CODE: A0.
RESULT: External protection device activated. External protection device connected to the terminal strip T1-T2 of indoor unit is activated.

CODE: A1.
RESULT: Malfunction of indoor unit PCB Malfunction due to noise Defect of indoor unit PCB.

CODE: A3.
RESULT: Malfunction of drain level control system Drain piping clogging, improper drain piping work Defect of drain pump. Defect of float switch.

CODE: A4.
RESULT: Malfunction of freezing protection Shortage of water volume Low water temperature setting Defect of 26WL. Defect of water temperature thermistor.

CODE: A5.
RESULT: High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor.

CODE: A6.
RESULT: Fan motor locked, overload, overcurrent Defect of connector contact Defect of indoor unit PCB Defect of fan motor.

CODE: A7.
RESULT: Malfunction of swing flap motor Failure of swing flap motorm, Defect of indoor unit PCB Jammed swing mechanism/blade.

CODE: A8.
RESULT: Malfunction of power supply Overcurrent of AC input, Defect of power supply voltage.

CODE: A9.
RESULT: Malfunction of electronic expansion valve drive Defect of electronic expansion valve coil, Defect of indoor unit PCB, Defect of connector contact.

CODE: AA.
RESULT: Heater overheat 26WH is activated.

CODE: AF.
RESULT: Malfunction of a humidifier system Water leakage of humidifier (option), Failure of swing float switch. Improper drain piping incline.

CODE: AH.
RESULT: Malfunction of dust collector of air cleaner Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB.

CODE: AJ.
RESULT: Malfunction of capacity setting (Indoor unit PCB) Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB.

CODE: C1.
RESULT: Failure of transmission (between indoor unit PCB and fan PCB) Defect of transmission of fan motor control driver.

CODE: C4.
RESULT: Malfunction of liquid pipe thermistor for heat exchanger Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger.

CODE: C5.
RESULT: Malfunction of gas pipe thermistor for heat exchanger Defect of connector contact. Defect of gas pipe thermistor for heat exchanger.

CODE: C6.
RESULT: Malfunction of fan motor control driver Defect of fan motor sensor system Defect of fan motor control driver.

CODE: C7.
RESULT: Front panel driving motor fault Defect of front panel driving motor Defect of limit switch.

CODE: C9.
RESULT: Malfunction of suction air thermistor Defect of connector contact Defect of thermistor for suction air.

CODE: CA.
RESULT: Malfunction of discharge air thermistor Defect of connector contact. Defect of thermistor for discharge air.

CODE: CC.
RESULT: Malfunction of humidity sensor system Defect of connector contact Defect of humidity sensor.

CODE: CJ.
RESULT: Malfunction of thermostat sensor in remote controller Defect of remote controller thermistor Malfunction due to noise Defect of remote controller PCB. Outdoor Unit.

CODE: E0.
RESULT: Protection devices actuated (unified) Protection device connected to outdoor PCB actuated Defect of protection device connector contact.

CODE: E1.
RESULT: Defect of outdoor unit PCB Malfunction due to noise Defect of outdoor unit PCB?.

CODE: E3.
RESULT: Actuation of high pressure switch (HPS) Dirty outdoor unit heat exchanger and suction filter Defect of HPS Clogged refrigerant piping Defect of connector contact.

CODE: E3.
RESULT: System No.1. Actuation of high pressure switch (HPS). Dirty outdoor unit heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact Outdoor Unit.

CODE: E4.
RESULT: Actuation of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connecting connector Defect of outdoor unit PCB.

CODE: E5.
RESULT: Overheat of inverter compressor motor Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: E5.
RESULT: Inverter compressor motor lock Inverter compressor lock Incorrect wiring.

CODE: E6.
RESULT: STD compressor motor overcurrent/lock Closed stop valve STD compressor lock.

CODE: E6.
RESULT: System No.1 Compressor overcurrent Defect of EXP. valve Defect of compressor Shortage of refrigerant amount.

CODE: E7.
RESULT: Malfunction of outdoor unit fan motor. Faulty contact of fan motor connector. Defect of fan motor, Defect of fan motor driver.

