$49 / month O.A.C Including Install
$49 / month O.A.C Including Install

24 / 7 Emergency Service Available. Call Us Now: 1.844.894.6832

Durham Region Air Conditioning Repair, Service and Installation

CLICK HERE FOR A FREE QUOTATION

If you're looking for help fixing your daikin air conditioner, look no further! Our comprehensive daikin air conditioner repair guide will explain common issues, provide troubleshooting tips, and show you how to read your model's error codes.


CODE: A0.
RESULT: External protection device activated. External protection device connected to the terminal strip T1-T2 of indoor unit is activated.

CODE: A1.
RESULT: Malfunction of indoor unit PCB Malfunction due to noise Defect of indoor unit PCB.

CODE: A3.
RESULT: Malfunction of drain level control system Drain piping clogging, improper drain piping work Defect of drain pump. Defect of float switch.

CODE: A4.
RESULT: Malfunction of freezing protection Shortage of water volume Low water temperature setting Defect of 26WL. Defect of water temperature thermistor.

CODE: A5.
RESULT: High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor.

CODE: A6.
RESULT: Fan motor locked, overload, overcurrent Defect of connector contact Defect of indoor unit PCB Defect of fan motor.

CODE: A7.
RESULT: Malfunction of swing flap motor Failure of swing flap motorm, Defect of indoor unit PCB Jammed swing mechanism/blade.

CODE: A8.
RESULT: Malfunction of power supply Overcurrent of AC input, Defect of power supply voltage.

CODE: A9.
RESULT: Malfunction of electronic expansion valve drive Defect of electronic expansion valve coil, Defect of indoor unit PCB, Defect of connector contact.

CODE: AA.
RESULT: Heater overheat 26WH is activated.

CODE: AF.
RESULT: Malfunction of a humidifier system Water leakage of humidifier (option), Failure of swing float switch. Improper drain piping incline.

CODE: AH.
RESULT: Malfunction of dust collector of air cleaner Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB.

CODE: AJ.
RESULT: Malfunction of capacity setting (Indoor unit PCB) Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB.

CODE: C1.
RESULT: Failure of transmission (between indoor unit PCB and fan PCB) Defect of transmission of fan motor control driver.

CODE: C4.
RESULT: Malfunction of liquid pipe thermistor for heat exchanger Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger.

CODE: C5.
RESULT: Malfunction of gas pipe thermistor for heat exchanger Defect of connector contact. Defect of gas pipe thermistor for heat exchanger.

CODE: C6.
RESULT: Malfunction of fan motor control driver Defect of fan motor sensor system Defect of fan motor control driver.

CODE: C7.
RESULT: Front panel driving motor fault Defect of front panel driving motor Defect of limit switch.

CODE: C9.
RESULT: Malfunction of suction air thermistor Defect of connector contact Defect of thermistor for suction air.

CODE: CA.
RESULT: Malfunction of discharge air thermistor Defect of connector contact. Defect of thermistor for discharge air.

CODE: CC.
RESULT: Malfunction of humidity sensor system Defect of connector contact Defect of humidity sensor.

CODE: CJ.
RESULT: Malfunction of thermostat sensor in remote controller Defect of remote controller thermistor Malfunction due to noise Defect of remote controller PCB. Outdoor Unit.

CODE: E0.
RESULT: Protection devices actuated (unified) Protection device connected to outdoor PCB actuated Defect of protection device connector contact.

CODE: E1.
RESULT: Defect of outdoor unit PCB Malfunction due to noise Defect of outdoor unit PCB?.

CODE: E3.
RESULT: Actuation of high pressure switch (HPS) Dirty outdoor unit heat exchanger and suction filter Defect of HPS Clogged refrigerant piping Defect of connector contact.

CODE: E3.
RESULT: System No.1. Actuation of high pressure switch (HPS). Dirty outdoor unit heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact Outdoor Unit.

CODE: E4.
RESULT: Actuation of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connecting connector Defect of outdoor unit PCB.

