The tables below contain lists of error codes for several models of the Midea air conditioners. For each error code, there is a short explanation of the type of the malfunction. There are separate tables for the following series of Midea ACs: R series, 9V, 9A, and the Cassette / Ceiling&Floor series. If you're looking for information on AC Outdoor Units, you will also nd it below.


Midea air conditioner error code R series

CODE: E0.
RESULT: EEPROM parameter error.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: Zero-crossing signal error.

CODE: E3.
RESULT: Fan speed out of control.

CODE: E5.
RESULT: Open or short circuit of outdoor temperature sensor.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature sensor.

CODE: P0.
RESULT: IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Inverter compressor drive error.

Midea air conditioner error code 9V series

CODE: E0.
RESULT: EEPROM.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: 3 Zero-crossing signal error.

CODE: E3.
RESULT: Indoor fan speed out of control.

CODE: E5.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature.

CODE: E7.
RESULT: Outdoor fan speed out of control.

CODE: P0.
RESULT: IBM malfunction or IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Compressor position protection.

CODE: P5.
RESULT: Inverter module protection.

Midea air conditioner error code 9A series

CODE: E0.
RESULT: EEPROM.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: Zero-crossing signal error.

CODE: E3.
RESULT: Indoor fan speed out of control.

CODE: E5.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature.

CODE: E7.
RESULT: Outdoor fan speed out of control.

CODE: P0.
RESULT: IBM malfunction or IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Compressor position protection.

CODE: P5.
RESULT: Inverter module protection.

Midea AC Outdoor Units error code (except M5OA-36HRDN1-Q model)

CODE: E0.
RESULT: EEPROM error.

CODE: E1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E2.
RESULT: No B Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E3.
RESULT: No C Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E6.
RESULT: No D Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E4.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E5.
RESULT: Compressor voltage protection.

CODE: E7.
RESULT: Communication malfunction between outdoor main chip and compressor control chip.

CODE: P0.
RESULT: Temperature protection of compressor discharge or compressor top. For M4OC-36HRDN1-Q,it only means compressor discharge temp.protection.

CODE: P1.
RESULT: High pressure protection(only for M4OC1-27HRDN1-Q, M4OC-36HRDN1-Q).

CODE: P2.
RESULT: Low pressure protection(only for M4OC1-27HRDN1-Q, M4OC-36HRDN1-Q).

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Inverter module protection.

CODE: P6.
RESULT: Condenser high-temperature protection.

Midea AC Outdoor Units error code For M5OA-36HRDN1-Q model

CODE: E0.
RESULT: EEPROM error.

CODE: E1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E2.
RESULT: Communication malfunction between outdoor unit and indoor units.

CODE: E3.
RESULT: Communication malfunction between outdoor main chip and compressor control chip.

CODE: E4.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E5.
RESULT: Compressor voltage protection.

CODE: E6.
RESULT: PFC module protection.

CODE: P0.
RESULT: Compressor top. temperature protection.

CODE: P1.
RESULT: High pressure protection.

CODE: P2.
RESULT: Low pressure protection.

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Compressor discharge high-temperature protection.

CODE: P5.
RESULT: Condenser high-temperature protection.

CODE: P6.
RESULT: Inverter module protection.

CODE: F1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective Midea air conditioner error codes.

CODE: F2.
RESULT: No B Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F3.
RESULT: No C Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F4.
RESULT: No D Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F5.
RESULT: No E Indoor unit coil outlet temp. sensor or connector of sensor is defective.

Midea M2OC-18HRDN1-M air conditioner error code

CODE: EO.
RESULT: EEPROM parameter error.

CODE: E1.
RESULT: No 1 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E2.
RESULT: No 2 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E3.
RESULT: No 3 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E6.
RESULT: No 4 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E4.
RESULT: Open or short circuit of outdoor temperature sensor.

CODE: E5.
RESULT: Compressor volt protection.

CODE: E7.
RESULT: Communication error between outdoor IC and DSP.

CODE: PO.
RESULT: Temperature protection of compressor top.

CODE: P1.
RESULT: High pressure protection (just for 36K 1x4 units).

CODE: P2.
RESULT: Low pressure protection (just for 36K 1x4 units).

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Inverter module protection.

CODE: P5.
RESULT: Outdoor temp, too low protection.

CODE: P6.
RESULT: Condenser high-temperature protection.

CODE: P7.
RESULT: Compressor driving protection.

CODE: PF.
RESULT: PFC protection (just for 36K 1x4 units).

Midea MSX-07HRN1-QC2 air conditioner error code

CODE: E1.
RESULT: EEPROM error.