CODE: E8.
RESULT: Overcurrent of inverter compressor, Defect of compressor, Defect of outdoor unit PCB Defect of inverter main circuit capacitor Defect of power transistor.

CODE: E9.
RESULT: Malfunction of electronic expansion valve coil Defect of electronic expansion valve Defect of connector contact Defect of outdoor unit PCB.

CODE: EA.
RESULT: Malfunction of four way valve Defect of four way valve Defect of outdoor unit PCB Shortage of gas Defect of thermistor.

CODE: EC.
RESULT: Malfunction of entering water temperature Malfunction of cooling water temperature. Defect of thermistor. Defect of outdoor unit PCB.

CODE: EF.
RESULT: Malfunction of thermal storage unit Defect of electronic expansion valve of thermal storage unit Defect of thermal storage PCB.

CODE: F3.
RESULT: Malfunction of discharge pipe temperature Shortage of gas. Defect of connector contact. Clogged refrigerant piping Defect fo discharge pipe thermistor.

CODE: F6.
RESULT: Abnormal high pressure in cooling Defect of outdoor unit fan motor Defect of electronic expansion valve Defect of heat exchanger thermistor, Defect of outdoor unit PCB.

CODE: F6.
RESULT: Refrigerant overcharged Refrigerant overcharged Disconnection of heat exchanger thermistor Disconnection of outdoor air thermistor Disconnection of liquid pipe thermistor.

CODE: H0.
RESULT: Malfunction of sensor system of compressor, Harness is disconnected, or defective connection Defect of PCB.

CODE: H1.
RESULT: Malfunction of humidifier unit damper, Defect of limit switch Defect of damper.

CODE: H3.
RESULT: Malfunction of high pressure switch (HPS), Defect of high pressure switch. Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H4.
RESULT: Malfunction of low pressure switch (LPS), Defect of low pressure switch Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H5.
RESULT: Malfunction of compressor motor overload thermistor Defect of connector contact. Defect of compressor motor overload thermistor.

CODE: H6.
RESULT: Malfunction of position detection sensor, Faulty contact of compress or cable. Defect of compressor, Defect of outdoor unit PCB.

CODE: H7.
RESULT: Malfunction of outdoor fan motor signal Faulty contact of fan wiring Defect of fan motor driver Defect of fan motor.

CODE: H8.
RESULT: Malfunction of compressor input (CT) system Defect of power transistor. Defect of reactor. Faulty wiring of inverter system Defect of outdoor unit PCB.

CODE: H9.
RESULT: Malfunction of outdoor air thermistor. Defect of connector contact Defect of thermistor for outdoor air.

CODE: HC.
RESULT: Malfunction of (hot) water temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of thermistor for water temperature.

CODE: HF.
RESULT: Alarm in thermal storage unit with ice Thermal storage group defective wiring Defect of setting Excess of thermal storage tank numbers.

CODE: HJ.
RESULT: Malfunction of thermal storage tank water level Low water level Defect of switch setting Water level detecting sensor failure Defect of connector contact Outdoor Unit.

CODE: J1.
RESULT: Malfunction of pressure sensor Defect of pressure sensor connector contact. Defect of pressure sensor. Defect of outdoor unit PCB.

CODE: J2.
RESULT: Malfunction of current sensor of compressor Defect of current sensor Defect of outdoor unit PCB Defect of compressor.
CODE: J3.
RESULT: Malfunction of discharge pipe thermistor. Defect of connector contact Defect of outdoor unit PCB Defect of discharge pipe thermistor.

CODE: J4.
RESULT: Malfunction of low pressure equivalent saturated temperature sensor system Defect of connector contact Defect of thermistor Defect of outdoor unit PCB (Multi-split, Super-multi ).

CODE: J5.
RESULT: Malfunction of suction pipe thermistor Defect of connector contact Defect of outdoor unit PCB Defect of suction pipe thermistor.

CODE: J6.
RESULT: Malfunction of heat exchanger thermistor Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: J7.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J8.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J9.
RESULT: Malfunction of gas pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of gas pipe thermistor.

CODE: JA.
RESULT: Malfunction of high pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of high pressure sensor.

CODE: JC.
RESULT: Malfunction of low pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of low pressure sensor.

