The tables below contain lists of error codes for several models of the Midea air conditioners. For each error code, there is a short explanation of the type of the malfunction. There are separate tables for the following series of Midea ACs: R series, 9V, 9A, and the Cassette / Ceiling&Floor series. If you're looking for information on AC Outdoor Units, you will also nd it below.


Midea air conditioner error code R series

CODE: E0.
RESULT: EEPROM parameter error.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: Zero-crossing signal error.

CODE: E3.
RESULT: Fan speed out of control.

CODE: E5.
RESULT: Open or short circuit of outdoor temperature sensor.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature sensor.

CODE: P0.
RESULT: IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Inverter compressor drive error.

Midea air conditioner error code 9V series

CODE: E0.
RESULT: EEPROM.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: 3 Zero-crossing signal error.

CODE: E3.
RESULT: Indoor fan speed out of control.

CODE: E5.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature.

CODE: E7.
RESULT: Outdoor fan speed out of control.

CODE: P0.
RESULT: IBM malfunction or IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Compressor position protection.

CODE: P5.
RESULT: Inverter module protection.

Midea air conditioner error code 9A series

CODE: E0.
RESULT: EEPROM.

CODE: E1.
RESULT: Indoor / outdoor units communication protection.

CODE: E2.
RESULT: Zero-crossing signal error.

CODE: E3.
RESULT: Indoor fan speed out of control.

CODE: E5.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E6.
RESULT: Open or short circuit of room or evaporator temperature.

CODE: E7.
RESULT: Outdoor fan speed out of control.

CODE: P0.
RESULT: IBM malfunction or IGBT over-strong current protection.

CODE: P1.
RESULT: Over voltage or too under voltage protection.

CODE: P2.
RESULT: Temperature protection of compressor top.

CODE: P4.
RESULT: Compressor position protection.

CODE: P5.
RESULT: Inverter module protection.

Midea AC Outdoor Units error code (except M5OA-36HRDN1-Q model)

CODE: E0.
RESULT: EEPROM error.

CODE: E1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E2.
RESULT: No B Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E3.
RESULT: No C Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E6.
RESULT: No D Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E4.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E5.
RESULT: Compressor voltage protection.

CODE: E7.
RESULT: Communication malfunction between outdoor main chip and compressor control chip.

CODE: P0.
RESULT: Temperature protection of compressor discharge or compressor top. For M4OC-36HRDN1-Q,it only means compressor discharge temp.protection.

CODE: P1.
RESULT: High pressure protection(only for M4OC1-27HRDN1-Q, M4OC-36HRDN1-Q).

CODE: P2.
RESULT: Low pressure protection(only for M4OC1-27HRDN1-Q, M4OC-36HRDN1-Q).

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Inverter module protection.

CODE: P6.
RESULT: Condenser high-temperature protection.

Midea AC Outdoor Units error code For M5OA-36HRDN1-Q model

CODE: E0.
RESULT: EEPROM error.

CODE: E1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: E2.
RESULT: Communication malfunction between outdoor unit and indoor units.

CODE: E3.
RESULT: Communication malfunction between outdoor main chip and compressor control chip.

CODE: E4.
RESULT: Outdoor unit temp. sensor or connector of temp. sensor is defective.

CODE: E5.
RESULT: Compressor voltage protection.

CODE: E6.
RESULT: PFC module protection.

CODE: P0.
RESULT: Compressor top. temperature protection.

CODE: P1.
RESULT: High pressure protection.

CODE: P2.
RESULT: Low pressure protection.

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Compressor discharge high-temperature protection.

CODE: P5.
RESULT: Condenser high-temperature protection.

CODE: P6.
RESULT: Inverter module protection.

CODE: F1.
RESULT: No A Indoor unit coil outlet temp. sensor or connector of sensor is defective Midea air conditioner error codes.

CODE: F2.
RESULT: No B Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F3.
RESULT: No C Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F4.
RESULT: No D Indoor unit coil outlet temp. sensor or connector of sensor is defective.

CODE: F5.
RESULT: No E Indoor unit coil outlet temp. sensor or connector of sensor is defective.

Midea M2OC-18HRDN1-M air conditioner error code

CODE: EO.
RESULT: EEPROM parameter error.

CODE: E1.
RESULT: No 1 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E2.
RESULT: No 2 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E3.
RESULT: No 3 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E6.
RESULT: No 4 Indoor units pipe temp, sensor or connector of pipe temp, sensor is defective.

CODE: E4.
RESULT: Open or short circuit of outdoor temperature sensor.

CODE: E5.
RESULT: Compressor volt protection.

CODE: E7.
RESULT: Communication error between outdoor IC and DSP.

CODE: PO.
RESULT: Temperature protection of compressor top.

CODE: P1.
RESULT: High pressure protection (just for 36K 1x4 units).

CODE: P2.
RESULT: Low pressure protection (just for 36K 1x4 units).

CODE: P3.
RESULT: Compressor current protection.

CODE: P4.
RESULT: Inverter module protection.

CODE: P5.
RESULT: Outdoor temp, too low protection.

CODE: P6.
RESULT: Condenser high-temperature protection.