CODE: E5.
RESULT: Overheat of inverter compressor motor Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: E5.
RESULT: Inverter compressor motor lock Inverter compressor lock Incorrect wiring.

CODE: E6.
RESULT: STD compressor motor overcurrent/lock Closed stop valve STD compressor lock.

CODE: E6.
RESULT: System No.1 Compressor overcurrent Defect of EXP. valve Defect of compressor Shortage of refrigerant amount.

CODE: E7.
RESULT: Malfunction of outdoor unit fan motor. Faulty contact of fan motor connector. Defect of fan motor, Defect of fan motor driver.

CODE: E8.
RESULT: Overcurrent of inverter compressor, Defect of compressor, Defect of outdoor unit PCB Defect of inverter main circuit capacitor Defect of power transistor.

CODE: E9.
RESULT: Malfunction of electronic expansion valve coil Defect of electronic expansion valve Defect of connector contact Defect of outdoor unit PCB.

CODE: EA.
RESULT: Malfunction of four way valve Defect of four way valve Defect of outdoor unit PCB Shortage of gas Defect of thermistor.

CODE: EC.
RESULT: Malfunction of entering water temperature Malfunction of cooling water temperature. Defect of thermistor. Defect of outdoor unit PCB.

CODE: EF.
RESULT: Malfunction of thermal storage unit Defect of electronic expansion valve of thermal storage unit Defect of thermal storage PCB.

CODE: F3.
RESULT: Malfunction of discharge pipe temperature Shortage of gas. Defect of connector contact. Clogged refrigerant piping Defect fo discharge pipe thermistor.

CODE: F6.
RESULT: Abnormal high pressure in cooling Defect of outdoor unit fan motor Defect of electronic expansion valve Defect of heat exchanger thermistor, Defect of outdoor unit PCB.

CODE: F6.
RESULT: Refrigerant overcharged Refrigerant overcharged Disconnection of heat exchanger thermistor Disconnection of outdoor air thermistor Disconnection of liquid pipe thermistor.

CODE: H0.
RESULT: Malfunction of sensor system of compressor, Harness is disconnected, or defective connection Defect of PCB.

CODE: H1.
RESULT: Malfunction of humidifier unit damper, Defect of limit switch Defect of damper.

CODE: H3.
RESULT: Malfunction of high pressure switch (HPS), Defect of high pressure switch. Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H4.
RESULT: Malfunction of low pressure switch (LPS), Defect of low pressure switch Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H5.
RESULT: Malfunction of compressor motor overload thermistor Defect of connector contact. Defect of compressor motor overload thermistor.

CODE: H6.
RESULT: Malfunction of position detection sensor, Faulty contact of compress or cable. Defect of compressor, Defect of outdoor unit PCB.

CODE: H7.
RESULT: Malfunction of outdoor fan motor signal Faulty contact of fan wiring Defect of fan motor driver Defect of fan motor.

CODE: H8.
RESULT: Malfunction of compressor input (CT) system Defect of power transistor. Defect of reactor. Faulty wiring of inverter system Defect of outdoor unit PCB.

CODE: H9.
RESULT: Malfunction of outdoor air thermistor. Defect of connector contact Defect of thermistor for outdoor air.

CODE: HC.
RESULT: Malfunction of (hot) water temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of thermistor for water temperature.

CODE: HF.
RESULT: Alarm in thermal storage unit with ice Thermal storage group defective wiring Defect of setting Excess of thermal storage tank numbers.

CODE: HJ.
RESULT: Malfunction of thermal storage tank water level Low water level Defect of switch setting Water level detecting sensor failure Defect of connector contact Outdoor Unit.

CODE: J1.
RESULT: Malfunction of pressure sensor Defect of pressure sensor connector contact. Defect of pressure sensor. Defect of outdoor unit PCB.

CODE: J2.
RESULT: Malfunction of current sensor of compressor Defect of current sensor Defect of outdoor unit PCB Defect of compressor.
CODE: J3.
RESULT: Malfunction of discharge pipe thermistor. Defect of connector contact Defect of outdoor unit PCB Defect of discharge pipe thermistor.

