CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

by Trevor Owens on Twintech Heating and Cooling

I returned from vacation to find my AC unit on the Fritz. After calling way too many places I connected with TwinTech. I’ve used the company in the past for my furnace so I was happy when I recognized Greg at my front door. He’s great and the service is always top notch. I’d highly recommend using twintech for honest, superior service in the Durham region. Thanks!

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

by Courtney Parkes on Twintech Heating and Cooling

Just hired TwinTech Heating & Cooling to do an A/C Unit removal & reinstall to allow for landscaping access on the side of my house, and they were wonderful!
Bob, Greg & Mitch make a great team! Quick appointment times, super knowledgeable, expert troubleshooting capabilities & very customer service oriented.
I would highly recommend them for all of your HVAC needs! Great job guys!!

by Jacqueline Graham on Twintech Heating and Cooling

Twintech Heating & Cooling installed my furnace in 2022 and in fall of 2023 installed my Panasonic Heat Pump. Greg and Mitch did a great job. Helped me through the rebate process. Super happy with the Heat Pump. Only used my furnace 5 times this winter. Energy bills lower, carbon emissions lower.Thank you Twintech. I recommend highly!

by Bill Grainger on Twintech Heating and Cooling

Just had a new furnace installed by Twintech. I can’t express how great these guys are at what they do. From the sales to installation they were professional all the way. Very reasonable pricing and courteous during the installation and willing to answer any questions I had. Highly recommended !!!

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Furnace Thermostat Issues

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 24, 2024

Furnace thermostat issues can lead to inefficient heating and discomfort, especially as temperatures drop. If your furnace isn’t functioning properly, the thermostat could be a common culprit. Here are some common thermostat-related problems an

Read More

My AC is Not Blowing Cold Air

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 7, 2024

There could be several reasons why your air conditioner isn't blowing cold air. Here are a few common issues and troubleshooting steps: Thermostat Settings: Make sure your thermostat is set to "cool" mode and the temperature is

Read More

My AC Unit is Not Working, What Now?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - June 29, 2022

You may encounter many problems with your air conditioner and while it is true that most problems require HVAC experts to repair them, there are some troubleshooting tips that can help homeowners fix the simple issues.Here is a troubleshooting guide

Read More

AC keeps freezing up?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 31, 2023

There are several possible reasons why your air conditioner (AC) may be freezing up. Here are some common causes: Dirty or clogged air filters: When the air filters are dirty or clogged, it restricts the airflow over the evaporator coils. Th

Read More