CODE: E2.
RESULT: Zero crossing detection error.

CODE: E3.
RESULT: Indoor fan speed has been out of control.

CODE: E4.
RESULT: Over current protection occurs 4 times.

CODE: E5.
RESULT: The T1 sensor is open circuit or short circuit.

CODE: E6.
RESULT: The T2 sensor is open circuit or short circuit.

CODE: E7.
RESULT: The T3 sensor is open circuit or short circuit.

CODE: E9.
RESULT: Indoor / outdoor units communication error.


See What Our Customers Are Saying:

by Patrick, Toronto on Twintech Heating and Cooling

The blower on our furnace stopped working leaving us with a cold house. Dave from TwinTech responded immediately to our HomeStars service request. From beginning to end Dave was nothing but helpful, friendly and professional, he did a great job of walking us through the quote and scope of work.


The replacement of the furnace went smoothly. The Guys did a great job, everyone was very friendly and polite. There were no hiccups, or unexpected costs. The only surprise was they left the work area cleaner than it was before they started.


Was a great experience with the whole TwinTech team. Its been a couple of months since the new furnace has been installed and its working great!

by Ed, Whitby on Twintech Heating and Cooling

I heard about TwinTech when researching new furnaces at furnaceprices.ca. After contacting them about my broken down furnace, Dave came to my house the next day to assess my situation and requirements for a new furnace. He recommended one that had stainless steel heat exchangers which sold me since my previous furnace had issues with a rusted secondary heat exchanger that had to be replaced. Dave also set me up with an appointment with an energy audit company so that I could take advantage of a rebate to help improve the energy efficiency of my home and get some money back. A few days later, Greg, Grant, and Mitch came to install the new furnace and remove the old one. When delivering and removing the furnaces, they were very careful not to damage my floors and walls, and even laid out red carpeting to protect the floors. They were very friendly and professional. The installation was completed in the time they said it would take and they cleaned up their work areas. Within a week, Dave called to follow-up to see how everything was going. I have already recommended them to several friends and family members who may need new furnaces soon.

by Fred, Toronto on Twintech Heating and Cooling

Twintech did a great job, from Dave the Sales Rep to the Office staff and The Professional Technicians who did the installation. They were professional, courteous, knowledgable and informative. From beginning to follow up we were completely satisfied with everything. Thanks Again. Sincerely The Laytons

by Elle, Oshawa on Twintech Heating and Cooling

Great product, great service, great follow-up. The Twintech Heating and Cooling arranged removal of my existing oil tank and they installed the new gas furnace Amana (made in USA). I am very happy with the final result and support I received throughout the process. My thanks go to the entire Twintech team for their professionalism, great communication and follow-up.

by John & Linda, Ajax on Twintech Heating and Cooling

We've had Twintech provide us with work in the past, for an inground pool heater and required rough-in for a new gas stove. More recently they provided the same friendly, professional, timely and clean installation of our new furnace.

by Bill, Whitby on Twintech Heating and Cooling

Reasonable price and the workmanship was prompt and timely and the employees were great to deal with.

by Nadia, Toronto on Twintech Heating and Cooling

The sales process was friendly, informative, and very consultative. They worked hard to earn our business by taking a careful look around our home to assess our needs, providing a lot of information about the product, and answering all our questions and finding the right solution for our home at a competitive price. They prepared us very well for what to expect on installation day, and the installation went very smoothly - no surprises, all very professional! They gave us a call after installation to ensure we were happy with the work. We're very happy that we chose to work with TwinTech to get our new furnace.

by Private User on Twintech Heating and Cooling

Twintech promptly responded to request for quotation. They were thorough and helpful in explaining options. The quote was very competitive. Installation of new furnace was very professionally completed. Excellent work.

by Rita, Scarborough on Twintech Heating and Cooling

When our old oil furnace finally broke down we decided it was time to finally convert to natural gas and finally install central air conditioning at the same time. Knowing it was going to be a significant investment for us, we wanted to make the right choice. Twintech came highly recommended by a friend and we were not disappointed. From the first contact with the salesperson, until the final touches on the installation, we were so pleased with their service. Everyone from the company was so friendly, efficient and a pleasure to deal with. Best of all, the cost was very competitive. We would certainly recommend Twintech to anyone requiring HVAC work in their home.

by Bob S, Pickering on Twintech Heating and Cooling

Mitch from Twintech came out for our annual furnace inspection. We found him to be friendly, conscientious & he left the work area clean. We were also very impressed with the thoroughness of the job he did. This is the 2nd job we’ve had Twintech do for us & have been very happy with the results for each. We highly recommend this company. Thank you, Mitch, Dave & Greg.