CODE: J4.
RESULT: Malfunction of low pressure equivalent saturated temperature sensor system Defect of connector contact Defect of thermistor Defect of outdoor unit PCB (Multi-split, Super-multi ).

CODE: J5.
RESULT: Malfunction of suction pipe thermistor Defect of connector contact Defect of outdoor unit PCB Defect of suction pipe thermistor.

CODE: J6.
RESULT: Malfunction of heat exchanger thermistor Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: J7.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J8.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J9.
RESULT: Malfunction of gas pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of gas pipe thermistor.

CODE: JA.
RESULT: Malfunction of high pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of high pressure sensor.

CODE: JC.
RESULT: Malfunction of low pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of low pressure sensor.

CODE: JE.
RESULT: Malfunction of sub-tank thermistor Defect of connector contact Defect of outdoor unit PCB Defect of sub-tank thermistor.

CODE: JF.
RESULT: Malfunction of heating thermistor for heat exchanger Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: JH.
RESULT: Malfunction of oil temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of oil temperature thermistor.

CODE: L0.
RESULT: Malfunction of inverter system Shortage of power supply capacity Defect of inverter PCB Defect of power transistor.

CODE: L1.
RESULT: Malfunction of inverter PCB Defect of compressor wiring Blown fuse Defect of outdoor unit fan motor Defect of inverter PCB.

CODE: L3.
RESULT: Electrical box temperature rise Fin temperature rise due to short-circuit Defect of power transistor Defect of outdoor unit fan Defect of outdoor unit PCB.

CODE: L4.
RESULT: Malfunction of inverter radiating fin temperature rise Fin temperature rise due to short-circuit Defect of fin thermistor.

CODE: L5.
RESULT: Inverter instantaneous overcurrent (DC) Closed stop valve Defect of compressor.

CODE: L6.
RESULT: Inverter instantaneous overcurrent (AC) Overcharge of refrigerant amount Defect of compressor Shortage of power supply capacity Defect of inverter unit.

CODE: L8.
RESULT: Overcurrent of inverter compressor Abnormal high pressure rise due to clogged refrigerant circuit and others Defect of compressor.

CODE: L9.
RESULT: Malfunction of inverter compressor startup Faulty of pressure equalization Defect of compressor wiring Defect of compressor.

CODE: LA.
RESULT: Malfunction of power transistor Defect of power transistor Defect of inverter PCB Defect of compressor.

CODE: LC.
RESULT: Malfunction of transmission between outdoor unit PCB and micro-computer Defect of grounding connection Defect of outdoor unit PCB Malfunction due to noise.

CODE: LC.
RESULT: Malfunction of transmission between control and inverter PCB Defect of connector contact Defect of inverter PCB Malfunction due to noise Defect of outdoor unit control PCB.

CODE: P0.
RESULT: Shortage of refrigerant amount (thermal storage unit) Shortage of refrigerant Clogged refrigerant piping Outdoor Unit.

CODE: P1.
RESULT: Power voltage imbalance, open phase Open phase Voltage imbalance between phases Faulty main circuit capacitor. Defect of wiring contact.

CODE: P2.
RESULT: Automatic refrigerant charge operation stop Closed stop valve. Closed valve of refrigerant tank.

CODE: P3.
RESULT: Malfunction of thermistor in electrical box Electrical box temperature rise (ambient temperature rise) Defect of fin thermistor, Defect of outdoor unit PCB.

CODE: P4.
RESULT: Malfunction of radiating fin temperature sensor Defect of radiating fin thermistor Defect of wiring contact Defect of outdoor unit PCB.

CODE: P8.
RESULT: Heat exchanger freezing protection during automatic refrigerant charging (Close the refrigerant cylinder. Start again from step 1.).

CODE: P9.
RESULT: Malfunction of fan motor (humidifier unit) Defect of fan motor Broken relay harness Defect of outdoor unit PCB Defect of connector contact.

CODE: P9.
RESULT: Automatic refrigerant charge operation completed.