CODE: JE.
RESULT: Malfunction of sub-tank thermistor Defect of connector contact Defect of outdoor unit PCB Defect of sub-tank thermistor.

CODE: JF.
RESULT: Malfunction of heating thermistor for heat exchanger Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: JH.
RESULT: Malfunction of oil temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of oil temperature thermistor.

CODE: L0.
RESULT: Malfunction of inverter system Shortage of power supply capacity Defect of inverter PCB Defect of power transistor.

CODE: L1.
RESULT: Malfunction of inverter PCB Defect of compressor wiring Blown fuse Defect of outdoor unit fan motor Defect of inverter PCB.

CODE: L3.
RESULT: Electrical box temperature rise Fin temperature rise due to short-circuit Defect of power transistor Defect of outdoor unit fan Defect of outdoor unit PCB.

CODE: L4.
RESULT: Malfunction of inverter radiating fin temperature rise Fin temperature rise due to short-circuit Defect of fin thermistor.

CODE: L5.
RESULT: Inverter instantaneous overcurrent (DC) Closed stop valve Defect of compressor.

CODE: L6.
RESULT: Inverter instantaneous overcurrent (AC) Overcharge of refrigerant amount Defect of compressor Shortage of power supply capacity Defect of inverter unit.

CODE: L8.
RESULT: Overcurrent of inverter compressor Abnormal high pressure rise due to clogged refrigerant circuit and others Defect of compressor.

CODE: L9.
RESULT: Malfunction of inverter compressor startup Faulty of pressure equalization Defect of compressor wiring Defect of compressor.

CODE: LA.
RESULT: Malfunction of power transistor Defect of power transistor Defect of inverter PCB Defect of compressor.

CODE: LC.
RESULT: Malfunction of transmission between outdoor unit PCB and micro-computer Defect of grounding connection Defect of outdoor unit PCB Malfunction due to noise.

CODE: LC.
RESULT: Malfunction of transmission between control and inverter PCB Defect of connector contact Defect of inverter PCB Malfunction due to noise Defect of outdoor unit control PCB.

CODE: P0.
RESULT: Shortage of refrigerant amount (thermal storage unit) Shortage of refrigerant Clogged refrigerant piping Outdoor Unit.

CODE: P1.
RESULT: Power voltage imbalance, open phase Open phase Voltage imbalance between phases Faulty main circuit capacitor. Defect of wiring contact.

CODE: P2.
RESULT: Automatic refrigerant charge operation stop Closed stop valve. Closed valve of refrigerant tank.

CODE: P3.
RESULT: Malfunction of thermistor in electrical box Electrical box temperature rise (ambient temperature rise) Defect of fin thermistor, Defect of outdoor unit PCB.

CODE: P4.
RESULT: Malfunction of radiating fin temperature sensor Defect of radiating fin thermistor Defect of wiring contact Defect of outdoor unit PCB.

CODE: P8.
RESULT: Heat exchanger freezing protection during automatic refrigerant charging (Close the refrigerant cylinder. Start again from step 1.).

CODE: P9.
RESULT: Malfunction of fan motor (humidifier unit) Defect of fan motor Broken relay harness Defect of outdoor unit PCB Defect of connector contact.

CODE: P9.
RESULT: Automatic refrigerant charge operation completed.

CODE: PA.
RESULT: Broken wire of heater (humidifier unit) Defect of heater unit Defect of outdoor unit PCB Defect of thermistor.

CODE: PA.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of master unit is empty.

CODE: PC.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 2 is empty.

CODE: PE.
RESULT: Automatic refrigerant charge operation nearly completed.

CODE: PH.
RESULT: Malfunction of temperature (humidifier unit) Defect of heater unit Defect of thermistor Defect of connector contact Defect of outdoor unit PCB.

CODE: PH.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 1 is empty.

CODE: PJ.
RESULT: Malfunction of capacity setting (Outdoor unit PCB) Capacity setting adaptor is not installed Improper capacity setting adaptor Defect of outdoor unit PCB.

CODE: PJ.
RESULT: Improper combination between inverter and fan driver Mistake of inverter PCB Mistake of control PCB Mistake of inverter fan PCB System.

