Amana PTAC Air Conditioner Error Codes

CODE: FP.
RESULT: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.
FIX: No Action required. This setting will disengage when the room temperature rises above 43°F.

CODE: Fd.
RESULT: Front Desk switch is closed. All outputs are switched off.
FIX: Open front desk switch to allow occupant unit operation.

CODE: Eo.
RESULT: Un-Configured Service Board - All operation held awaiting configuration.
FIX: Enter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.

CODE: EH.
RESULT: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
FIX: Open front emergency hydronic switch to allow occupant unit operation.

CODE: LS.
RESULT: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.
FIX: Open load shedding switch to allow occupant unit operation.

CODE: On.
RESULT: Control is configured to respond to a wired thermostat.
FIX: No action if a wired thermostat is being used.Otherwise, see Configuration Settings.

CODE: oP.
RESULT: Open Door Lockout (DS1 & DS2 open; wireless).
FIX: Close Room Door. Unit will not condition space with door open.

CODE: nP.
RESULT: Window Switch Lockout - (LS & INN open).
FIX: Close Room Door or Window. Unit will not condition space with door or window open.

CODE: HP.
RESULT: Heat Sentinel - (WIAT > u3).
FIX: No action required. This setting will disengage when the room temperature falls.

CODE: Ur.
RESULT: Un-Rented Status (EHH & INN or wireless).
FIX: Front Desk needs to set to Rented mode (if applicable).

CODE: F1.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.

CODE: F2.
RESULT: Wireless Remote Thermostat failure.
FIX: Replace Wireless Thermostat.

CODE: F3.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor.

CODE: F4.
RESULT: Indoor Coil Thermistor either above or below operating tolerances.
FIX: Replace Red Indoor Coil Thermistor.

CODE: F5.
RESULT: Wireless Thermostat failure.
FIX: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.

CODE: F6.
RESULT: Indoor Discharge Thermistor either above or below operating tolerances.
FIX: Replace Yellow Indoor Discharge Thermistor.

CODE: Fb.
RESULT: Low Remote Battery Warning.
FIX: Replace Batteries in Wireless Devices.

CODE: H1.
RESULT: High Voltage Protection engaged. Power supply voltage is to high.
FIX: Check for incoming power at correct voltage.

CODE: br.
RESULT: Brown Out Protection engaged. Power was lost or voltage is low.
FIX: Check for incoming power at correct voltage.

CODE: L6.
RESULT: Discharge Air Too Hot.
FIX: Clean Filter or Remove Air Blockage.

CODE: LC.
RESULT: Outdoor Coil Thermistor temperature high.
FIX: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.

CODE: C2.
RESULT: Indoor Air Recirculation. Large delta between thermostat and return.
FIX: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.

CODE: C5.
RESULT: Outdoor Coil temperature too high for outdoor ambient temperature.
FIX: Check for Blocked Outdoor Air or Clean Coil.

CODE: C1.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C3.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C4.
RESULT: Indoor Coil froze up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C6.
RESULT: Poor Unit Performance.
FIX: Check for blower motor, compressor, or electric heat operation.

CODE: C7.
RESULT: Indoor Freezing Lockout (ICT - IAT > 20) +10 Min.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


See What Our Customers Are Saying:

by silvercola from Toronto on Twintech Heating and Cooling

I received three quotes before deciding to choose Twintech. Dave's prices was much more reasonable than the competitors. I most appreciated their honest recommendations. Others tried to oversell their products and services. Thank you Dave!

by Shane from Whitby on Twintech Heating and Cooling

They had the best price and did a great job on the installation. Recommend them to anyone.

by gabnai7 on Twintech Heating and Cooling

It was a amazing and professional high quality job
Friendly and very helpful representatives
Thank you for understanding my concern
And explain very well
Overall we pleased with your service
Tanks

by Linda, Toronto on Twintech Heating and Cooling

My 19 year old furnace stopped working when the cold weather hit in November, and I was left without heat. I interviewed several companies and found TWINTECH HEATING and COOLING to be very knowledgeable, quick to respond to my inquiries and very competitively priced.
Dave provided all of the information and pricing ahead of time and set up the appointment for the installation. Greg and Mitch arrived on time to do the installation and worked quickly and efficiently to complete the job.
After the completion of the installation, Dave followed up to ensure that everything was working well and that I didn't have any concerns.
Overall, this was a low-stress and flawless experience from start to finish. I would highly recommend TWINTECH HEATING and COOLING to anyone that requires a new furnace.

by Sean, Whitby on Twintech Heating and Cooling

Our 20 year old furnace broke down during the first cold weekend this past November and our usual HVAC company never returned our phone call. Their loss, missing out on a sale since we didn't want to spend much fixing an old furnace and our 40 year old air conditioner was also long overdue for replacement. We proceeded in obtaining three different quotes for furnace and air conditioner replacement, and proceeded with the one we received from Twintech.


Dave was friendly, knowledgable and accommodating to our schedule and provided with us with a price that fell in the middle of the three quotes that we had. We felt that the Amana furnace and air conditioner he quoted us on were the best products and value offered to us and felt most comfortable with the professionalism and reputation of Twintech.


Greg, Grant and Mitch were at our house for installation the day after we decided to proceed. The guys were friendly and informative, the job was completed efficiently and workmanship appears excellent. Our house is certainly much more comfortable with the new two-stage variable speed Amana furnace compared to the old clunker! And, we're looking forward to enjoying the new air conditioner once summer rolls around again. Thanks Twintech!

by Bill, Oshawa on Twintech Heating and Cooling

We are very happy with our new furnace. The service was excellent the guys worked 6 hours straight through and there was no mess at all they took the old furnace box’s etc with them they then explained everything to us they were very helpful and pleasant , when we need a new air conditioner we know who to call!

by Ken, Bomanville on Twintech Heating and Cooling

The crew from sales to installation was very professional and had great attention to detail

by Tracy, Pickering on Twintech Heating and Cooling

We couldn’t have been more impressed with Twintech - from our first service call with Mitch who took the time to thoroughly diagnose the issue with our furnace, to Dave who proposed a well thought out solution to meet our needs and finally Greg and team who acted quickly to install given we had no heat.


We did our due diligence by soliciting quotes from alternate providers and were shocked and disappointed by the aggressive and manipulative tactics used.


Twintech was honest in their approach, detailed in their product knowledge, reasonably priced, diligent in their follow-up and valued our business.


Well done Twintech! You made this a positive experience for us and our new furnace works beautifully!

by Skapoor, Ajax on Twintech Heating and Cooling

We recently purchased an Amana high efficiency furnace and humdifier through Twintech. The work was completed very professionally and the quality of the workmanship was high. There was some additional sheet metal work required to complete the installation, which they were able to complete themselves. Overall I am very pleased with the work and would highly recommend Twintech for a furnace replacement.

by Steve, Oshawa on Twintech Heating and Cooling

We were very pleased with every aspect of the work that was done. They were very professional and polite. They arrived when they said they would and job was completed on estimated time


We would highly recommend them to whoever needed a recommendation


We have a very large dog and they were very understanding and respectful of him being around