Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by rcnichols electric in Whitby on Twintech Heating and Cooling

We had Grant and Greg Dainty quote to replace our 20 yr old furnace. I have known them for years and have had other jobs done by them ( AC and Pool Htr). The price was very reasonable and the job was completed in one day.

by Rick. F. in Pickering on Twintech Heating and Cooling

TwinTech was the right choice. Our consultation with Dave set the tone. Professional and knowledgeable, we even received a follow-up call within hours of our install completion, wow! TwinTech arrived as scheduled to install our A/C unit. Within minutes of arrival Greg noted and explained a few out of code faults on our furnace installed by another company, problems fixed, thanks TwinTech. Greg, Grant and "Subaru" Pete were meticulous start to finish. Highly recommended!

by Taresh, Pickering on Twintech Heating and Cooling

Twintech replaced our aging +20 yrs old Furnace & AC with the variable high efficiency Napoleon Furnace matched with the Goodman AC. Sales guy ,Dave was great, gave a no pressure estimate, explained about the Government Rebate program which they took care of completely including arranging the home energy audit. On the scheduled day Greg and his team arrived on time, did a great job and completed the same day , extremely professional and courteous, cleaned up everything , tested the system, Greg took his time to explain the setup. Very impressed with the Napoleon Furnace 9600 which did a great job in maintaining a comfortable temperature last winter and now with the hot weather the Goodman AC cooled the house in much less time than the old AC unit could ever. From start to finish Twintech were great and have no hesitation in recommending them 100%.

by Private User Pickering, ON on Twintech Heating and Cooling

The Twintech team did an excellent job installing our new Goodman air conditioner. They were polite and professional. Greg was knowledgeable and clearly experienced. Thank you Twintech for bringing our cooling system up to current regulations. Job well done!

by Y. M. from Pickering on Twintech Heating and Cooling

Dave from TwinTech was very knowledgeable, professional and thorough in the buying process. He helped us to identify the best furnace for our home and our budget. When we needed a new filter a year later and seemed to have a problem finding the right one, I called Dave up and he delivered a filter to me the next day! The cost was on par with other retailers, but it was this unexpected personal service that really was impressive. The furnace? Works like a charm.

by JLH from Pickering on Twintech Heating and Cooling

Imagine, it's 5 minutes after the midnight countdown New Year's eve and the furnace quits. We called TwinTech fully expecting to leave a message and actually spoke with Greg, one of the owners! We had an immediate repair early the next morning & a new furnace within the week. We have entrusted TwinTech with all our home HVAC service needs for over 6 years. That's why this week with an opportunity to purchase a new BBQ, we called them 1st to see about a gas line install. It's chicken on the grill tonight! They are efficient, reliable, honest, hard working, and -- attentive is an understatement.

by Curtis, Ajax on Twintech Heating and Cooling

Wonderful customer service, starting from the job quote (Dave), to the clean install, to the follow-up. Twintech is a small company which installed my Napoleon furnace, A/C, John Wood tank, and ran the line for my gas dryer. The installation was completed as promised in one day. The work area was kept very clean, and they even took care of my old rental tank. The professionalism and wonderful customer service is second to none. They completed all of my rebate paperwork, and now I'm getting $2000 back! You will not be disappointed if you hire this company for your project.

by Roy in Pickering on Twintech Heating and Cooling

I was referred to Twintech by a neighbour and was not disappointed. Not only was the customer service excellent their workmanship was second to none. Greg and Grant work extremely clean covering the pathway to the furnace room, labeling the essential parts, left the area spotless and were efficient. They cleaned up the mess left by the previous installers (wiring, improperly installed AC coil, and gaps in venting etc). They also ran through the operation of the new furnace and gave me some maintenance tips. Greg and Grant are professional and all around good guys. I will definitely recommend their service to anyone without hesitation.

by Peter Buck, Pickering on Twintech Heating and Cooling

Very satisfied with service from Twintech , beginning with all the information provided by Dave , which helped make the decision much easier . Installation was very smooth & done on time as promised & cleanup was well done . Would definitely recommend this company & use them again for any future needs . Well done.

by Angela from Ajax on Twintech Heating and Cooling

Twintech Heating & Cooling Inc. came in and replaced my 39 year old furnace with a beautiful Napoleon variable high efficiency furnace! Their work was efficient and professional and they were a pleasure to deal with, from sales to installation! I would highly recommend them.