CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

I left a live chat message on their website that my air conditioning was not working. Within 1hr a representative called me to discuss my options.
The next day he came to the house to review my needs and give me a price for a new system. Price quoted was less than I expected and the installation was completed the following day. I found their salesman and the installers very knowledgeable and easy to deal with. All my questions were answered. Everything was properly explained in regards to what unit was needed and why, along with instruction where needed for use.
The installers made sure everything was working properly before they left.

by Samta Chanana on Twintech Heating and Cooling

This is to thank Twintech Heating and Cooling for their exceptional and timely service. Mitch, their technician was very courteous and generous with his time right from his first meeting with us. He not only took the time to check everything but also educated us on why we needed what he recommended. Greg and Mitch graciously accommodated us on our requested day and time for job to be done. They were both very courteous and responsive to our needs and special requests especially in a tight spot. The job was finished neatly and on time. Thank you Twintech for your great service !

by Private User on Twintech Heating and Cooling

They came the day and time they had planned for us and were very fast and efficient! The AC works amazing and it is amazing during the heat of the summer we have already got! Thanks for everything you did for us!

by Private User on Twintech Heating and Cooling

Would recommend this company to friends and family in a heartbeat. Very professional , on time and left no mess when the job was done.

by stefany on Twintech Heating and Cooling

Great customer service. Responsive and professional. I would highly recommend Twintech, I used them previously for repair service and a new air conditioner- very satisfied.

by dianeramsden on Twintech Heating and Cooling

Our air conditioner failed. Made a call and within 15 min a technician was at our door.
The issue was fixed and many suggestions were provided.
Thanks to Mitch. Great service !

by Kazuko on Twintech Heating and Cooling

Our furnace was rattling, as soon as we put our air conditioner on this past week. We had researched looking for a company that was Registered with Better Business Bureau, and this company TwinTech, had A+ Rating. Scott, was immediately helpful via text/phone and sent his technician as soon as he was able...Mitchell/technician provided great professional service. Thank you TwinTech.
Sean and Debbie

by ANOOP on Twintech Heating and Cooling

I contacted various companies when looking to install a new furnace and I found Twintech to be transparent with their communication and approach. They had options to suit my various requirements and the price vs quality was very good. The after installation communication was also very good and they answered all queries I had.

by Private User on Twintech Heating and Cooling

My furnace broke down last month. The team was quick to respond, courteous, professional and mindful of COVID-19 concerns. I highly recommend them if you are considering replacing or servicing your HVAC equipment.

by Private User on Twintech Heating and Cooling

I was very happy with the installation and price. I would definitely recommend. Thank you Twintech.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Twintech - Trusted Heat Pump Sellers and Consultants in Pickering

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 21, 2025

When it comes to energy-efficient, year-round comfort in the Town of Pickering, more and more homeowners are turning to heat pumps. And when you're looking for a trusted expert to guide you through the process of selecting, installing, and mai

Read More

Gas Fireplace Maintenance Tips

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 28, 2019

There has always been something comforting about fireplaces. On a cold winter day, you may come inside to grab a hot beverage and warm up by a roaring fire. Not only do fireplaces warm up your home, but they also make your house more inviting and inc

Read More

Increasing the Longevity of Your Air Conditioner

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 18, 2024

Increasing the Longevity of Your Air Conditioner Your air conditioner is an essential appliance, especially during the hot summer months. Proper care and maintenance can significantly extend its lifespan, saving you money on repairs and replacements

Read More

Twintech - Your Experts on Heat Pump Rebates in Toronto

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 19, 2025

If you live in the Durham Region or Toronto and are considering upgrading your home’s comfort system, now is the perfect time. With generous rebates available on Amana and Panasonic heat pumps, homeowners can save thousands while enjoying ef

Read More