CODE: PA.
RESULT: Broken wire of heater (humidifier unit) Defect of heater unit Defect of outdoor unit PCB Defect of thermistor.

CODE: PA.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of master unit is empty.

CODE: PC.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 2 is empty.

CODE: PE.
RESULT: Automatic refrigerant charge operation nearly completed.

CODE: PH.
RESULT: Malfunction of temperature (humidifier unit) Defect of heater unit Defect of thermistor Defect of connector contact Defect of outdoor unit PCB.

CODE: PH.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 1 is empty.

CODE: PJ.
RESULT: Malfunction of capacity setting (Outdoor unit PCB) Capacity setting adaptor is not installed Improper capacity setting adaptor Defect of outdoor unit PCB.

CODE: PJ.
RESULT: Improper combination between inverter and fan driver Mistake of inverter PCB Mistake of control PCB Mistake of inverter fan PCB System.

CODE: U0.
RESULT: Shortage of refrigerant Shortage of refrigerant Closed stop valve Clogged refrigerant piping.

CODE: U1.
RESULT: Reverse phase, open phase Reverse phase, open phase of power wiring Wrong wiring. Defect of outdoor unit PCB.

CODE: U2.
RESULT: Defect of power supply voltage or instantaneous power failure. Defect of power supply voltage Instantaneous power failure Defect of wiring contact.

CODE: U3.
RESULT: Check operation not executed. Check operation not executed.

CODE: U3.
RESULT: Malfunction of transmission Malfunction due to noise Defect of outdoor unit PCB Wrong wiring.

CODE: U4.
RESULT: Malfunction of transmission between indoor and outdoor unit Defect or indoor-outdoor transmission wiring Malfunction due to noise Defect of indoor unit PCB and outdoor unit PCB.

CODE: U5.
RESULT: Malfunction of transmission between indoor unit and remote controller Defect of remote controller wiring Defect of indoor unit PCB Malfunction due to noise Defect of remote controller main/sub setting.

CODE: U6.
RESULT: Malfunction of transmission between indoor units Faulty wiring Defect of indoor unit PCB Malfunction due to noise.

CODE: U7.
RESULT: Malfunction of transmission between main body micro-computer. INV micro-computer Harness disconnection/broken wire between PCB Defect of outdoor unit PCB.

CODE: U7.
RESULT: Malfunction of transmission between outdoor units Defect of wiring between outdoor units Defect of outdoor unit switch setting Defect of wiring between outdoor thermal storage units.

CODE: U8.
RESULT: Malfunction of transmission between remote controllers Defect of remote controller main/sub setting Defect of remote controller wiring. Defect of remote controller PCB Others.

CODE: 77.
RESULT: System No. 1 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 78.
RESULT: System No. 2 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 7A.
RESULT: System No. 2 Malfunction of current sensor of compressor Defect of current sensor. Defect of compressor Defect of outdoor unit PCB.

CODE: 7C.
RESULT: System No. 2 Malfunction of pump inter lock Cooling water pump interlock actuated.

CODE: 80.
RESULT: Malfunction of entering water temperature thermistor. Defect of connector contact. Defect of entering water temperature thermistor.

CODE: 81.
RESULT: Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 82.
RESULT: System No. 1 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 83.
RESULT: System No. 2 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 84.
RESULT: System No. 1 Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 85.
RESULT: System No. 2. Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 86.
RESULT: System No. 2. Malfunction of discharge pipe thermistor. Defect of connecting connector Defect of discharge pipe thermistor.

CODE: 88.
RESULT: System No. 2. Malfunction of discharge pipe temperature. Shortage of gas. Defect of discharge pipe thermistor Defect of connector contact. Clogged refrigerant piping.

CODE: 89.
RESULT: Malfunction of brazed-plate heat exchanger freezing Dirty heat exchanger. Shortage of refrigerant amount Defect of thermistor.

CODE: 8A.
RESULT: System No. 2 Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 8E.
RESULT: System No. 1 Malfunction of suction pipe thermistor 1 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8F.
RESULT: System No. 1 Malfunction of suction pipe thermistor 2 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8H.
RESULT: Abnormal high hot water temperature Three-way valve malfunction. Defect of thermistor Defect of water temperature setting.

