Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Bill, Whitby on Twintech Heating and Cooling

Reasonable price and the workmanship was prompt and timely and the employees were great to deal with.

by Nadia, Toronto on Twintech Heating and Cooling

The sales process was friendly, informative, and very consultative. They worked hard to earn our business by taking a careful look around our home to assess our needs, providing a lot of information about the product, and answering all our questions and finding the right solution for our home at a competitive price. They prepared us very well for what to expect on installation day, and the installation went very smoothly - no surprises, all very professional! They gave us a call after installation to ensure we were happy with the work. We're very happy that we chose to work with TwinTech to get our new furnace.

by Private User on Twintech Heating and Cooling

Twintech promptly responded to request for quotation. They were thorough and helpful in explaining options. The quote was very competitive. Installation of new furnace was very professionally completed. Excellent work.

by Rita, Scarborough on Twintech Heating and Cooling

When our old oil furnace finally broke down we decided it was time to finally convert to natural gas and finally install central air conditioning at the same time. Knowing it was going to be a significant investment for us, we wanted to make the right choice. Twintech came highly recommended by a friend and we were not disappointed. From the first contact with the salesperson, until the final touches on the installation, we were so pleased with their service. Everyone from the company was so friendly, efficient and a pleasure to deal with. Best of all, the cost was very competitive. We would certainly recommend Twintech to anyone requiring HVAC work in their home.

by Bob S, Pickering on Twintech Heating and Cooling

Mitch from Twintech came out for our annual furnace inspection. We found him to be friendly, conscientious & he left the work area clean. We were also very impressed with the thoroughness of the job he did. This is the 2nd job we’ve had Twintech do for us & have been very happy with the results for each. We highly recommend this company. Thank you, Mitch, Dave & Greg.

by Brent L on Twintech Heating and Cooling

Work was done on schedule, professionally, according to quote and with minimal inconvenience to building users. Very happy with the end result. The only area for improvement from my experience - need more timely quoting process.

by Karen on Twintech Heating and Cooling

The team was great! Very knowledgeable, professional and extremely helpful. A few days after install the unit didn’t seem to be working, user error, but within minutes of contacting them..on a Saturday.. a tech was on the phone troubleshooting with us. I highly recommend Twintech for your cooling or heating needs. They stand by their products and a pleasure to deal with.

by Rob on Twintech Heating and Cooling

During the hottest week in the summer our old A/C decided to call it quits. I called Twintech Heating & Cooling after receiving a referral from a family member; came highly rated for being an honest, family-run business, who appreciates their customers. Dave was able to accommodate my hectic schedule and book a late evening appointment to walk through the specifics. Greg and Mitch arrived exactly on time a few days later, were very polite and friendly, and within a couple of hours had a new unit up and running. I also received a follow-up call to ensure we were happy with the Amana.

by Linda Robinson on Twintech Heating and Cooling

They were on time and very professional. I'm so glad I decided to go with Twintech, thanks!

by Famcam1953 on Twintech Heating and Cooling

Timely and appreciated - this was during the hottest days this year when our Air and Furnace way.
Efficient. Professional. No BS or overselling. What was promised, was delivered at a cost-effective price point.
Down to earth.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

3 Benefits of Cold Climate Source Heat Pumps

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 1, 2019

During the winter, it isn’t uncommon for the temperature to drop to, and remain at, freezing temperatures for the entire season.  Due to this temperature shift, many homeowners will find themselves feeling extremely uncomfortable. Th

Read More

Why Should I Change My Air Filter?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 22, 2020

Your furnace and air conditioner work hard to keep your home comfortable during the cold and warm seasons. During these seasons, you should be checking your filter every 30 days and changing the filters at least every three months, depending on how o

Read More

Top Ways to Save Some Money During the Colder Months

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 27, 2020

In Canada, we spend most of the year using our heaters. You'd think that we know everything there is to know about our heating systems. You'll be surprised how many homeowners do not know that their heating system at home is not efficient as they thi

Read More

Heat Pumps - A Smart Move for Ontario Homes

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 5, 2025

Ontario homeowners know the struggle of dealing with hot, humid summers and long, cold winters. Traditionally, this has meant separate systems: an air conditioner for cooling and a furnace for heating. But with modern heat pump technology, one

Read More