Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by iqster in Toronto on Twintech Heating and Cooling

Received a new range and needed someone to disconnect the old range and connect the new gas range. They did a thorough job and were kind enough to remove the old range from the house. Thank you!

by AJM in Pickering on Twintech Heating and Cooling

Very satisfied with this company! Salesperson Dave was very good, very knowledgeable and gave me the impression that he wanted to sell me what I needed rather than what would put the most money in the company's pocket. He also called back after the installation to see if I was satisfied with the result. The installation crew of Greg, Grant and Peter did a great job. They arrived on time, completed the job quickly, answered all my questions and thoroughly cleaned up. They told me to call if I had any further questions. They left me with the impression that they really cared about their work and my satisfaction and that it wasn't " just a job". Prior to researching for a new furnace, I had never heard of this company but I'm glad that I did and would highly recommend them to anyone looking for a new furnace or air conditioning unit. They may be small but they do a great job!!

by David from Toronto on Twintech Heating and Cooling

I first met Greg and Grant (The Twin Brothers from Twin Tech - yup -it's not just a cool company name) back in 2014 when our furnace broke down and they installed our Carrier Furnace and AC that we purchased through Sears. I liked them instantly when I met them due to their friendly and professional service, and the fact that they didn't mind taking a little extra time to explain things in terms I could understand. Since that time they have reached out to me at least once a year to ensure that everything was running smoothly with my system and to keep me appraised of their evolving services. Due to this high level of proactive customer service I didn't hesitate to call and obtain their help for a Gas Stove removal and installation. When I scheduled the call Greg and Grant let me know that they would arrive the morning of the appliance delivery to disconnect the old gas stove, and then return in the afternoon to connect the new stove. Sure enough, they did just that as promised. Where they exceeded my expectations is with the extra level of support helping to assemble the burners and grills on the stove and in the oven. This may seem like a small thing to some but to my wife who was at home during this entire process it meant a stress free transition to the meal prep for the day. When I called home to ask about the install she commented that, "they left the place cleaner than it was when they arrived and they setup all the grills on top of the stove and in the oven... they didn't have to do all that -Wow!". You know what they say, Happy Wife, Happy Life. So in summary, I am recommending Twintech Heating & Cooling for all of your Furnace, Air Conditioning, and Gas Line needs. I've even called on these guys to help swap out a leaky water valve. They are just so easy to reach and communicate with by phone, and they don't mind a text message to confirm the details. You can rest easy when you have the Twins on your side as an extension of your household maintenance plan.

by Jr in Pickering on Twintech Heating and Cooling

First thing, they actually showed up for a quote. Other big name companies in the area didn't even return my call , job was done as expected and new equipment is quiet and installed very clean and professional. Would highly recommend these guys.

by Melissa P. from Port Hope on Twintech Heating and Cooling

They removed our old furnace and replaced it with a new furnace and AC system.

by Nancy H. from Oshawa on Twintech Heating and Cooling

Work was performed in a clean and timely manner. The furnace and metal work was performed by the Twintech team (did not require separate contractor to do the metal work). Energy audit was arranged and promised rebates were received. The overall price was very competitive. We have recommended Twintech to several of our friends and family. Awesome job.

by Syd from Whitby on Twintech Heating and Cooling

Grant and Greg installed a heating and AC system in our new Linwood post and beam home. Post and beam can be challenging structures for running ductwork and their high ceilings and open concept frequently frustrate efforts at balancing air flow and controlling temperatures. But these guys did it and did it right the first time. Even the building inspector was impressed with what he saw. More importantly, the boys brought a high degree of trust and integrity to the job. Something in short supply these days.

by jenner iksmom from Oshawa on Twintech Heating and Cooling

Very polite and professional. They removed my o
ld furnace and A/C and installed my new ones. They were efficient and thoroughly cleaned up when they were done! I would highly recommend them!

by Rob from Toronto on Twintech Heating and Cooling

Pro from start to finish. They were able to fix my gas fireplace at very little cost as well.

by murray mcmichael from Ajax on Twintech Heating and Cooling

Excellent installation very knowledgeable gentlemen! Would highly recommend them to all my friends for any hvac work !

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Is My Amana Heat Pump Good For the Environment?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 30, 2024

I can provide some general information that might help you evaluate the environmental impact of your Amana heat pump. Energy Efficiency: Heat pumps, including those made by Amana, are generally more energy-efficient than traditional heating

Read More

Panasonic Heat Pump Service Durham Region

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 21, 2025

When it comes to efficient home climate control, few solutions match the reliability and innovation of Panasonic heat pumps. Whether you're aiming to reduce your energy bills or looking for an eco-friendly way to heat and cool your home, Panas

Read More

Common Furnace Problems and How to Fix Them

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 26, 2024

Here’s a comprehensive guide to common furnace problems and how to fix them: 1. Furnace Won’t Turn On Possible Causes: Thermostat is not set correctly. Power issue (tripped circuit breaker or blown fuse). Pilot light is

Read More

How does the AC get billed?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 23, 2023

I just moved in with my best friend and we are confused on how the AC will be determined how much it costs us. We are currently going through a 110° heatwave where we live. The issue IS NOT what the temperature is set at, I grew up without

Read More