CODE: 90.
RESULT: Abnormal chilled water quantity, abnormal AXP. Shortage of water volume Disconnection of AXP.

CODE: 91.
RESULT: System No. 2 Malfunction of electronic expansion valve Defect of connector contact Defect of electronic expansion valve coil.

CODE: 92.
RESULT: System No. 2 Malfunction of suction pipe thermistor Defect of connector contact Defect of suction pipe thermistor.

CODE: 94.
RESULT: Malfunction of transmission (between heat reclaim ventilation unit and fan unit) Defect of fan unit PCB Defect of connecting wire between (1) and (2).

CODE: 95.
RESULT: System No. 1 Malfunction of inverter system Defect of fan inverter unit.

CODE: 96.
RESULT: System No. 2 Malfunction of inverter system Defect of fan inverter unit.

CODE: 97.
RESULT: Malfunction of thermal storage unit Defect of thermal storage unit.

CODE: 98.
RESULT: Malfunction of thermal storage brine pump Actuation of thermal storage brine pump overcurrent (OC).

CODE: 99.
RESULT: Malfunction of thermal storage brine tank Low water level of thermal storage brine tank System.

CODE: U9.
RESULT: Malfunction of transmission (other system) Defect of communication between other indoor unit and outdoor unit Other indoor unit electronic expansion valve failure.

CODE: UA.
RESULT: Defect of indoor/outdoor power supply Wrong model connections Wrong PCB connected Improper power supply Defect of PCB.

CODE: UA.
RESULT: Malfunction of field setting Malfunction of field setting by remote controller Defect of remote controller wiring Defective connection of optional device Defect of indoor unit PCB.

CODE: UA.
RESULT: Improper combination of indoor and outdoor units Excess of connected indoor units Malfunction of field setting Uncanceled service mode. Defect of outdoor unit PCB.

CODE: UA.
RESULT: Remote temperature setting wire disconnection Remote temperature setting wire disconnection Defect of connector contact.

CODE: UC.
RESULT: Malfunction of setting of centralized controller address. Address duplication of centralized controller.

CODE: UE.
RESULT: Malfunction of transmission between indoor unit and centralized controller Malfunction of wiring between indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB.

CODE: UF.
RESULT: Wiring and piping mismatch Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units.

CODE: UH.
RESULT: Malfunction of system Improper connection of transmission wiring between indoor- outdoor units and outdoor-outdoor units Defect of indoor and outdoor unit PCB (RA: Mismatching indoor and outdoor units, Defect of voltage, Freeze protection in other indoor unit (k).

CODE: UJ.
RESULT: Malfunction of transmission (Accessory devices) Defect of accessory devices Faulty wiring.

CODE: M1.
RESULT: Malfunction of centralized remote controller PCB. Defect of centralized remote controller PCB.

CODE: M8.
RESULT: Malfunction of transmission between optional controllers for centralized control Other centralized control power disconnection Centralized control reset switch ON Defect of transmission wiring. Central remote controller address change.

CODE: MA.
RESULT: Improper combination of optional controllers for centralized control Improper combination of optional controllers for centralized control More than one master controller is connected Faulty setting of centralized control Defect of centralized control.

CODE: MC.
RESULT: Address duplication, improper setting Address duplication of central remote controller.

CODE: 60.
RESULT: External protection device actuated Actuation of external protection device Defect of output signal wiring Defect of control PCB.

CODE: 64.
RESULT: Malfunction of indoor air thermistor Defect of connecting connector Defect of thermistor for indoor air Defect of control PCB.

CODE: 65.
RESULT: Malfunction of outdoor air thermistor Defect of connector contact Defect of control PCB Defect of outdoor air thermistor.

CODE: 6A.
RESULT: Malfunction of damper system Defect of connector contact Defect of damper motor Defect of limit switch Defect of control PCB.