CODE: P7.
RESULT: Compressor driving protection.

CODE: PF.
RESULT: PFC protection (just for 36K 1x4 units).

Midea MSX-07HRN1-QC2 air conditioner error code

CODE: E1.
RESULT: EEPROM error.

CODE: E2.
RESULT: Zero crossing detection error.

CODE: E3.
RESULT: Indoor fan speed has been out of control.

CODE: E4.
RESULT: Over current protection occurs 4 times.

CODE: E5.
RESULT: The T1 sensor is open circuit or short circuit.

CODE: E6.
RESULT: The T2 sensor is open circuit or short circuit.

CODE: E7.
RESULT: The T3 sensor is open circuit or short circuit.

CODE: E9.
RESULT: Indoor / outdoor units communication error.


See What Our Customers Are Saying:

by Scott and Sandra in Ajax on Twintech Heating and Cooling

After receiving numerous quotes to replace my old furnace and AC unit (which was 20 years old) I went with Twintech. Dave, in sales, answered questions professionally and promptly and worked diligently in order to secure my business. Installation was scheduled the week after and Greg and Peter showed up, as scheduled, and did a fine job installing both units. The site was left tidy and neat. I would highly recommend Twintech for your furnace and AC work.

by Linda from Whitby on Twintech Heating and Cooling

I chose TwinTech because they installed my new furnace a few years ago and did a great job. When they installed my new A/C, they replaced all parts -- the copper pipes, the housing on top of the furnace and the wiring. (Apparently, the wiring for my old A/C was insufficient.) Their pricing was competitive. The sales representative came to see me within a few hours of my call. My new A/C was installed a few days later and I couldn't be happier with Twintech's professionalism and work. I would recommend TwinTech to any homeowner.

by george polychronis from Whitby on Twintech Heating and Cooling

Had a great experience with this company. Great price and great customer service. You wont be disappointed with twintech. Discussed the job with Greg while he was installing who was extremely informative and obviously enjoys the work he does.

by Nuzio in Markham on Twintech Heating and Cooling

I needed my AC unit relocated due to upcoming landscape work. I reached out to the Twintech team through Homestars. Dave connected with me immediately to discuss the project and various options. We decided the best option was to mount the unit on the wall. Greg was in touch with me the same day as well and we scheduled the work for later that same week. This was a small job so I did not think I would get immediate attention. The Twintech team exceeded my expectations in every respect. They were very knowledgeable and friendly. The team arrived exactly on time on the scheduled day and worked efficiently to get the job done quickly. I would definitely use Twintech again for any Heating and AC projects.

by Leslie B, Pickering on Twintech Heating and Cooling

I have used Greg Dainty for over 15 years in 3 different homes, for heating, cooling, pool heaters, appliances and bbq lines. Greg has always been so professional, friendly and the workmanship nothing short of fantastic. Greg has always discussed my options and fixing versus replacing, giving his honest opinion and what works best for me cost effective wise and long term. I have valued his opinion so much and have not trusted my gas needs with anyone since using him. I have also referred him to many of my friends and family and have always been so thankful with how well and quickly he looks after us all. I hold Greg in the highest regard and would recommend him to anyone with complete confidence!

by Marcel M, Whitby ON on Twintech Heating and Cooling

Really nice honest guys. It was a pleasure to do business with a company that does exactly what they say they’re going to do! My basement was cleaner after they installed my new furnace and AC. Thanks again Greg and Grant and for doing such a great job.

by George In Pickering on Twintech Heating and Cooling

5 star service!! I had twin tech install a high efficiency furnace and hot water tank at my home. I am taking time to write this review as a thanks for what I viewed as next level service that went above and beyond. Prior to installation they explained my specific options without pushy sales tactics and up front costs. Greg and Grant replaced a large portion of the duct work (built in their own shop) that had rusted over the years which resulted in a great looking job. It was a pleasure to work with people are passionate and take pride in their work. Following the installation they explained all aspects and maintenance of the new equipment. Products have worked flawlessly. Thanks again Greg and Grant! Highly recommend!!

by Donna J, in Ajax on Twintech Heating and Cooling

Twin Tech was great; they were honest, reliable and very thorough. I would recommend their services and will definitely be using them in the future.

by Sheila C. Pickering on Twintech Heating and Cooling

Hi Dave, Thank You Dave for coming to my aid this past summer when my AC quit. Your men did a great job installing and cleaning the area. The unit is working very well and i would highly recommend your company TwinTech. Dave you delivered what you sold and i truly appreciate it.

by Darin O. Whitby on Twintech Heating and Cooling

My experience with TWINTECH has been excellent, start to finish. While doing market research I made a list of several local companies and called them for some high-level information. Dave was the first to call me back, and the only one to book a meeting to see my place in order to give an informed, accurate estimate. He reviewed the different AC makes and models with me, explained the technology, and made a recommendation appropriate to my home. The installation went smoothly. I had one post-installation issue – there was moderate noise/vibrations coming from the duct system. I called about this, booked an appointment, and the technician resolved the issue during the service call. I feel assured having a 10-year warranty on parts & labour. I would recommend TWINTECH to anyone considering an AC or furnace for their home. Regards,