Amana PTAC Air Conditioner Error Codes

CODE: FP.
RESULT: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.
FIX: No Action required. This setting will disengage when the room temperature rises above 43°F.

CODE: Fd.
RESULT: Front Desk switch is closed. All outputs are switched off.
FIX: Open front desk switch to allow occupant unit operation.

CODE: Eo.
RESULT: Un-Configured Service Board - All operation held awaiting configuration.
FIX: Enter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.

CODE: EH.
RESULT: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
FIX: Open front emergency hydronic switch to allow occupant unit operation.

CODE: LS.
RESULT: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.
FIX: Open load shedding switch to allow occupant unit operation.

CODE: On.
RESULT: Control is configured to respond to a wired thermostat.
FIX: No action if a wired thermostat is being used.Otherwise, see Configuration Settings.

CODE: oP.
RESULT: Open Door Lockout (DS1 & DS2 open; wireless).
FIX: Close Room Door. Unit will not condition space with door open.

CODE: nP.
RESULT: Window Switch Lockout - (LS & INN open).
FIX: Close Room Door or Window. Unit will not condition space with door or window open.

CODE: HP.
RESULT: Heat Sentinel - (WIAT > u3).
FIX: No action required. This setting will disengage when the room temperature falls.

CODE: Ur.
RESULT: Un-Rented Status (EHH & INN or wireless).
FIX: Front Desk needs to set to Rented mode (if applicable).

CODE: F1.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.

CODE: F2.
RESULT: Wireless Remote Thermostat failure.
FIX: Replace Wireless Thermostat.

CODE: F3.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor.

CODE: F4.
RESULT: Indoor Coil Thermistor either above or below operating tolerances.
FIX: Replace Red Indoor Coil Thermistor.

CODE: F5.
RESULT: Wireless Thermostat failure.
FIX: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.

CODE: F6.
RESULT: Indoor Discharge Thermistor either above or below operating tolerances.
FIX: Replace Yellow Indoor Discharge Thermistor.

CODE: Fb.
RESULT: Low Remote Battery Warning.
FIX: Replace Batteries in Wireless Devices.

CODE: H1.
RESULT: High Voltage Protection engaged. Power supply voltage is to high.
FIX: Check for incoming power at correct voltage.

CODE: br.
RESULT: Brown Out Protection engaged. Power was lost or voltage is low.
FIX: Check for incoming power at correct voltage.

CODE: L6.
RESULT: Discharge Air Too Hot.
FIX: Clean Filter or Remove Air Blockage.

CODE: LC.
RESULT: Outdoor Coil Thermistor temperature high.
FIX: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.

CODE: C2.
RESULT: Indoor Air Recirculation. Large delta between thermostat and return.
FIX: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.

CODE: C5.
RESULT: Outdoor Coil temperature too high for outdoor ambient temperature.
FIX: Check for Blocked Outdoor Air or Clean Coil.

CODE: C1.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C3.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C4.
RESULT: Indoor Coil froze up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C6.
RESULT: Poor Unit Performance.
FIX: Check for blower motor, compressor, or electric heat operation.

CODE: C7.
RESULT: Indoor Freezing Lockout (ICT - IAT > 20) +10 Min.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


See What Our Customers Are Saying:

by Brent L on Twintech Heating and Cooling

Work was done on schedule, professionally, according to quote and with minimal inconvenience to building users. Very happy with the end result. The only area for improvement from my experience - need more timely quoting process.

by Karen on Twintech Heating and Cooling

The team was great! Very knowledgeable, professional and extremely helpful. A few days after install the unit didn’t seem to be working, user error, but within minutes of contacting them..on a Saturday.. a tech was on the phone troubleshooting with us. I highly recommend Twintech for your cooling or heating needs. They stand by their products and a pleasure to deal with.

by Rob on Twintech Heating and Cooling

During the hottest week in the summer our old A/C decided to call it quits. I called Twintech Heating & Cooling after receiving a referral from a family member; came highly rated for being an honest, family-run business, who appreciates their customers. Dave was able to accommodate my hectic schedule and book a late evening appointment to walk through the specifics. Greg and Mitch arrived exactly on time a few days later, were very polite and friendly, and within a couple of hours had a new unit up and running. I also received a follow-up call to ensure we were happy with the Amana.

by Linda Robinson on Twintech Heating and Cooling

They were on time and very professional. I'm so glad I decided to go with Twintech, thanks!

by Famcam1953 on Twintech Heating and Cooling

Timely and appreciated - this was during the hottest days this year when our Air and Furnace way.
Efficient. Professional. No BS or overselling. What was promised, was delivered at a cost-effective price point.
Down to earth.

by DG Sellers on Twintech Heating and Cooling

Professionally done and took care to cover all entry floors to the house for the installers to remove the old furnace and install a new furnace.
I also made recommendations of the tankless water heater that we had installed and items to address. We did not know they also installed tankless water heaters.

by Bill, Pickering on Twintech Heating and Cooling

Price was not the cheapest nor the most expensive of my quotes. It's the quality of the installation that makes for a good AC system. The twins' knowledge & professionalism was evident in the small details:
Very clean work. Greg made sure that the refrigerant level & temperature were correct. They reinstall the insulation & vapor barrier around the wall. The outside electrical cords were secured to the wall. Proud to support this local company. Thank you.

by Taz on Twintech Heating and Cooling

Great team of guys came to do the work. Very professional. Arrived on time worked very efficiently and were very clean. They answered any questions we had without hesitation. The air conditioner works great and is so quiet. I highly recommend them and they don't try to up-sell anything right from the start.

by Jordan on Twintech Heating and Cooling

The service was prompt, professional and very courteous. Competitive price. Would highly recommend this company.

by David on Twintech Heating and Cooling

Excellent workmanship, and quick response. Would recommend Twintech to anyone.