Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

Excellent job. Excellent service. Competitive price. Its rare to find a company with the knowledge and professional results we have experienced with Twintech. The clean and neat installation with attention to detail and drop sheers to respect our property is a clear indication of Twintechs high level of integrity. The 1-1/2 gas line upgrade they did for our pool 3 years ago was awesome. Can't say enough. Thank-you Twintech.

by Private User on Twintech Heating and Cooling

Twitch did a great job with the installation of our new furnace. I really appreciated their honesty and I could trust what they were telling me. Another company tried to suggest significantly more work at a greater cost claiming it was necessary to meet current building code. Twintech is very fair. All staff I meet were friendly, polite and trustworthy. I would recommend Twitch for a furnace.

by Private User on Twintech Heating and Cooling

This is a professional team that's easy to deal with. I would strongly recommend them

by hj.taggart in OSHAWA on Twintech Heating and Cooling

Very professional firm from start to finish!
They removed the old oil tank and furnace. They installed air conditioning and a new propane furnace.
Professional installation, on time and no mess.
Very pleased with their work and would highly recommend the company. Our house is three stories so they spent the time to do all the calculations to make sure we would have great performance on each floor.
Thank you again!

by susieschoeppler in Oshawa on Twintech Heating and Cooling

Upon a routine yearly maintenance, it was discovered there was a leak in the heat exchanger and a I needed a new furnace. I know nothing about these things and was completely stressed out. The company I had the maintenance plan with quoted me a huge number to rent a furnace, I just wanted to cry. Then I spoke to Dave at Twintech. He was so knowledgeable and calming, provided me a fair quote and within a few days I had an amazing crew show up to my house and install my new energy efficient furnace! I have already recommended these wonderful people at Twintech to a good friend of mine. Thank you Twintech!!

by Private User on Twintech Heating and Cooling

Great service and great people to deal with, from sales to installer. I highly recommend this company.

by GR from Oshawa on Twintech Heating and Cooling

Twintech replaced our aging furnace and air conditioner recently. I highly recommend this company. Their quote was competitive, they were on time and respectful of our home and extremely professional. From the salesman to the installers and the owner who followed up afterward to ensure we were satisfied, we are very pleased with the service. We are looking forward to working with this company for all of our HVAC needs for the years to come. Excellent workmanship and service!

by nathans in Scarborough on Twintech Heating and Cooling

We wanted to get our AC replaced as it was 22-years old and added to this our furnace was costing more and more to repair. So, we decided to get both the furnace and AC replaced.

After going through a few quotes and product reviews we decided to go with Twintech. The three-men crew arrived early in the morning, wasted no time and got to work right away. By 2:00 pm, they were all done. I’ve found their work to be top notch and they were completely professional. I had all my questions answered to my satisfaction both during the progress of their work and at end.

I have pleasure in recommending Twintech to anyone who is looking to get their furnace or Ac replaced

Nathan S.

by Private User on Twintech Heating and Cooling

Our air conditioner died On a Saturday and within hours Dave came out to take a look and discuss replacement/repair options.
The new air conditioner was installed on the Wednesday. The new unit was installed quickly. The installers were friendly and cleaned up afterwards.
We noticed a slight leak around the furnace that night and they came out the next day and fixed the issue. It has been working great and is quieter than our previous unit.
Very satisfied and would highly recommend TwinTech.

by Nancy in Toronto on Twintech Heating and Cooling

I contacted TwinTech to replace my 20-year old A/C. Dave, their service rep, promptly replied and was at my home within 2 hours. He was friendly and knowledgeable and didn't try to upgrade or oversell their A/C units but suggested the best fit for my small 1000 feet bungalow. Although this was during a heatwave and very busy, they were able to fit me in 2 days later. The TwinTech crew installed a 1.5 ton Ducane A/C unit that is now running smoothly while maintaining a constant cooling temperature. The crew were very courteous, professional and efficient and I will definitely recommend TwinTech to family and friends. I much appreciated your great service.
Nancy M., Oshawa