McQuay was established in 1933. She specialized in the supply and service of air conditioning, ventilation and heating equipment, as well as in the production of heating equipment - heat exchangers and radiators.


McQuay Furnace error codes are seen in three colors, red, green, and amber/yellow. Each color will also flash a specific number of times to signify a specific error. Breaking down each color, and number of flashes, will help you solve the problem you are having with your York Furnace.


CODE: SLOW GREEN FLASH
RESULT: Normal operation

CODE: SLOW AMBER FLASH
RESULT: Normal operation with call for heat

CODE: RAPID RED FLASH
RESULT: Twinning error, incorrect 24V phasing.
FIX: Check twinning wiring. Flame sense current is below 1.5 microamps

CODE: RAPID AMBER FLASH
RESULT: Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

CODE: 4 AMBER FLASHES
RESULT: The control is receiving a "Y" signal from the thermostat without a "G" signal, indicating improper thermostat wiring.

CODE: 1 RED FLASH
RESULT: This indicates that flame was sensed when there was not a call for heat.
FIX: The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.

CODE: 2 RED FLASHES
RESULT: This indicates that the normally open pressure switch contacts are stuck in the closed position.
FIX: The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. This indicates the normally open pressure switch contact did not close after the inducer was energized.

CODE: 3 RED FLASHES
RESULT: This could be caused by a number of problems: faulty inducer, blocked vent pipe broken pressure switch hose or faulty pressure switch.

CODE: 4 RED FLASHES
RESULT: This indicates that the main limit switch has opened its normally closed contacts.
FIX: The control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 5 RED FLASHES
RESULT: This fault is indicated if the normally closed contacts in the rollout switch opens.
FIX: The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 6 RED FLASHES
RESULT: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat.
FIX: If the main blower is in a "Delay on" mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

CODE: 7 RED FLASHES
RESULT: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
FIX: Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

CODE: 8 RED FLASHES
RESULT: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle.
FIX: This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

CODE: 9 RED FLASHES
RESULT: Indicates reversed line voltage polarity or grounding problem.
FIX: Both heating and cooling operations will be affected. check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

CODE: 10 RED FLASHES
RESULT: Flame sensed with no call for heat.
FIX: Check gas valve and gas valve wiring This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes.

CODE: 11 RED FLASHES
RESULT: This condition is usually caused by a failed blower motor or blower wheel.
FIX: Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

CODE: 12 RED FLASHES
RESULT: This code indicates an open igniter circuit.
FIX: This could be a disconnected or loose wire or a cracked or broken igniter.

CODE: STEADY ON RED
RESULT: Control failure.
FIX: Replace control board.

CODE: 60-MINUTE AUTOMATIC RESET FROM LOCKOUT
RESULT: This control includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7, 8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.

CODE: IGNITION CONTROL FLAME SENSE LEVELS
RESULT: Normal flame sense current is approximately 3.7 microamps DC Low flame signal warning starts at 1.5 microamps. Low flame signal control lockout point is 0.1 microamps DC.


See What Our Customers Are Saying:

by Taz on Twintech Heating and Cooling

Great team of guys came to do the work. Very professional. Arrived on time worked very efficiently and were very clean. They answered any questions we had without hesitation. The air conditioner works great and is so quiet. I highly recommend them and they don't try to up-sell anything right from the start.

by Jordan on Twintech Heating and Cooling

The service was prompt, professional and very courteous. Competitive price. Would highly recommend this company.

by David on Twintech Heating and Cooling

Excellent workmanship, and quick response. Would recommend Twintech to anyone.

by Todd Whyte on Twintech Heating and Cooling

My existing 15-yr old A/C went down on me during the first major heatwave of the season. Researched my options, as well as a few different installers, and decided on Twintech.

They gave me confidence right from the beginning. Extremely knowledgeable. Their communication was excellent - always responded to questions quickly. Given we were in a heatwave, they were fully booked. However, within days they were able to fit me in due to a cancellation. Upon learning that the Amana unit I was getting installed was on backorder, TwinTech went to bat for me with the manufacturer and was able to get me the next model up within a day, for the same price - Amazing!