CODE: 70.
RESULT: System No. 2 Compressor overload Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: 71.
RESULT: System No. 2 Compressor overcurrent Shortage of refrigerant amount Short-circuit Defect of compressor.

CODE: 72.
RESULT: System No. 2 Fan motor overcurrent Defect of fan motor connector contact Defect of fan motor Defect of PCB.

CODE: 73.
RESULT: System No. 2 Malfunction of high pressure (HPS) actuated Dirty heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact.

CODE: 74.
RESULT: System No. 2 Malfunction of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connector contact Defect of LPS.

CODE: 75.
RESULT: System No. 2 Malfunction of low pressure sensor Defect of connector contact Defect of PCB Defect of low pressure sensor.

CODE: 76.
RESULT: System No. 2 Malfunction of high pressure sensor Defect of connector contact Defect of PCB Defect of high pressure sensor.


See What Our Customers Are Saying:

by Harry in Toronto on Twintech Heating and Cooling

Ever since I turned on my furnace on Oct 2018 I hear a humming sound when the furnace fan kicks in. I called Adamson Air System who installed my furnace 7 years ago and couldn't figure it out the problem. I just wasted money to the guy who couldn't figure it out. I found Twin Tech via Amana / Goodman website. I checked the reviews from previous Twin Tech customers. I called Greg and was onsite on time this morning Sunday, Nov 25 2018. He figured it out what's wrong with the furnace and explained what the previous installer (adamson air system) did wrong when they installed it. His knowledgeable about his job. He recommend to replace the fun motor because the sound is not normal when it's running. Looking forward to see him again to replace the fan motor.

by Roger in Pickering on Twintech Heating and Cooling

Our house is over 22 years old and I had been researching furnaces and A/C brands for a while and thought it was time to take the plunge. After calling three different companies to come in and quote the job, this one won me over. From the first visit from Dave all the way to the end of the install by Greg, Grant, and Piotr, I was glad to have picked this company. Dave was very knowledgeable and really took the time to explain what kind of quality installation I was going to get as well as showing me some of their previous work and certificates.

I was also surprised at how quick the installation took and how nice everything looked afterward, I mean it's only a furnace right? They even re positioned the furnace so that I have easier access to my filter and humidistat, awesome! If you are looking for a company that cares about their customers and is proud about the quality of work they do, along with a great and competitive price, then stop right here because you found it.

by Louis in Pickering on Twintech Heating and Cooling

Once our AC Unit started to fail, I called our past Heating & Cooling provider for support. The response was we needed a new motor for our Furnace. It was time to check their Quote against the marketplace, I reached to other providers online. One of the owner of Twintech (Greg), called me and offered a preliminary Quote and recommendation online. The others needed to set an appointment and came to measure and spend 1 hour before offering a quote. Then I asked Twintech to come finalize their quote to make sure their recommendation was aligned and met our needs.

Twintech was professional throughout the process, easy to deal with (Web, Phone and in Person), price right and met their commitment. Their team expedited the process and installation, arranged for a energy assessment for available rebates and most importantly, delivered on their commitment and managed to do a few extras. They installed a New Furnace, AC unit and Nest thermostat in a day, remove all older units, left the house and outdoors clean and without any debris. Great to be able to support a Local Company, Neighbour and Professional team - Well Done Team Twintech !!!

by Elizabeth and John L from Scarborough on Twintech Heating and Cooling

In October 2018, I contacted Greg at Twintech to do a furnace cleaning. Greg discovered that my furnace, installed in 2006 by another company, had been installed incorrectly, leading to restricted air flow. The heat exchanger was also defective. As well, my furnace was too large for the size of my house.

In my opinion, the biggest concern most of us have as consumers is that we have no idea of the quality or knowledge and experience of the technicians any heating and cooling company will send into our homes. I could have avoided having my 2006 furnace installed improperly (leading to early replacement), had I known about Twintech then.

