Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Tina - Whitby in Whitby on Twintech Heating and Cooling

The people from Twintech were very friendly and personable...from the salesman to the installers. The installation was done as scheduled. I love my new air conditioner. My neighbour has a York and that thing is so noisy compared to my Goodman!! Thanks Twintech!!

by Cathy f. from Pickering on Twintech Heating and Cooling

Thank you, Twintech. They installed an A/C in my home in the middle of a heat wave which we appreciated very much. I found the team good, not overly friendly, other than the brothers. Dave, the salesperson was awesome, and, it's because of him that I was sold on using Twintech. I had other questions about additional work I am curious about and would have liked them to follow up and provide a quote. Other than that, which ultimately is not related to the great work they did, I would definitely recommend them, although I don't believe they go outside of Durham (check with them).

by Linda from Durham Region on Twintech Heating and Cooling

We have used this company a few times so I can't remember exactly what we paid but I do know that their fees are always very reasonable.

The first time we called Greg was when our furnace conked out while we were away. He came right away, showed me the problem and fixed it immediately.

The second time was when we needed an air conditioner moved and lifted to a platform. Again, he showed up on time, completed the job quickly (including a new gas line) and the fee was very reasonable.

We have received a quote from Greg to replace the air conditioner and furnace and when we are ready to move ahead, we will be calling him.

I have no hesitation in recommending TwinTech!

by AS from Pickering on Twintech Heating and Cooling

Our rating for Twintech is 5/5 stars. They are very professional and efficient, and the transparency they maintain right from the preliminary assessment till the day of the work is a testament to their experience in the field. We had Twintech replace our air conditioning and furnace, and we appreciate the efforts taken by Greg.

by Raymond from Toronto on Twintech Heating and Cooling

After 18 years my Air conditioner died in the middle of a heat wave. I entered my information on Home Stars and within the hour Dave from Twin Tech responded and offered to meet me as soon as possible depending on my availability. Dave was very knowledgeable about the products Twin Tech offered and even though this was the first quote I received . I felt very comfortable in giving Twin Tech my business. maybe it was the professional approach. Needless to say that the crew with Greg and Grant arrived promptly at the time they committed to were very professional and within a few hours had the place cool. They cleaned up and one would never know that I had work done . I know that the System is new and I probably wont need to worry about it for some time. However with the professionalism displayed by the crew I feel assured that should I need to call for service Twin Tech will respond. I also know that should I need a new Heating system I will go with Twin Tech. Keep up the good work.

by gerard harrington from Ajax on Twintech Heating and Cooling

Greg and team were amazing! All interaction via email and text 100% professional. From consult to product recommendation their service was phenomenal!

Installed a Napoleon furnace (ecm dc drive variable 2-stage) and it was a game changer for the whole house. Blended air temperature through and through the entire house and it’s saving us money by cutting down our utility bill by ALOT!

by D &. from Whitby on Twintech Heating and Cooling

We purchased a new cooling & heating system from Twintech and the team was fantastic. From sales to installation, the team were great to work with. Friendly (our dog even enjoyed having them over), professional and accommodating. I’d recommend Twintech in a heart beat to anyone. Superb customer service.

by Anonymous from Pickering on Twintech Heating and Cooling

End to end service. From quote, overseeing installation, contacting and making arrangements for energy audit. Warranty program is comprehensive. Cleaned up mess of assistant walking through my place without proper indoor foot covering when I pointed out that I was not happy about footprints on my floors.

by Bob S in Pickering on Twintech Heating and Cooling

In April we hired Twintech Heating & Cooling to replace our 20 year old water tank & 35 year old air conditioner. We got 5 estimates for the job & decided to go with Twintech for the following reasons.

- The Sales Manager, Dave, was very personable & knowledgeable as all of our questions were answered. (We had a list of questions we asked each of the contractors when we got the estimates)
- We got 5 estimates for the job. All contractors verbally told us they had the required qualifications but Dave was the only one to physically show us their license & insurance documentation.
- Twintech carried the Napoleon air conditioner & we wanted to support Canadian industry as it is assembled in Barrie On.

Safety is important at Twintech as demonstrated when we discussed with Dave, the need to change our install date because of freezing rain. Access was required by navigating a set of outside steps & Dave identified that safety took precedence.
On the installation date, Greg, Peter & Grant showed up on time & methodically accomplished the removal & installation of both units. The guys did a great job cleaning up as well.

When the job was completed we mentioned to Greg that we were pleased with the work they had done & were going to have them come out & do our furnace inspection in Sept. Greg said we can save our money as he had inspected the heat exchanger on the furnace while doing the job & there was no need to have another inspection in Sept. We were very impressed with Greg’s initiative. This is top shelf service. Thank you Greg.

As the weather was too cool to complete a functional test of the air conditioner on the installation date, Dave made a follow-up call to us to see how things were going & Greg also came out to check the operation. No problems.

We are very happy we hired professionals like Dave, Greg, Grant & Peter & have no hesitation in recommending Twintech Heating & Cooling. They will now be our "go to" guys.

by ted diplock in Toronto on Twintech Heating and Cooling

These guys are the best. From start to finish they exceeded my expectations and delivered a great product. They accommodated the nuances of my 100 year old home which was really appreciated. The install was easy to schedule and done fantastically. I’m so excited to have an efficiently heated and cooled home.