Fault Display on the Dual 8 Numeral Tube of Outdoor Mainboard

CODE: E1.
RESULT: Actuation of high pressure switch.
FIX: Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E3.
RESULT: Actuation of low pressure switch.
FIX: When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than 3sec and the system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E4.
RESULT: Air discharge high temperature protection of compressor.
FIX: The exhaust temperature is higher than 125C for more than 5sec, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5 sec, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: F2.
RESULT: Malfunction of condenser temperature thermistor.
FIX: Malfunction of condenser temperature thermistor is detected when there is a short circuit or an open circuit in the condenser temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F3.
RESULT: Malfunction of outdoor ambient temperature thermistor.
FIX: Malfunction outdoor ambient temperature thermistor is detected when there is a short circuit or an open circuit in the outdoor ambient temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F4.
RESULT: Malfunction of Exhaust Temp. Sensor.
FIX: If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 2 minutes or short circuit 5 seconds successively at any time .The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

CODE: ON.
RESULT: Normal operation.
FIX: Unit operating normally or in standby mode.

CODE: H1.
RESULT: Defrost operation.
FIX 1: Power problem. Check control transformer power (24V). If power is available to demand control board and LED(s) do not light, replace control board.
FIX 2: Actuation of high pressure switch. Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 3: Actuation of low pressure switch. When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than3sec and the system will be shut down..The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 4: Air discharge high-temperature protection of compressor. The exhaust temperature is higher than 125C for more than 5s, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5s, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 5: Malfunction of exhaust Temp. Sensor. If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 3 minutes or short circuit 5 seconds successively at any time The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.


See What Our Customers Are Saying:

by Brent L on Twintech Heating and Cooling

Work was done on schedule, professionally, according to quote and with minimal inconvenience to building users. Very happy with the end result. The only area for improvement from my experience - need more timely quoting process.

by Karen on Twintech Heating and Cooling

The team was great! Very knowledgeable, professional and extremely helpful. A few days after install the unit didn’t seem to be working, user error, but within minutes of contacting them..on a Saturday.. a tech was on the phone troubleshooting with us. I highly recommend Twintech for your cooling or heating needs. They stand by their products and a pleasure to deal with.

by Rob on Twintech Heating and Cooling

During the hottest week in the summer our old A/C decided to call it quits. I called Twintech Heating & Cooling after receiving a referral from a family member; came highly rated for being an honest, family-run business, who appreciates their customers. Dave was able to accommodate my hectic schedule and book a late evening appointment to walk through the specifics. Greg and Mitch arrived exactly on time a few days later, were very polite and friendly, and within a couple of hours had a new unit up and running. I also received a follow-up call to ensure we were happy with the Amana.

by Linda Robinson on Twintech Heating and Cooling

They were on time and very professional. I'm so glad I decided to go with Twintech, thanks!

by Famcam1953 on Twintech Heating and Cooling

Timely and appreciated - this was during the hottest days this year when our Air and Furnace way.
Efficient. Professional. No BS or overselling. What was promised, was delivered at a cost-effective price point.
Down to earth.

by DG Sellers on Twintech Heating and Cooling

Professionally done and took care to cover all entry floors to the house for the installers to remove the old furnace and install a new furnace.
I also made recommendations of the tankless water heater that we had installed and items to address. We did not know they also installed tankless water heaters.

by Bill, Pickering on Twintech Heating and Cooling

Price was not the cheapest nor the most expensive of my quotes. It's the quality of the installation that makes for a good AC system. The twins' knowledge & professionalism was evident in the small details:
Very clean work. Greg made sure that the refrigerant level & temperature were correct. They reinstall the insulation & vapor barrier around the wall. The outside electrical cords were secured to the wall. Proud to support this local company. Thank you.

by Taz on Twintech Heating and Cooling

Great team of guys came to do the work. Very professional. Arrived on time worked very efficiently and were very clean. They answered any questions we had without hesitation. The air conditioner works great and is so quiet. I highly recommend them and they don't try to up-sell anything right from the start.

by Jordan on Twintech Heating and Cooling

The service was prompt, professional and very courteous. Competitive price. Would highly recommend this company.

by David on Twintech Heating and Cooling

Excellent workmanship, and quick response. Would recommend Twintech to anyone.