McQuay Furnace error codes are seen in three colors, red, green, and amber/yellow. Each color will also flash a specific number of times to signify a specific error. Breaking down each color, and number of flashes, will help you solve the problem you are having with your York Furnace.


CODE: SLOW GREEN FLASH
RESULT: Normal operation

CODE: SLOW AMBER FLASH
RESULT: Normal operation with call for heat

CODE: RAPID RED FLASH
RESULT: Twinning error, incorrect 24V phasing.
FIX: Check twinning wiring. Flame sense current is below 1.5 microamps

CODE: RAPID AMBER FLASH
RESULT: Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

CODE: 4 AMBER FLASHES
RESULT: The control is receiving a "Y" signal from the thermostat without a "G" signal, indicating improper thermostat wiring.

CODE: 1 RED FLASH
RESULT: This indicates that flame was sensed when there was not a call for heat.
FIX: The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.

CODE: 2 RED FLASHES
RESULT: This indicates that the normally open pressure switch contacts are stuck in the closed position.
FIX: The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. This indicates the normally open pressure switch contact did not close after the inducer was energized.

CODE: 3 RED FLASHES
RESULT: This could be caused by a number of problems: faulty inducer, blocked vent pipe broken pressure switch hose or faulty pressure switch.

CODE: 4 RED FLASHES
RESULT: This indicates that the main limit switch has opened its normally closed contacts.
FIX: The control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 5 RED FLASHES
RESULT: This fault is indicated if the normally closed contacts in the rollout switch opens.
FIX: The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 6 RED FLASHES
RESULT: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat.
FIX: If the main blower is in a "Delay on" mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

CODE: 7 RED FLASHES
RESULT: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
FIX: Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

CODE: 8 RED FLASHES
RESULT: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle.
FIX: This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

CODE: 9 RED FLASHES
RESULT: Indicates reversed line voltage polarity or grounding problem.
FIX: Both heating and cooling operations will be affected. check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

CODE: 10 RED FLASHES
RESULT: Flame sensed with no call for heat.
FIX: Check gas valve and gas valve wiring This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes.

CODE: 11 RED FLASHES
RESULT: This condition is usually caused by a failed blower motor or blower wheel.
FIX: Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

CODE: 12 RED FLASHES
RESULT: This code indicates an open igniter circuit.
FIX: This could be a disconnected or loose wire or a cracked or broken igniter.

CODE: STEADY ON RED
RESULT: Control failure.
FIX: Replace control board.

CODE: 60-MINUTE AUTOMATIC RESET FROM LOCKOUT
RESULT: This control includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7, 8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.

CODE: IGNITION CONTROL FLAME SENSE LEVELS
RESULT: Normal flame sense current is approximately 3.7 microamps DC Low flame signal warning starts at 1.5 microamps. Low flame signal control lockout point is 0.1 microamps DC.


See What Our Customers Are Saying:

by Eric Y, Greenbank on Twintech Heating and Cooling

Dave was great in helping me get the proper units for my property, as well as getting them installed. The installers arrived when they said they would, and completed the project on time, and professionally. If I needed another furnace, I would use Dave again.

by Ed B., Whitby on Twintech Heating and Cooling

I have known Greg and Grant Dainty for many years and have used their company for my house and business. I recommended them also for my parents and sister and they all have been very satisfied with the quality of work for a reasonable price. I just recently had them install a new HVAC system in an older house and was very pleased with their work. Craig in Pickering. After meeting with various heating and air conditioning contractors I was referred to Twin Tech Heating and Cooling through a family member. Greg and Grant arrived at my home and provided me with an estimate and a plan as to how they were going to remove and replace my furnace and air conditioner. On the day of install Greg and Grant arrived at my home on time and were very professional and extremely courteous as to any questions or concerns that I had. The removal and install was truly professional and the attention to detail was exactly what I was looking for. I’ve seen many installs from other contractors and I couldn’t be any happier to have had such a clean looking install. The sheet metal work, ducting and venting all look fantastic. Upon completion Greg and Grant left me feeling extremely happy and very fortunate of a job well done. Thanks again Twin Tech!!

by Floreene in Whitby on Twintech Heating and Cooling

My old furnace had finally broken down for the last time when contacted twintech to have a new furnace installed…They were prompt, knowledgeable and very reasonably priced. They did such a great job i tell all my friends and family about this company.

by Damien McIsaac. Ajax on Twintech Heating and Cooling

To whom it may concern, I recently had TwinTech (Greg and Grant Dainty) replace my furnace and service both my gas fireplaces and air conditioning unit. They were professional, courteous and very fair in their pricing. I would gladly recommend TwinTech to anyone needing work done. I can be contacted at 905-626-XXXX.

by Blair N. - Toronto on Twintech Heating and Cooling

My Fiancé and I have relied on Twintech Heating and Cooling now for the better part of the last 10 years. In that time, Greg has installed a furnace, an air conditioner, and a heat-pump at our residence in Toronto. In each instance Greg and his team were a pleasure to deal with. They were courteous and professional throughout the whole process and the quality of their work is first rate. Our experiences have always been extremely positive and we have referred his services numerous times to our friends and family. Without hesitation, I would recommend Greg and TwinTech Heating and Cooling to anyone looking to service or replace their existing heat/AC equipment

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Is My Furnace Heating Unevenly?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 4, 2025

If your furnace is heating your home unevenly, it could indicate a problem with the system or other factors affecting heat distribution. Here are some common causes and potential solutions: 1. Clogged or Dirty Air Filters Cause: A dirty filt

Read More

Is My AC Working Smoothly?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 26, 2024

To determine if your AC is working smoothly, you can consider a few indicators: Air Temperature: Check if the air blowing out of the vents is as cold as expected. It should be noticeably cooler than the room temperature. Airflow: Ens

Read More

Why Am I Not Getting Heat From My Heat Pump?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 2, 2023

If you're not getting heat from your heat pump, there could be several reasons for the issue. Heat pumps work by transferring heat from the outdoor air to your home during the heating season. Here are some common reasons why a heat pump might not

Read More

Why Choose a Panasonic Heat Pump Over Other Brands?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 26, 2024

Choosing a Panasonic heat pump over other brands depends on various factors such as performance, features, reliability, energy efficiency, and overall value. Here are some reasons why one might consider a Panasonic heat pump: Inverter Technolog

Read More