Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by dianeramsden on Twintech Heating and Cooling

Our air conditioner failed. Made a call and within 15 min a technician was at our door.
The issue was fixed and many suggestions were provided.
Thanks to Mitch. Great service !

by Kazuko on Twintech Heating and Cooling

Our furnace was rattling, as soon as we put our air conditioner on this past week. We had researched looking for a company that was Registered with Better Business Bureau, and this company TwinTech, had A+ Rating. Scott, was immediately helpful via text/phone and sent his technician as soon as he was able...Mitchell/technician provided great professional service. Thank you TwinTech.
Sean and Debbie

by ANOOP on Twintech Heating and Cooling

I contacted various companies when looking to install a new furnace and I found Twintech to be transparent with their communication and approach. They had options to suit my various requirements and the price vs quality was very good. The after installation communication was also very good and they answered all queries I had.

by Private User on Twintech Heating and Cooling

My furnace broke down last month. The team was quick to respond, courteous, professional and mindful of COVID-19 concerns. I highly recommend them if you are considering replacing or servicing your HVAC equipment.

by Private User on Twintech Heating and Cooling

I was very happy with the installation and price. I would definitely recommend. Thank you Twintech.

by Dorothy on Twintech Heating and Cooling

Had furnace and air conditioning unit put in. They did an excellent job great price and everything clean as can be, I was very pleased

by Barry on Twintech Heating and Cooling

All winter I have had an issue with very little heat reaching the 2nd floor of our home. After this past winter ended I decided to look into this. I found Twintech Heating and Cooling on line and started the process. After explaining my problem I had a call form Twintech and the tech came out and walked through things with me. The problem was the heating vent pipe had been dropped down in size by someone years ago causing little heat reaching the 2nd floor. Further into checking out the older furnace and AC they found a few things not properly installed by the last install of the old furnace and also that the AC was on it's last legs. I asked for a quote and waited a few days and we decided to go ahead with Twintech. They called a few days before to set up an installation time and date. The day of the install the guys were a half hour early which was a plus. The day of the install was great, the guys worked away removing the old furnace and AC.After which they installed the new furnace and AC. After they cleaned up the basement with all their tools and scrap metal etc. they came back inside to walk thru what they did. They also tested both the furnace and cooling systems to make sure everything worked and I the customer was happy. I now have heat on the 2nd floor for next winter. The guys from Twin tech were very professional. Their work habits and knowledge of the job was excellent. Their workmanship was just excellent, it was just up there with my standards as a homeowner. I am very pleased to have chosen Twintech for my new furnace and AC.. If I had to rate this experience with Twintech this company is a 10 in my books.Product,workmanship and customer care says it all.

by Craig in Whitby on Twintech Heating and Cooling

I called Twintech during the Covid 19 crisis because our furnace was broken and it was still very cold during the nights. Dave answered all of my questions by phone but wanted to come have a look but only if our family felt comfortable having someone visit during the uncertainty surrounding the pandemic and was able to attend that very same affternoon.

He was very courteous and informative but most importantly he respected his and our safety by wearing medical gloves in our home and maintaining proper physical distancing. He reviewed the various options of the products that suited our needs going over not only price but quality of workmanship, warrantees and where the product was manufactured which were all important factors in making such a large purchase. You could tell that Dave had been in this industry for a very long time.

The installation was done by a fine young gentleman the very next day and we now have a toasty warm home to ride out this crisis in while humming along at 96% efficiency!

I would recommend this very professional, small family business for anyone in need of HVAC equipment or maintenance.

by Lucy in Markham on Twintech Heating and Cooling

My special thanks to Twintech teams! They had replaced my furnace and A/C, and installed a new humidifier for me 2 weeks ago. Dave, the sales manager, not only provided me with an honest quote on the best HVAC products with best quality and warranties, he also arranged portable heaters for me and sent supporting docs to energy company for energy audit. Above and beyond service!

Greg, Grant, Mitch had worked tirelessly and professionally to perform the HVAC installation. They worked with professional tools, and performed proper measurement readings after installation. They are very patient with all my questions, and very pleasant to communicate.

Great work guys! This company sure knows their products and they stand behind their services. My home comfort level has improved! I am glad that I can support an ethical and honest local family business.

by ddame on Twintech Heating and Cooling

Professional, flexible on price and delivered on time...well done. All you can ask for when getting a new furnace.