The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.


CODE: On solid, no flash.
RESULT: None.
FIX: Normal operation.

CODE: Rapid continuous flashing.
RESULT: Standard Thermostat Control 288ANA/180ANA only.
FIX: Unit being controlled by standard thermostat inputs instead of Evolution Control. Only high stage operation is aveliable. This operating mode should be used in emergency situations only.

CODE: 1 pause.
RESULT: None.
FIX: Normal operation.

CODE: 2 pause.
RESULT: None.
FIX: Normal operation.

CODE: 16.
RESULT: System Communications Failure.
FIX: Communication with User Interface lost. Check wiring to UI, indoor and outdoor units.

CODE: 25.
RESULT: Invalid Model Plug.
FIX: Control does not detect a model plug or detects an invalid model plug. Unit will not operate without correct model plug.

CODE: 31.
RESULT: High Pressure Switch Open.
FIX: High - pressure switch trip. Check refrigerant charge, outdoor fan operating and coils for airflow restrictions.

CODE: 32.
RESULT: Low Pressure Switch Open.
FIX: Low - pressure switch trip. Check refrigerant charge and indoor air flow.

CODE: 45.
RESULT: Control Fault.
FIX: Outdoor unit control board has failed. Control board needs to be replaced.

CODE: 46.
RESULT: Brown Out (230v).
FIX: Line voltage < 187v for at least 4 seconds.

CODE: 47.
RESULT: No 230v at Unit Measured at L1 and L2 on circuit board.
FIX: There is no 230v at the contactor when indoor unit is powered and cooling/heating demand exists.

CODE: 53.
RESULT: Outdoor Air Temp Sensor Fault.
FIX: Outdoor air sensor not reading or out of range.

CODE: 55.
RESULT: Outdoor Coil Sensor Fault.
FIX: Coil sensor not reading or out of range. Ohm out sensor and check wiring.

CODE: 56.
RESULT: Thermistors out of range.
FIX: Improper relationship between coil sensor and outdoor air sensor. Ohm out sensor and check wiring.

CODE: 71.
RESULT: Low Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 72.
RESULT: High Stage Thermal Cut out.
FIX: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long.

CODE: 73.
RESULT: Contactor Shorted.
FIX: Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring error.

CODE: 74.
RESULT: No 230v at Compressor.
FIX: Compressor voltage not sensed when compressor should be starting. Contactor may be stuck open or there is a wiring error.

CODE: 75.
RESULT: Low Stage Did Not Start.
FIX: Specified start voltage at VR terminal was not achieved in low stage. Start relay was de-energized after 1 second.

CODE: 76.
RESULT: Low Stage Did Not Start 3 times.
FIX: For 3 consecutive low stage starts, the specified start voltage at VR terminal was not achieved and start relay was de-energized. Low stage locked out for 30 minutes.

CODE: 77.
RESULT: High Stage Did Not Start.
FIX: Specified start voltage at VS terminal was not achieved in high stage. Start relay was de-energized after 1 second.

CODE: 78.
RESULT: High Stage Did Not Start 3 times.
FIX: For 3 consecutive high stage starts, the specified start voltage at VS terminal was not achieved and start relay was de-energized. High stage locked out for 30 minutes.

CODE: 81.
RESULT: Low Stage Thermal Lockout.
FIX: Thermal cutout occurs in three consecutive low/high stage cycles. Low stage locked out 4 hours or until 24v power recycled.

CODE: 82.
RESULT: High Stage Thermal Lockout.
FIX: Thermal Lockout occurs in three consecutive high/low stage cycles. High stage locked out for 4 hours or until 24V power recycled.


See What Our Customers Are Saying:

by Nancy H. from Oshawa on Twintech Heating and Cooling

Work was performed in a clean and timely manner. The furnace and metal work was performed by the Twintech team (did not require separate contractor to do the metal work). Energy audit was arranged and promised rebates were received. The overall price was very competitive. We have recommended Twintech to several of our friends and family. Awesome job.

by Syd from Whitby on Twintech Heating and Cooling

Grant and Greg installed a heating and AC system in our new Linwood post and beam home. Post and beam can be challenging structures for running ductwork and their high ceilings and open concept frequently frustrate efforts at balancing air flow and controlling temperatures. But these guys did it and did it right the first time. Even the building inspector was impressed with what he saw. More importantly, the boys brought a high degree of trust and integrity to the job. Something in short supply these days.

by jenner iksmom from Oshawa on Twintech Heating and Cooling

Very polite and professional. They removed my o
ld furnace and A/C and installed my new ones. They were efficient and thoroughly cleaned up when they were done! I would highly recommend them!

by Rob from Toronto on Twintech Heating and Cooling

Pro from start to finish. They were able to fix my gas fireplace at very little cost as well.

by murray mcmichael from Ajax on Twintech Heating and Cooling

Excellent installation very knowledgeable gentlemen! Would highly recommend them to all my friends for any hvac work !

by Private User from Private User on Twintech Heating and Cooling

I have used Twintech many times over the years. They always arrive quickly and get the issue fixed. The most recent incident was when my air conditioner broke last week I called Greg at 11:30am and he was at my home by 2:30pm he had the unit fixed by 3:30pm. Twintech are very reliable and honest and they are experts in the field. I have already recommended them to many of my friends. I would not use anyone but them for my heating and air conditioning issues.

by Kate A in Pickering on Twintech Heating and Cooling

I would highly recommend these guys, professional, fast and competitive pricing. I moved into this place with no working AC unit with a 8 month baby, he was able to come with in a week to fix even in the busy summer days. He really values his customers , I am already recommending to my neighbors.

by Private User in Whitby on Twintech Heating and Cooling

Very impressed they arrive to quote even though I had forgotten to call them back to confirm date & time. They showed the day before installation to deliver the unit. Returned the next day as promised at 9am. Project was completed in a professional manner. They even fixed a few things that they noticed were not installed correctly, or to code by previous heating & air contractors we had at our residence before. Would recommend this company to everyone!

by Private User from Bowmanville on Twintech Heating and Cooling

Greg removed old oil furnace and oil tank from basement relocated new Napoleon propane furnace to allow duct work to be rerouted to a much more suitable location. Moved air conditioner to the new furnace. Dave recommended two available grants to assist with cost. They kept to their original quoted price which was substantially lower than a competitors for the same furnace and work. They completed the work as stated when stated and left the area clean and tidy. We are very pleased with the outcome.

by astephenson in Oshawa on Twintech Heating and Cooling

Twintech installed a Goodman furnace and ac init. Very professional install, both units are working well.