CODE: U0.
RESULT: Shortage of refrigerant Shortage of refrigerant Closed stop valve Clogged refrigerant piping.

CODE: U1.
RESULT: Reverse phase, open phase Reverse phase, open phase of power wiring Wrong wiring. Defect of outdoor unit PCB.

CODE: U2.
RESULT: Defect of power supply voltage or instantaneous power failure. Defect of power supply voltage Instantaneous power failure Defect of wiring contact.

CODE: U3.
RESULT: Check operation not executed. Check operation not executed.

CODE: U3.
RESULT: Malfunction of transmission Malfunction due to noise Defect of outdoor unit PCB Wrong wiring.

CODE: U4.
RESULT: Malfunction of transmission between indoor and outdoor unit Defect or indoor-outdoor transmission wiring Malfunction due to noise Defect of indoor unit PCB and outdoor unit PCB.

CODE: U5.
RESULT: Malfunction of transmission between indoor unit and remote controller Defect of remote controller wiring Defect of indoor unit PCB Malfunction due to noise Defect of remote controller main/sub setting.

CODE: U6.
RESULT: Malfunction of transmission between indoor units Faulty wiring Defect of indoor unit PCB Malfunction due to noise.

CODE: U7.
RESULT: Malfunction of transmission between main body micro-computer. INV micro-computer Harness disconnection/broken wire between PCB Defect of outdoor unit PCB.

CODE: U7.
RESULT: Malfunction of transmission between outdoor units Defect of wiring between outdoor units Defect of outdoor unit switch setting Defect of wiring between outdoor thermal storage units.

CODE: U8.
RESULT: Malfunction of transmission between remote controllers Defect of remote controller main/sub setting Defect of remote controller wiring. Defect of remote controller PCB Others.

CODE: 77.
RESULT: System No. 1 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 78.
RESULT: System No. 2 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 7A.
RESULT: System No. 2 Malfunction of current sensor of compressor Defect of current sensor. Defect of compressor Defect of outdoor unit PCB.

CODE: 7C.
RESULT: System No. 2 Malfunction of pump inter lock Cooling water pump interlock actuated.

CODE: 80.
RESULT: Malfunction of entering water temperature thermistor. Defect of connector contact. Defect of entering water temperature thermistor.

CODE: 81.
RESULT: Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 82.
RESULT: System No. 1 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 83.
RESULT: System No. 2 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 84.
RESULT: System No. 1 Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 85.
RESULT: System No. 2. Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 86.
RESULT: System No. 2. Malfunction of discharge pipe thermistor. Defect of connecting connector Defect of discharge pipe thermistor.

CODE: 88.
RESULT: System No. 2. Malfunction of discharge pipe temperature. Shortage of gas. Defect of discharge pipe thermistor Defect of connector contact. Clogged refrigerant piping.

CODE: 89.
RESULT: Malfunction of brazed-plate heat exchanger freezing Dirty heat exchanger. Shortage of refrigerant amount Defect of thermistor.

CODE: 8A.
RESULT: System No. 2 Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 8E.
RESULT: System No. 1 Malfunction of suction pipe thermistor 1 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8F.
RESULT: System No. 1 Malfunction of suction pipe thermistor 2 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8H.
RESULT: Abnormal high hot water temperature Three-way valve malfunction. Defect of thermistor Defect of water temperature setting.

CODE: 90.
RESULT: Abnormal chilled water quantity, abnormal AXP. Shortage of water volume Disconnection of AXP.

CODE: 91.
RESULT: System No. 2 Malfunction of electronic expansion valve Defect of connector contact Defect of electronic expansion valve coil.

CODE: 92.
RESULT: System No. 2 Malfunction of suction pipe thermistor Defect of connector contact Defect of suction pipe thermistor.

CODE: 94.
RESULT: Malfunction of transmission (between heat reclaim ventilation unit and fan unit) Defect of fan unit PCB Defect of connecting wire between (1) and (2).

CODE: 95.
RESULT: System No. 1 Malfunction of inverter system Defect of fan inverter unit.

CODE: 96.
RESULT: System No. 2 Malfunction of inverter system Defect of fan inverter unit.

