CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by stan.marosek from Ajax on Twintech Heating and Cooling

Class Act ! These guys were professional right from the quote stage through to installation. They know their stuff and took their time to help educate me. They take pride in their work and it shows. I would recommend TwinTech Heating and Cooling to anyone. Keep up the great work !!!

by W. Lacombe in Pickering on Twintech Heating and Cooling

This Company is terrific. No high pressure sales and they deliver exactly what they promise to deliver. The new furnace is great and we now get consistent temperatures throughout the house. The installers were great and very efficient and completed the work on schedule on the promised day. Everyone representing this company was very aware of their presence in our house and worked diligently to keep our home as uninterrupted and as clean as was humanly possible. We did not need to go around the house to clean up after they left, what a nice surprise. We have had follow up by the company to ensure everything is to our satisfaction. How unusual in today's environment. The impression left by Twintech is that they care about us and our home. This is so refreshing in today's high tech world. Out thanks go out to Dave in sales and G, G, and P (the installers).

by jiinyiong in Ajax on Twintech Heating and Cooling

They were Timely and professional. They were very Knowledgeable with answering all of my questions.

by Connie in Pickering on Twintech Heating and Cooling

The entire process was prompt and professional, from the initial quote to the installation of the new furnace. The team installed the new furnace and removed the old one in approx. 4 hrs. The guys were very knowledgeable and gave me lots of information. I have used Twintech before for a new A/C installation and new I was in good hands.

by Valentine in Pickering on Twintech Heating and Cooling

The overall experience dealing with this company was great from start to finish when getting a new furnace and ac this year. Everything was clearly explained to us during our consultation with Dave and there were no surprises with added costs. The work was done as expected and their response time to inquiries were very timely generally within a few hours or less. They are all very professional and was a pleasure to do business with them. Highly recommend to anyone looking for honest quality professional service.

by Jiri in Toronto on Twintech Heating and Cooling

From the initial contact we had an excellent experience with this company and all its personnel. Dave Gergley was an excellent, helpful, sales person and solicitous of our needs. He recommended only what was required and did not up sell or make any suggestions for products that we did not need, such as a new A.C. He explained the rebate process and basically outlined how to get the best furnace at the lowest price. When it was time for installation, the technicians could not have been more considerate, careful, attentive to detail, obviously committed to safety and optimum functioning of the appliance they were setting up. We have been perfectly satisfied with the functioning of the furnace and all aspects of acquiring it from the initial contact with Dave through to the installation process and follow ups inquiring about our satisfaction. Also they initiated the rebate process and contacted the appropriate inspection agency to carry it out. We highly recommend this company for all heating and cooling needs and we will contact them again when it is time to replace our A.C.

by Drew in Pickering on Twintech Heating and Cooling

Twintech was excellent from the initial quote and throughout the install. They had a competitive rate for hot water tank and ended up buying the tank from them, had them remove the old tank and install the new one. The day of install they were prompt and out in about 2 hours. Professional , courteous really great guys. We took a look at my 30 year old furnace and they were able to offer some suggestions for future there too.

by Harry in Toronto on Twintech Heating and Cooling

Ever since I turned on my furnace on Oct 2018 I hear a humming sound when the furnace fan kicks in. I called Adamson Air System who installed my furnace 7 years ago and couldn't figure it out the problem. I just wasted money to the guy who couldn't figure it out. I found Twin Tech via Amana / Goodman website. I checked the reviews from previous Twin Tech customers. I called Greg and was onsite on time this morning Sunday, Nov 25 2018. He figured it out what's wrong with the furnace and explained what the previous installer (adamson air system) did wrong when they installed it. His knowledgeable about his job. He recommend to replace the fun motor because the sound is not normal when it's running. Looking forward to see him again to replace the fan motor.

by Roger in Pickering on Twintech Heating and Cooling

Our house is over 22 years old and I had been researching furnaces and A/C brands for a while and thought it was time to take the plunge. After calling three different companies to come in and quote the job, this one won me over. From the first visit from Dave all the way to the end of the install by Greg, Grant, and Piotr, I was glad to have picked this company. Dave was very knowledgeable and really took the time to explain what kind of quality installation I was going to get as well as showing me some of their previous work and certificates.

I was also surprised at how quick the installation took and how nice everything looked afterward, I mean it's only a furnace right? They even re positioned the furnace so that I have easier access to my filter and humidistat, awesome! If you are looking for a company that cares about their customers and is proud about the quality of work they do, along with a great and competitive price, then stop right here because you found it.

by Louis in Pickering on Twintech Heating and Cooling

Once our AC Unit started to fail, I called our past Heating & Cooling provider for support. The response was we needed a new motor for our Furnace. It was time to check their Quote against the marketplace, I reached to other providers online. One of the owner of Twintech (Greg), called me and offered a preliminary Quote and recommendation online. The others needed to set an appointment and came to measure and spend 1 hour before offering a quote. Then I asked Twintech to come finalize their quote to make sure their recommendation was aligned and met our needs.

Twintech was professional throughout the process, easy to deal with (Web, Phone and in Person), price right and met their commitment. Their team expedited the process and installation, arranged for a energy assessment for available rebates and most importantly, delivered on their commitment and managed to do a few extras. They installed a New Furnace, AC unit and Nest thermostat in a day, remove all older units, left the house and outdoors clean and without any debris. Great to be able to support a Local Company, Neighbour and Professional team - Well Done Team Twintech !!!