The tables below contain lists of error codes for several models of the Midea air conditioners. For each error code, there is a short explanation of the type of the malfunction. There are separate tables for the following series of Midea ACs: R series, 9V, 9A, and the Cassette / Ceiling&Floor series. If you're looking for information on AC Outdoor Units, you will also nd it below.


Midea air conditioner error code R series

CODE: E0.
RESULT: EEPROM parameter error.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: Zero-crossing signal error.

CODE: E3.
RESULT: Fan speed out of control.

CODE: E5.
RESULT: Open or short circuit of outdoor temperature sensor.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature sensor.

CODE: P0.
RESULT: IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Inverter compressor drive error.

Midea air conditioner error code 9V series

CODE: E0.
RESULT: EEPROM.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: 3 Zero-crossing signal error.

CODE: E3.
RESULT: Indoor fan speed out of control.

CODE: E5.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature.

CODE: E7.
RESULT: Outdoor fan speed out of control.

CODE: P0.
RESULT: IBM malfunction or IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Compressor position protection.

CODE: P5.
RESULT: Inverter module protection.

Midea air conditioner error code 9A series

CODE: E0.
RESULT: EEPROM.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: Zero-crossing signal error.

CODE: E3.
RESULT: Indoor fan speed out of control.

CODE: E5.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature.

CODE: E7.
RESULT: Outdoor fan speed out of control.

CODE: P0.
RESULT: IBM malfunction or IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Compressor position protection.

CODE: P5.
RESULT: Inverter module protection.

Midea AC Outdoor Units error code (except M5OA-36HRDN1-Q model)

CODE: E0.
RESULT: EEPROM error.

CODE: E1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E2.
RESULT: No B Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E3.
RESULT: No C Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E6.
RESULT: No D Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E4.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E5.
RESULT: Compressor voltage protection.

CODE: E7.
RESULT: Communication malfunction between outdoor main chip and compressor control chip.

CODE: P0.
RESULT: Temperature protection of compressor discharge or compressor top. For M4OC-36HRDN1-Q,it only means compressor discharge temp.protection.

CODE: P1.
RESULT: High pressure protection(only for M4OC1-27HRDN1-Q, M4OC-36HRDN1-Q).

CODE: P2.
RESULT: Low pressure protection(only for M4OC1-27HRDN1-Q, M4OC-36HRDN1-Q).

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Inverter module protection.

CODE: P6.
RESULT: Condenser high-temperature protection.

Midea AC Outdoor Units error code For M5OA-36HRDN1-Q model

CODE: E0.
RESULT: EEPROM error.

CODE: E1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E2.
RESULT: Communication malfunction between outdoor unit and indoor units.

CODE: E3.
RESULT: Communication malfunction between outdoor main chip and compressor control chip.

CODE: E4.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E5.
RESULT: Compressor voltage protection.

CODE: E6.
RESULT: PFC module protection.

CODE: P0.
RESULT: Compressor top. temperature protection.

CODE: P1.
RESULT: High pressure protection.

CODE: P2.
RESULT: Low pressure protection.

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Compressor discharge high-temperature protection.

CODE: P5.
RESULT: Condenser high-temperature protection.

CODE: P6.
RESULT: Inverter module protection.

CODE: F1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective Midea air conditioner error codes.

CODE: F2.
RESULT: No B Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F3.
RESULT: No C Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F4.
RESULT: No D Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F5.
RESULT: No E Indoor unit coil outlet temp. sensor or connector of sensor is defective.

Midea M2OC-18HRDN1-M air conditioner error code

CODE: EO.
RESULT: EEPROM parameter error.

CODE: E1.
RESULT: No 1 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E2.
RESULT: No 2 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E3.
RESULT: No 3 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E6.
RESULT: No 4 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E4.
RESULT: Open or short circuit of outdoor temperature sensor.

CODE: E5.
RESULT: Compressor volt protection.

CODE: E7.
RESULT: Communication error between outdoor IC and DSP.

CODE: PO.
RESULT: Temperature protection of compressor top.

CODE: P1.
RESULT: High pressure protection (just for 36K 1x4 units).

CODE: P2.
RESULT: Low pressure protection (just for 36K 1x4 units).

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Inverter module protection.

CODE: P5.
RESULT: Outdoor temp, too low protection.