As far as the installation was concerned, I couldn’t be more impressed. These guys were clearly very experienced and did a fantastic job. Very clean, polite, timely & informative. They even thoroughly sealed all the exposed gaps in my ductwork. I’ve had plenty of heating and cooling work done in the past and have never used the same contractor twice because I’ve never been very impressed. However, from now on, I’ll always be contacting Twintech first!

by Jordan Arnott, Courtice on Twintech Heating and Cooling

They were very friendly and took care of everything. The install looks great (and works great), they were very knowledgeable. Installed our a/c efficiently despite the difficult install location both inside and outside and they made it work.

by Lori Ellis on Twintech Heating and Cooling

Phenomenal service, so glad I found these guys a few years back after being "hosed" badly by 3 other companies. I've recommended them to so many, and they all are so thankful.

by Jonathan Rogoza on Twintech Heating and Cooling

This company is fantastic. Dave came out and gave me a very honest and reasonable quote, unlike a quote received from another company. I had a bunch of questions that were easily answered and when I had questions regarding heating/cooling a previously unheated room above the Garage, Dave arranged for Greg to come out for an assessment of this new space and gave me his recommendation along with his professional thoughts on all of my options.

These guys have been nothing but Professional, honest and helpful along the way. I can't recall the two other guys doing the install, but they were great as well. Good workmanship, everything was cleaned up and everything functions as promised. I could go on and on about my experience, but it's all positive so what more could you want?

Give them a call, see for yourself. If I had to buy another furnace/AC or heat pump, they'd be my first call.

by Private User on Twintech Heating and Cooling

I hired twin tech to convert my townhouse heating from electric to gas and install a furnace and a/c unit. I had talked with many other vendors, and received several quotes, but chose them, and very happy I did. Here are some of the reasons why:
1. They were realistic about the timeline for the work, when they could start and how long it would take. (They said upfront, it was their busy season and would need to get back to me in 3 weeks, which they did):
2. They had a quote with options for me. They were clear about the entertainment of what they would and would not do (they’d build duct work, id need another contractor to box in ductwork). This allowed me to plan as I was my own general contractor for my renovations).
3. They spoke to me in a language I understood, neither too technical nor too simple. They answered all my questions as I had them. Everyone is so lovely to work with, the sales team and the contractors who are worked in my home.
4. It’s been 4 m since the work was complete. They still answer my emails and my furnace is working very well!

I unabashedly recommend! Price, customer care and quality workmanship were all amazing!

by Anna Chin, Ajax on Twintech Heating and Cooling

On one of the coldest days of winter, our furnace stopped working. Our regular furnace company came and told us we had a CO2 leak and shut us off. Their quote for a new furnace was way too high and they couldn't even install it on the same day. TwinTech was recommended to us by a friend. We called and spoke to Dave who was very nice and knowledgeable. Grant showed up a short time later and a new furnace was installed the same day with no troubles at all. Best of all, we received a higher-end furnace than what was offered by our previous company and at a cheaper price. I would recommend TwinTech with no hesitation at all.

by Hiba, Pickering on Twintech Heating and Cooling

I installed a new furnace and Air conditioner with them. The installation is of high quality and according to standards. The guys are professional and reasonably priced.. I highly recommend them.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

What Type of Efficiency Gain Should I Expect With a New Furnace?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 13, 2024

The efficiency gain you can expect with a new furnace depends on several factors, including the efficiency rating of your current furnace, the efficiency rating of the new furnace, and any technological advancements in heating systems since your curr

Read More

Covering AC After Summer: Should You Do It?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 25, 2017

There are times during the year when you need to do maintenance on your heating and cooling system. For your air conditioner, it will be in the spring, and for your heating unit, in the fall. Some homeowners wonder, however, if their outside air cond

Read More

Getting Heat Pump Replaced Under Warranty Need Advice

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 1, 2023

Here's a step-by-step guide to ensure a smooth process: Read the Warranty: Start by reviewing your heat pump's warranty documentation. Understand what is covered under the warranty, the duration of coverage, and any specific conditions

Read More

Why Does My Furnace Keep Turning Off?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 21, 2024

If your furnace keeps turning off unexpectedly, it's a sign of an underlying issue that needs attention. Here are some common reasons for this problem: 1. Overheating A furnace may turn off if it's overheating due to a clogged air filte

Read More