CODE: 97.
RESULT: Malfunction of thermal storage unit Defect of thermal storage unit.

CODE: 98.
RESULT: Malfunction of thermal storage brine pump Actuation of thermal storage brine pump overcurrent (OC).

CODE: 99.
RESULT: Malfunction of thermal storage brine tank Low water level of thermal storage brine tank System.

CODE: U9.
RESULT: Malfunction of transmission (other system) Defect of communication between other indoor unit and outdoor unit Other indoor unit electronic expansion valve failure.

CODE: UA.
RESULT: Defect of indoor/outdoor power supply Wrong model connections Wrong PCB connected Improper power supply Defect of PCB.

CODE: UA.
RESULT: Malfunction of field setting Malfunction of field setting by remote controller Defect of remote controller wiring Defective connection of optional device Defect of indoor unit PCB.

CODE: UA.
RESULT: Improper combination of indoor and outdoor units Excess of connected indoor units Malfunction of field setting Uncanceled service mode. Defect of outdoor unit PCB.

CODE: UA.
RESULT: Remote temperature setting wire disconnection Remote temperature setting wire disconnection Defect of connector contact.

CODE: UC.
RESULT: Malfunction of setting of centralized controller address. Address duplication of centralized controller.

CODE: UE.
RESULT: Malfunction of transmission between indoor unit and centralized controller Malfunction of wiring between indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB.

CODE: UF.
RESULT: Wiring and piping mismatch Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units.

CODE: UH.
RESULT: Malfunction of system Improper connection of transmission wiring between indoor- outdoor units and outdoor-outdoor units Defect of indoor and outdoor unit PCB (RA: Mismatching indoor and outdoor units, Defect of voltage, Freeze protection in other indoor unit (k).

CODE: UJ.
RESULT: Malfunction of transmission (Accessory devices) Defect of accessory devices Faulty wiring.

CODE: M1.
RESULT: Malfunction of centralized remote controller PCB. Defect of centralized remote controller PCB.

CODE: M8.
RESULT: Malfunction of transmission between optional controllers for centralized control Other centralized control power disconnection Centralized control reset switch ON Defect of transmission wiring. Central remote controller address change.

CODE: MA.
RESULT: Improper combination of optional controllers for centralized control Improper combination of optional controllers for centralized control More than one master controller is connected Faulty setting of centralized control Defect of centralized control.

CODE: MC.
RESULT: Address duplication, improper setting Address duplication of central remote controller.

CODE: 60.
RESULT: External protection device actuated Actuation of external protection device Defect of output signal wiring Defect of control PCB.

CODE: 64.
RESULT: Malfunction of indoor air thermistor Defect of connecting connector Defect of thermistor for indoor air Defect of control PCB.

CODE: 65.
RESULT: Malfunction of outdoor air thermistor Defect of connector contact Defect of control PCB Defect of outdoor air thermistor.

CODE: 6A.
RESULT: Malfunction of damper system Defect of connector contact Defect of damper motor Defect of limit switch Defect of control PCB.

CODE: 70.
RESULT: System No. 2 Compressor overload Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: 71.
RESULT: System No. 2 Compressor overcurrent Shortage of refrigerant amount Short-circuit Defect of compressor.

CODE: 72.
RESULT: System No. 2 Fan motor overcurrent Defect of fan motor connector contact Defect of fan motor Defect of PCB.

CODE: 73.
RESULT: System No. 2 Malfunction of high pressure (HPS) actuated Dirty heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact.

CODE: 74.
RESULT: System No. 2 Malfunction of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connector contact Defect of LPS.

CODE: 75.
RESULT: System No. 2 Malfunction of low pressure sensor Defect of connector contact Defect of PCB Defect of low pressure sensor.

CODE: 76.
RESULT: System No. 2 Malfunction of high pressure sensor Defect of connector contact Defect of PCB Defect of high pressure sensor.