CODE: P6.
RESULT: Condenser high-temperature protection.

CODE: P7.
RESULT: Compressor driving protection.

CODE: PF.
RESULT: PFC protection (just for 36K 1x4 units).

Midea MSX-07HRN1-QC2 air conditioner error code

CODE: E1.
RESULT: EEPROM error.

CODE: E2.
RESULT: Zero crossing detection error.

CODE: E3.
RESULT: Indoor fan speed has been out of control.

CODE: E4.
RESULT: Over current protection occurs 4 times.

CODE: E5.
RESULT: The T1 sensor is open circuit or short circuit.

CODE: E6.
RESULT: The T2 sensor is open circuit or short circuit.

CODE: E7.
RESULT: The T3 sensor is open circuit or short circuit.

CODE: E9.
RESULT: Indoor / outdoor units communication error.


See What Our Customers Are Saying:

by MB, Ajax on Twintech Heating and Cooling

Installation was done quickly and professionally. The new furnace is quiet and provides even heat.

by Richard from Oshawa on Twintech Heating and Cooling

They removed and discarded old furnace. Installed new furnace. Installed air intake pipe, that had never been installed by builder, no charge. Replaced loose hose on floor with hard pipe and rerouted it to drain, no charge. Almost 33% cheaper then quote from Enercare, which was the company we dealt with and had insurance with for 8 years. No yearly fee for cleaning/insurance, saves 300 a year. Courteous, professional, fast, and friendly. My wife and I have been recommending them to everyone we know and meet, and will continue to do so. Thanks for everything, Twintech!!!

by Darcy from Pickering on Twintech Heating and Cooling

This company was great to deal with. Our furnace went down and they installed a new furnace the next day with a lot of professionalism!

by gillian hooton from Uxbridge on Twintech Heating and Cooling

Finally! An honest company with highly knowledgeable and informative staff. Had a furnace service and found multiply errors in our system from an amateur installer. Very fair price to correct problems and will definitely use again.

by dflynn in Ajax on Twintech Heating and Cooling

Had to replace the heating & a/c unit in a condo apartment dwelling. this company recommended by the property manager and president of the condo building. found their workmanship and attention to details very good and very thorough. were able to resolve small problems and situations and happy to feel the heat in my unit. it's pricey, but happy was done by a very professional service. thank you.

by alisiena from Toronto on Twintech Heating and Cooling

Fantastic team. Completed the job as per the specifications and in under 3 hours. Highly recommended Twintech.

by David from Toronto on Twintech Heating and Cooling

During the summer, I previously hired TwinTech to replace my air conditioner when it failed. They did an excellent job so when I decided to proactively replace the furnace I contacted them. The furnace I had was 22 years old and showed signs of internal leakage. It still worked but rather than wait to have it fail in cold weather, I decided to purchase a higher efficiency model before it failed and take advantage of energy efficiency rebates. TwinTech offered very useful advice on the make and model of furnace to choose including high efficiency and variable speed motor. The price was reasonable, TwinTech arrived at the allotted time, installed the new furnace (including some re-routing of exhaust lines since the existing ones were too close to other vents), removed the old furnace, tested the installation and cleaned everything up. Overall, it was a good experience, they did a great job and the new furnace is working well.

by Jaime-Lynne in Pickering on Twintech Heating and Cooling

Greg came over at 9:30pm to rescue my daughter and I from a horrible experience with Enercare that evening. He was professional. Kind. And got us what we needed quickly and at an afford price. I would 100% recommend calling on Greg and his team for any of your heating and cooling needs in the future!!

by Matt C. Oshawa on Twintech Heating and Cooling

Installed a great hot water heater when our old one failed. When my furnace died during cold weather they showed up quickly and my house was warm before my wife got home. :)

by B Davis in Pickering on Twintech Heating and Cooling

I don’t usually right reviews but when you receive service like this I felt it was a must. Honest and fair. I Have 4 children and on Xmas eve my furnace stopped working and a gentleman came out and got me up and running so at least we would have heat for the holidays. As promised he would replace my furnace early in the new year. The job was completed on time, great price for quality furnace and extremely clean and professional job. Would have never known anyone was in the house. Not a spec of dust or mess from lugging out an old rusty furnace. If you have any ac or heating concerns twintech is your only option. I was royally impressed with and I’m sure you will be too.