With Twintech you get it all. Because Twintech is a smaller company you can rest assured that the only technicians who will work in your home are Greg and his twin brother Grant who are co-owners and fully licensed and certified with over 30 years of experience in installing and servicing heating and cooling equipment. They are both friendly and personable and answer all your questions. Their workmanship is outstanding. We had a 2 stage, variable speed Goodman furnace installed. My wife and I noticed a difference in the heating and even temperature of our 2 storey home almost immediately. Our old furnace always heated too much on the main floor and too little upstairs. We are also impressed with how quiet the furnace is.

Twintech's office manager, David Gergley, is equally friendly and not only gave us a competitive quote to replace our furnace (we sought other quotes), but also went above and beyond my expectations when he made arrangements with an energy audit company so that we would be considered for a grant from Enbridge and IESO.

Needless to say, I give Twintech a 10 out of 10 and highly recommend them!

by James, Ajax on Twintech Heating and Cooling

Clean, Fast and Efficient Work. Between all the quotes I received Twintech was a few dollars less and offered the best warranty.

by garysumnec360, Whitby on Twintech Heating and Cooling

They did an excellent job. Everything was very well explained. At the end of the job everything was very well cleaned up.

by Glade, Pickering on Twintech Heating and Cooling

Twintech offered me a competitive price but more importantly great sales and installation service. They did everything with attention to detail and quality workmanship that is hard to find in this day and age. Dave who first game to visit me answered most of my questions and probed about my needs. For the technical/install questions he was unable to answer he quickly had Greg and Grant the owners answer for me. They did not cut corners on the installation or do anything to simply save time. They stayed into the early evening to complete the job and removed all my old components and even fixed up mistakes other workers ahd made in the past. I would highly recommend them and use them again if the need arises in the future. If you are looking for service or new equipment I would highly recommend Twintech be on your list of Heating companies to get a quote from and ask your questions to.

by Anne of Major Oaks in Pickering on Twintech Heating and Cooling

The company epitomizes high quality service: from the initial client interaction with Dave to the installation and follow up with the technical team. One of the key features I look for is the ability of a technical person to talk to and not talk down to the customer when responding to questions and I had quite a few, all of which were very professionally addressed. I was also quite impressed with the follow up service, promptness, the obvious competence of the team who left no stone un-turned to ensure I was a satisfied customer. Thank you guys.

by Aileen Johnson in Toronto on Twintech Heating and Cooling

All staff concerned were total professionals. Sales rep Dave was like having an old friend at your house. No up selling or pressure, just good honest facts and figures. The owners and assistant who installed our unit worked quietly, efficiently and left our home clean. We could not have been happier with the service and attention we were given. We are so happy a family member recommended Twintech. She said "don't call anyone else, just call them...they are amazing". And they were!!! Thank you guys for the great work!!! A. Johnson

by Lynsey from Toronto on Twintech Heating and Cooling

We are completing a large project adding an addition on to our house and couldn’t be more pleased with our decision to trust Twintech with our hvac work. They removed and replaced the furnace, installed a new A/C unit, swapped our tank water heater for a tankless unit, and completed ducting and new A/C lines through the addition. Without hesitation we would recommend Twintech to anyone.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Does a Furnace Reduce its Efficiency as it Ages?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 9, 2024

Yes, a furnace can experience a reduction in efficiency as it ages. Several factors contribute to this decline. Wear and Tear: Over time, the components of a furnace, such as the heat exchanger, blower motor, and igniter, can wear out or become

Read More

How Long Can My AC Run Before Breaking?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 28, 2024

The lifespan of an air conditioning (AC) unit and how long it can run continuously without breaking depends on several factors, including the type and quality of the unit, how well it is maintained, the conditions in which it operates, and usage patt

Read More

Common Mistakes When Getting a New Furnace

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 20, 2025

Here are some common mistakes people make when getting a new furnace, and how to avoid them: Choosing the Wrong Size A furnace that's too big will cycle on and off frequently, leading to uneven heating and higher energy bills. Too smal

Read More

Unusual Noises From Furnace

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 28, 2024

If you’re hearing unusual noises from your furnace, it could signal a problem that needs immediate attention. Here's a guide to some common noises and their potential causes: 1. Banging or Popping Cause: This often indicates delaye

Read More