Fault Display on the Dual 8 Numeral Tube of Outdoor Mainboard

CODE: E1.
RESULT: Actuation of high pressure switch.
FIX: Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E3.
RESULT: Actuation of low pressure switch.
FIX: When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than 3sec and the system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: E4.
RESULT: Air discharge high temperature protection of compressor.
FIX: The exhaust temperature is higher than 125C for more than 5sec, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5 sec, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

CODE: F2.
RESULT: Malfunction of condenser temperature thermistor.
FIX: Malfunction of condenser temperature thermistor is detected when there is a short circuit or an open circuit in the condenser temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F3.
RESULT: Malfunction of outdoor ambient temperature thermistor.
FIX: Malfunction outdoor ambient temperature thermistor is detected when there is a short circuit or an open circuit in the outdoor ambient temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

CODE: F4.
RESULT: Malfunction of Exhaust Temp. Sensor.
FIX: If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 2 minutes or short circuit 5 seconds successively at any time .The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

CODE: ON.
RESULT: Normal operation.
FIX: Unit operating normally or in standby mode.

CODE: H1.
RESULT: Defrost operation.
FIX 1: Power problem. Check control transformer power (24V). If power is available to demand control board and LED(s) do not light, replace control board.
FIX 2: Actuation of high pressure switch. Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 3: Actuation of low pressure switch. When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than3sec and the system will be shut down..The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 4: Air discharge high-temperature protection of compressor. The exhaust temperature is higher than 125C for more than 5s, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90C for more than 5s, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.
FIX 5: Malfunction of exhaust Temp. Sensor. If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 3 minutes or short circuit 5 seconds successively at any time The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.


See What Our Customers Are Saying:

by rcnichols electric in Whitby on Twintech Heating and Cooling

We had Grant and Greg Dainty quote to replace our 20 yr old furnace. I have known them for years and have had other jobs done by them ( AC and Pool Htr). The price was very reasonable and the job was completed in one day.

by Rick. F. in Pickering on Twintech Heating and Cooling

TwinTech was the right choice. Our consultation with Dave set the tone. Professional and knowledgeable, we even received a follow-up call within hours of our install completion, wow! TwinTech arrived as scheduled to install our A/C unit. Within minutes of arrival Greg noted and explained a few out of code faults on our furnace installed by another company, problems fixed, thanks TwinTech. Greg, Grant and "Subaru" Pete were meticulous start to finish. Highly recommended!

by Taresh, Pickering on Twintech Heating and Cooling

Twintech replaced our aging +20 yrs old Furnace & AC with the variable high efficiency Napoleon Furnace matched with the Goodman AC. Sales guy ,Dave was great, gave a no pressure estimate, explained about the Government Rebate program which they took care of completely including arranging the home energy audit. On the scheduled day Greg and his team arrived on time, did a great job and completed the same day , extremely professional and courteous, cleaned up everything , tested the system, Greg took his time to explain the setup. Very impressed with the Napoleon Furnace 9600 which did a great job in maintaining a comfortable temperature last winter and now with the hot weather the Goodman AC cooled the house in much less time than the old AC unit could ever. From start to finish Twintech were great and have no hesitation in recommending them 100%.

by Private User Pickering, ON on Twintech Heating and Cooling

The Twintech team did an excellent job installing our new Goodman air conditioner. They were polite and professional. Greg was knowledgeable and clearly experienced. Thank you Twintech for bringing our cooling system up to current regulations. Job well done!

by Y. M. from Pickering on Twintech Heating and Cooling

Dave from TwinTech was very knowledgeable, professional and thorough in the buying process. He helped us to identify the best furnace for our home and our budget. When we needed a new filter a year later and seemed to have a problem finding the right one, I called Dave up and he delivered a filter to me the next day! The cost was on par with other retailers, but it was this unexpected personal service that really was impressive. The furnace? Works like a charm.

by JLH from Pickering on Twintech Heating and Cooling

Imagine, it's 5 minutes after the midnight countdown New Year's eve and the furnace quits. We called TwinTech fully expecting to leave a message and actually spoke with Greg, one of the owners! We had an immediate repair early the next morning & a new furnace within the week. We have entrusted TwinTech with all our home HVAC service needs for over 6 years. That's why this week with an opportunity to purchase a new BBQ, we called them 1st to see about a gas line install. It's chicken on the grill tonight! They are efficient, reliable, honest, hard working, and -- attentive is an understatement.

by Curtis, Ajax on Twintech Heating and Cooling

Wonderful customer service, starting from the job quote (Dave), to the clean install, to the follow-up. Twintech is a small company which installed my Napoleon furnace, A/C, John Wood tank, and ran the line for my gas dryer. The installation was completed as promised in one day. The work area was kept very clean, and they even took care of my old rental tank. The professionalism and wonderful customer service is second to none. They completed all of my rebate paperwork, and now I'm getting $2000 back! You will not be disappointed if you hire this company for your project.

by Roy in Pickering on Twintech Heating and Cooling

I was referred to Twintech by a neighbour and was not disappointed. Not only was the customer service excellent their workmanship was second to none. Greg and Grant work extremely clean covering the pathway to the furnace room, labeling the essential parts, left the area spotless and were efficient. They cleaned up the mess left by the previous installers (wiring, improperly installed AC coil, and gaps in venting etc). They also ran through the operation of the new furnace and gave me some maintenance tips. Greg and Grant are professional and all around good guys. I will definitely recommend their service to anyone without hesitation.

by Peter Buck, Pickering on Twintech Heating and Cooling

Very satisfied with service from Twintech , beginning with all the information provided by Dave , which helped make the decision much easier . Installation was very smooth & done on time as promised & cleanup was well done . Would definitely recommend this company & use them again for any future needs . Well done.

by Angela from Ajax on Twintech Heating and Cooling

Twintech Heating & Cooling Inc. came in and replaced my 39 year old furnace with a beautiful Napoleon variable high efficiency furnace! Their work was efficient and professional and they were a pleasure to deal with, from sales to installation! I would highly recommend them.