In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Hector in Scarborough on Twintech Heating and Cooling

Last week our Furnace failed overnight. We called Twintech to help us get it running again. They did a really thorough check on it, and got it running in less than an hour. Given that it was an old Furnace (+20 years old), we were giving two options: repair it or replace it. Instead of doing a repair on it that could break in a week or two, they recommended us to change it. I like that they were honest on the recommendation, not forcing a new furnace on us. At the end we went with a new Furnace. Twintech solutions service & salesman gave us recommendation on the size of the unit and many options that could work for our home. They ended up doing an excellent work in our furnace, replacing the filter to a better option and replacing some pieces that had water damage. They cleaned after themselves and leave everything even better than what they found. They even went far and beyond tiding up the hose connections that we had on the basement.

by Ryan Doherty in Whitby on Twintech Heating and Cooling

I am in the process of finishing my basement and wanted to make sure I got the low hanging duct work fixed in advance. After reviewing 5 quotes I selected Twintech to award the contract to. The price was competitive however what won me over was Grant's (co-owner) attention to detail and his ability to focus on what my goals and priorities were for the project. His team completed the job over 3 days as there was significant duct work changes and the relocation of all of the equipment. They also completed the job with little downtime so we weren't left overnight without heat during freezing winter temperatures.

by Private User from Oshawa on Twintech Heating and Cooling

My father woke up to no heat one Saturday morning. We had a few names that friends had recommended but while checking out the companies' ratings on HomeStars, we found Twintech with great ratings too. The other companies either didn't get back to us or didn't have time to come at such short notice. TwinTech made the time in their schedule for what they judged to be an emergency: no heat in the home of an elderly person. At no extra fee for a short notice, weekend visit. They recommended an upgraded furnace unit and explained that we would qualify for a rebate that would bring the price down to that of a lower model. They set us up with the rep from the MNR that covers the rebate so that we didn't have to deal with the paperwork & phone calls ourselves. Installation was quick, efficient, & smooth. We were so pleased with their service we ordered a new water heater too. Both are working great (efficient & quiet!) & my father is safe & comfortable. We can't say enough about how pleased we are with their service. We have already recommended them to others.

by joe calabro in Pickering on Twintech Heating and Cooling

Twintech Heating & Cooling. I just want to say thanks for helping me . My Furnace stopped working. And l phone Dave Getgley he set me up with Greg. What an amazing team they did a great job in setting me up with a new Furnace. Anyone that needed a new Furnace these are the guys to call. Thanks again for a job well done.

by Peter from Ajax on Twintech Heating and Cooling

Our home has had poor heating and air conditioning the past couple of years. Dave recommended a Goodman solution with more power than we had. Grant and Greg installed the units in late November. Heating is better than ever. We have a warm home again and look forward to the winter. Can't wait to see how the AC runs in 2018. Job was super clean and professionally done. Highly recommended.

by iqster in Toronto on Twintech Heating and Cooling

Received a new range and needed someone to disconnect the old range and connect the new gas range. They did a thorough job and were kind enough to remove the old range from the house. Thank you!

by AJM in Pickering on Twintech Heating and Cooling

Very satisfied with this company! Salesperson Dave was very good, very knowledgeable and gave me the impression that he wanted to sell me what I needed rather than what would put the most money in the company's pocket. He also called back after the installation to see if I was satisfied with the result. The installation crew of Greg, Grant and Peter did a great job. They arrived on time, completed the job quickly, answered all my questions and thoroughly cleaned up. They told me to call if I had any further questions. They left me with the impression that they really cared about their work and my satisfaction and that it wasn't " just a job". Prior to researching for a new furnace, I had never heard of this company but I'm glad that I did and would highly recommend them to anyone looking for a new furnace or air conditioning unit. They may be small but they do a great job!!

by David from Toronto on Twintech Heating and Cooling

I first met Greg and Grant (The Twin Brothers from Twin Tech - yup -it's not just a cool company name) back in 2014 when our furnace broke down and they installed our Carrier Furnace and AC that we purchased through Sears. I liked them instantly when I met them due to their friendly and professional service, and the fact that they didn't mind taking a little extra time to explain things in terms I could understand. Since that time they have reached out to me at least once a year to ensure that everything was running smoothly with my system and to keep me appraised of their evolving services. Due to this high level of proactive customer service I didn't hesitate to call and obtain their help for a Gas Stove removal and installation. When I scheduled the call Greg and Grant let me know that they would arrive the morning of the appliance delivery to disconnect the old gas stove, and then return in the afternoon to connect the new stove. Sure enough, they did just that as promised. Where they exceeded my expectations is with the extra level of support helping to assemble the burners and grills on the stove and in the oven. This may seem like a small thing to some but to my wife who was at home during this entire process it meant a stress free transition to the meal prep for the day. When I called home to ask about the install she commented that, "they left the place cleaner than it was when they arrived and they setup all the grills on top of the stove and in the oven... they didn't have to do all that -Wow!". You know what they say, Happy Wife, Happy Life. So in summary, I am recommending Twintech Heating & Cooling for all of your Furnace, Air Conditioning, and Gas Line needs. I've even called on these guys to help swap out a leaky water valve. They are just so easy to reach and communicate with by phone, and they don't mind a text message to confirm the details. You can rest easy when you have the Twins on your side as an extension of your household maintenance plan.

by Jr in Pickering on Twintech Heating and Cooling

First thing, they actually showed up for a quote. Other big name companies in the area didn't even return my call , job was done as expected and new equipment is quiet and installed very clean and professional. Would highly recommend these guys.

by Melissa P. from Port Hope on Twintech Heating and Cooling

They removed our old furnace and replaced it with a new furnace and AC system.