut down..The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 4: Air discharge high-temperature protection of compressor. The exhaust temperature is higher than 125C for more than 5s, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5s, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 5: Malfunction of exhaust Temp. Sensor. If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 3 minutes or short circuit 5 seconds successively at any time The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

mrcool air conditioner error codes

mrcool air conditioner codes


See What Our Customers Are Saying:

by Trevor Owens on Twintech Heating and Cooling

I returned from vacation to find my AC unit on the Fritz. After calling way too many places I connected with TwinTech. I’ve used the company in the past for my furnace so I was happy when I recognized Greg at my front door. He’s great and the service is always top notch. I’d highly recommend using twintech for honest, superior service in the Durham region. Thanks!

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

by Courtney Parkes on Twintech Heating and Cooling

Just hired TwinTech Heating & Cooling to do an A/C Unit removal & reinstall to allow for landscaping access on the side of my house, and they were wonderful!
Bob, Greg & Mitch make a great team! Quick appointment times, super knowledgeable, expert troubleshooting capabilities & very customer service oriented.
I would highly recommend them for all of your HVAC needs! Great job guys!!

by Jacqueline Graham on Twintech Heating and Cooling

Twintech Heating & Cooling installed my furnace in 2022 and in fall of 2023 installed my Panasonic Heat Pump. Greg and Mitch did a great job. Helped me through the rebate process. Super happy with the Heat Pump. Only used my furnace 5 times this winter. Energy bills lower, carbon emissions lower.Thank you Twintech. I recommend highly!

by Bill Grainger on Twintech Heating and Cooling

Just had a new furnace installed by Twintech. I can’t express how great these guys are at what they do. From the sales to installation they were professional all the way. Very reasonable pricing and courteous during the installation and willing to answer any questions I had. Highly recommended !!!

by Colin Vernon on Twintech Heating and Cooling

They've cleaned my furnace a couple of times and mentioned that the hot water tank standards were going to change soon so I decided to change mine out.

There were a few challenges during the process but the installers handled the problems without missing a stride! I now have really hot water again!

by Heidi B on Twintech Heating and Cooling

Highly recommend Twintech Heating company, we got honest and detailed information on what was needed to replace and install a new gas furnace. Bob and Greg made us feel comfortable withe process through their thorough explanation and knowledge of the right furnace for our needs. The professionalism and courteous friendly attitude towards the customer is what we liked the most as they treated us like family. So happy with our decision and new furnace we will be looking into get our rental water heater replaced and installed by Twintech team. We feel better having their knowledge on our side and will only trust them with any further maintenance of furnace.

by Kirushanth Rasiah on Twintech Heating and Cooling

Customer service and knowledge is priority in this industry, and Twintech has it. I've dealt with their team for maintenance and a furnace replacement. They're accommodating and make great recommendations, and came through at a great price over the big guys in the industry. They'll be my next call when I need service or maintenance.

by Leonard Glass on Twintech Heating and Cooling

I decided that the noises and age of the existing furnace which was old and not very efficient to replace it. Gave Greg a call and Grant and Greg got to work on it. Because of supply issues with the current heating type that would be an easier install Greg convinced me to change the location of the system and it would provide me better service for heat and efficiency. I had skeptical but went ahead anyway putting trust in Greg And Grant. Greg, Grant and Mitch came through and in 2 days had completely relocated my heating and A/C system. I can honestly say Greg was right my old house has been warmer and more evenly heated as it ever was. For anyone reading this rather long winded review can take my word for it, Twin Tech can take care of your needs.

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

Related Links:
heating and cooling, oshawa heating and cooling, heating and cooling services, commercial heating and cooling,


mrcool air conditioner error codes

See What Our Customers Are Saying:

by Trevor Owens on Twintech Heating and Cooling

I returned from vacation to find my AC unit on the Fritz. After calling way too many places I connected with TwinTech. I’ve used the company in the past for my furnace so I was happy when I recognized Greg at my front door. He’s great and the service is always top notch. I’d highly recommend using twintech for honest, superior service in the Durham region. Thanks!

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

by Courtney Parkes on Twintech Heating and Cooling

Just hired TwinTech Heating & Cooling to do an A/C Unit removal & reinstall to allow for landscaping access on the side of my house, and they were wonderful!
Bob, Greg & Mitch make a great team! Quick appointment times, super knowledgeable, expert troubleshooting capabilities & very customer service oriented.
I would highly recommend them for all of your HVAC needs! Great job guys!!

by Jacqueline Graham on Twintech Heating and Cooling

Twintech Heating & Cooling installed my furnace in 2022 and in fall of 2023 installed my Panasonic Heat Pump. Greg and Mitch did a great job. Helped me through the rebate process. Super happy with the Heat Pump. Only used my furnace 5 times this winter. Energy bills lower, carbon emissions lower.Thank you Twintech. I recommend highly!

by Bill Grainger on Twintech Heating and Cooling

Just had a new furnace installed by Twintech. I can’t express how great these guys are at what they do. From the sales to installation they were professional all the way. Very reasonable pricing and courteous during the installation and willing to answer any questions I had. Highly recommended !!!

Fine Tuning Your Furnace For the Winter

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 28, 2024

As the cold weather approaches, ensuring your furnace is in top shape is essential for both comfort and efficiency. Properly tuning your furnace before winter can help you avoid sudden breakdowns, improve energy efficiency, and ensure even heating th

Read More

Dealing with Humid Indoor Air

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 21, 2018

Having excess moisture in your home leads to damage and encourages harmful mold and mildew growth. Find out how you can reduce moisture at home and prevent the problems it causes by reading this week’s blog! INDOOR HUMIDITY AND MOISTURE H

Read More

Portable AC not cooling at all

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 8, 2023

It's frustrating when your portable AC unit doesn't seem to be cooling your room effectively. There are several steps you can take to improve its cooling performance: Proper Installation: Ensure that the portable AC unit is installed co

Read More

Is My AC Working Smoothly?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 26, 2024

To determine if your AC is working smoothly, you can consider a few indicators: Air Temperature: Check if the air blowing out of the vents is as cold as expected. It should be noticeably cooler than the room temperature. Airflow: Ens

Read More