See What Our Customers Are Saying:

by Ian, Toronto on Twintech Heating and Cooling

The term excellent or incredible does not seem high enough praise for the Twintech Heating and cooling company that recently replaced our 15 year old furnace. To start with, the response from Dave at Twintech to our original pricing request was the quickest and most professional of the 5 prices we received which included two of the primary natural gas providers. The Twintech pricing was the most competitive by a considerable margin.
We had Dave visit our home to confirm all pricing which he did and scheduled us for next day installation which was not offered my the majority of the other providers.
The installation; the team arrived on time and provided coverings to all of the hardwood flooring and stairs and proceeded with the removal and reinstallation of the new furnace, the workers predicated six hours and were completed in five hours. I have to mention how courteous and polite the workers were each time we interacted with them from start to finish.
The final result was amazing, all materials were cleaned up and removed from the house and the workmanship very impressive.
One feature that really stood out for me which shows a high level of professionalism was that we had various condensation hoses from the furnace , humidifier and an air filtration unit meeting at the one drain, the installation crew ran PVC tubing including elbows along two sides of the furnace to guide the hoses into one PVC tube at the drain, it looks great!
When the install was completed and tested the Twintech technician guided us through the features and recommendation's for care of the new furnace.
We highly recommend Twintech to anyone for the outstanding service provided to us.

by Stephen, Pickering on Twintech Heating and Cooling

I didn't hesitate to call Twintech in for a 2nd time as they did an outstanding job installing my new furnace last year. This time my 18 year old air conditioner was on its last legs. Greg and the team are top notch, highly skilled technicians. The job was executed in a timely and professional manner. Greg was extremely thorough and went the extra mile to make sure everything was operating efficiently. Lastly, Dave is a true gentleman and really made the customer experience pleasurable and worry free. Always remember that good work ain't cheap and cheap work ain't good.

by Derek, Whitby on Twintech Heating and Cooling

It's so hard to find solid companies these days, but I was very pleased to find one in Twintech. Greg and his crew were very clean, respectful and professional. We were most impressed at how all the things they said they would do, were done. Sounds strange, but usually when a contractor comes to your home they say they will take care of this and that, make sure this is done, etc but when the work starts you have to constantly remind them of your previous discussions. Greg ensured every item he said he would do was done, no reminders required. The work was done right, at a fair price and on time. We will be sure to call them when our A/C unit dies (fingers crossed that's not going to happen too soon :) )

by Patrick, Toronto on Twintech Heating and Cooling

Replaced our aging hot water tank with a tankless system. Excellent work, fast efficient and clean.

Walked us through the new system and recommended maintenance schedule.

This is our second time working with TwinTech and we are very happy with the quality of their work and professionalism.

by Troy, Toronto on Twintech Heating and Cooling

Efficient work and great follow up by the team at Twin Tech. Great product and communication.

by Peter, Pickering on Twintech Heating and Cooling

On coldest night of the year our furnace quit. At 8:40 in the morning Greg arrived and gave us a diagnosis and a recommendation. By 2:30 we had a new furnace and were warm again. Great company. Great customer service. Good reasonable price.

Peter, Pickering

by New Furnace Installed on Twintech Heating and Cooling

Twin tech team was very efficient and prompt. They provided a quote within hours of request and got the job done on time. No disruption to home function. We would highly recommend this team. Job well done.

by John from Toronto on Twintech Heating and Cooling

Our furnace bit the dust, and Twintech came out to troubleshoot and diagnose the problem within a couple of hours. Mitch was super helpful, patient, and answered all of our questions. When we decided to get the furnace replaced, the crew was over first thing the next morning and did a fantastic job. Not only did they complete the job in a few hours, but they cleaned up and respected our house as they went, and answered all of our follow-up questions. I've used Twintech for our HVAC needs in the past and will continue to do so. I'd recommend them to anyone, and it feels good to support a local, family-owned business.

by Ryan k on Twintech Heating and Cooling

Dave and the Twintech team were fabulous from day 1 and helped us through the process to identifying a new furnace and AC unit. This was our first time through this process and Dave did a thorough job explaining all the components and was very patience answering all our questions. Dave provided great insights and fair pricing.

The Twintech team did an awesome installation. Very clean and efficient. I would highly recommended their service.

by Louise in Scarborough on Twintech Heating and Cooling

We had a new Amana furnace installed by Twintech and we were very pleased with the installation. It is nice to have a warm house again.