The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by rcnichols electric in Whitby on Twintech Heating and Cooling

We had Grant and Greg Dainty quote to replace our 20 yr old furnace. I have known them for years and have had other jobs done by them ( AC and Pool Htr). The price was very reasonable and the job was completed in one day.

by Rick. F. in Pickering on Twintech Heating and Cooling

TwinTech was the right choice. Our consultation with Dave set the tone. Professional and knowledgeable, we even received a follow-up call within hours of our install completion, wow! TwinTech arrived as scheduled to install our A/C unit. Within minutes of arrival Greg noted and explained a few out of code faults on our furnace installed by another company, problems fixed, thanks TwinTech. Greg, Grant and "Subaru" Pete were meticulous start to finish. Highly recommended!

by Taresh, Pickering on Twintech Heating and Cooling

Twintech replaced our aging +20 yrs old Furnace & AC with the variable high efficiency Napoleon Furnace matched with the Goodman AC. Sales guy ,Dave was great, gave a no pressure estimate, explained about the Government Rebate program which they took care of completely including arranging the home energy audit. On the scheduled day Greg and his team arrived on time, did a great job and completed the same day , extremely professional and courteous, cleaned up everything , tested the system, Greg took his time to explain the setup. Very impressed with the Napoleon Furnace 9600 which did a great job in maintaining a comfortable temperature last winter and now with the hot weather the Goodman AC cooled the house in much less time than the old AC unit could ever. From start to finish Twintech were great and have no hesitation in recommending them 100%.

by Private User Pickering, ON on Twintech Heating and Cooling

The Twintech team did an excellent job installing our new Goodman air conditioner. They were polite and professional. Greg was knowledgeable and clearly experienced. Thank you Twintech for bringing our cooling system up to current regulations. Job well done!

by Y. M. from Pickering on Twintech Heating and Cooling

Dave from TwinTech was very knowledgeable, professional and thorough in the buying process. He helped us to identify the best furnace for our home and our budget. When we needed a new filter a year later and seemed to have a problem finding the right one, I called Dave up and he delivered a filter to me the next day! The cost was on par with other retailers, but it was this unexpected personal service that really was impressive. The furnace? Works like a charm.

by JLH from Pickering on Twintech Heating and Cooling

Imagine, it's 5 minutes after the midnight countdown New Year's eve and the furnace quits. We called TwinTech fully expecting to leave a message and actually spoke with Greg, one of the owners! We had an immediate repair early the next morning & a new furnace within the week. We have entrusted TwinTech with all our home HVAC service needs for over 6 years. That's why this week with an opportunity to purchase a new BBQ, we called them 1st to see about a gas line install. It's chicken on the grill tonight! They are efficient, reliable, honest, hard working, and -- attentive is an understatement.

by Curtis, Ajax on Twintech Heating and Cooling

Wonderful customer service, starting from the job quote (Dave), to the clean install, to the follow-up. Twintech is a small company which installed my Napoleon furnace, A/C, John Wood tank, and ran the line for my gas dryer. The installation was completed as promised in one day. The work area was kept very clean, and they even took care of my old rental tank. The professionalism and wonderful customer service is second to none. They completed all of my rebate paperwork, and now I'm getting $2000 back! You will not be disappointed if you hire this company for your project.

by Roy in Pickering on Twintech Heating and Cooling

I was referred to Twintech by a neighbour and was not disappointed. Not only was the customer service excellent their workmanship was second to none. Greg and Grant work extremely clean covering the pathway to the furnace room, labeling the essential parts, left the area spotless and were efficient. They cleaned up the mess left by the previous installers (wiring, improperly installed AC coil, and gaps in venting etc). They also ran through the operation of the new furnace and gave me some maintenance tips. Greg and Grant are professional and all around good guys. I will definitely recommend their service to anyone without hesitation.

by Peter Buck, Pickering on Twintech Heating and Cooling

Very satisfied with service from Twintech , beginning with all the information provided by Dave , which helped make the decision much easier . Installation was very smooth & done on time as promised & cleanup was well done . Would definitely recommend this company & use them again for any future needs . Well done.

by Angela from Ajax on Twintech Heating and Cooling

Twintech Heating & Cooling Inc. came in and replaced my 39 year old furnace with a beautiful Napoleon variable high efficiency furnace! Their work was efficient and professional and they were a pleasure to deal with, from sales to installation! I would highly recommend them.