$49 / month O.A.C Including Install
$49 / month O.A.C Including Install

24 / 7 Emergency Service Available. Call Us Now: 1.844.894.6832

Durham Region Air Conditioning Repair, Service and Installation

CLICK HERE FOR A FREE QUOTATION

The Payne gas furnace has built in diagnostics and is designed to assist with the identification and correction of faults. The furnace utilizes an LED, to describe its condition.This can be viewed through a port on the blower access panel. You can take corrective action in response to any faults indicated by the LED.


The number of short flashes of the LED represents the first digit of the two digit fault code. The number of long flashes of the LED represents the second digit of the fault code.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 11.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY- Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 12.
RESULT: BLOWER CALIBRATION LOCKOUT- Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 13.
RESULT: LIMIT SWITCH LOCKOUT- Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 14.
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours. Refer to #34.

CODE: 21.
RESULT: INVALID MODEL SELECTION- Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 22.
RESULT: SETUP ERROR- Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 23.
RESULT: INVALID BLOWER AIRFLOW SELECTION- Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 24.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind.

CODE: 31.
RESULT: Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch - Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 33.
RESULT: LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 34.
RESULT: IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 41.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE- Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 42.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE- Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 43.
RESULT: PRESSURE SWITCH CALIBRATION FAULT- Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 44.
RESULT: BLOWER CALIBRATION FAULT- Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 45.
RESULT: CONTROL CIRCUITRY LOCKOUT -Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Jacqueline Graham on Twintech Heating and Cooling

Twintech Heating & Cooling installed my furnace in 2022 and in fall of 2023 installed my Panasonic Heat Pump. Greg and Mitch did a great job. Helped me through the rebate process. Super happy with the Heat Pump. Only used my furnace 5 times this winter. Energy bills lower, carbon emissions lower.Thank you Twintech. I recommend highly!

by Bill Grainger on Twintech Heating and Cooling

Just had a new furnace installed by Twintech. I can’t express how great these guys are at what they do. From the sales to installation they were professional all the way. Very reasonable pricing and courteous during the installation and willing to answer any questions I had. Highly recommended !!!

by Colin Vernon on Twintech Heating and Cooling

They've cleaned my furnace a couple of times and mentioned that the hot water tank standards were going to change soon so I decided to change mine out.

There were a few challenges during the process but the installers handled the problems without missing a stride! I now have really hot water again!

by Heidi B on Twintech Heating and Cooling

Highly recommend Twintech Heating company, we got honest and detailed information on what was needed to replace and install a new gas furnace. Bob and Greg made us feel comfortable withe process through their thorough explanation and knowledge of the right furnace for our needs. The professionalism and courteous friendly attitude towards the customer is what we liked the most as they treated us like family. So happy with our decision and new furnace we will be looking into get our rental water heater replaced and installed by Twintech team. We feel better having their knowledge on our side and will only trust them with any further maintenance of furnace.

by Kirushanth Rasiah on Twintech Heating and Cooling

Customer service and knowledge is priority in this industry, and Twintech has it. I've dealt with their team for maintenance and a furnace replacement. They're accommodating and make great recommendations, and came through at a great price over the big guys in the industry. They'll be my next call when I need service or maintenance.

by Leonard Glass on Twintech Heating and Cooling

I decided that the noises and age of the existing furnace which was old and not very efficient to replace it. Gave Greg a call and Grant and Greg got to work on it. Because of supply issues with the current heating type that would be an easier install Greg convinced me to change the location of the system and it would provide me better service for heat and efficiency. I had skeptical but went ahead anyway putting trust in Greg And Grant. Greg, Grant and Mitch came through and in 2 days had completely relocated my heating and A/C system. I can honestly say Greg was right my old house has been warmer and more evenly heated as it ever was. For anyone reading this rather long winded review can take my word for it, Twin Tech can take care of your needs.

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

by Cibele Ceroni on Twintech Heating and Cooling

Great Team! Furnace broke in the weekend, Bob visited same day and Greg installed new one on Monday. Team was professional, respectful and knowledgeable. Installation went very well, Greg found solutions to challenges, like hiding new conduits in the ceiling. Looks nice and new furnace is working great. Five Stars.

by Jackie Graham on Twintech Heating and Cooling

I used Twintech to install a new furnace for my home. Bob was terrific in explaining the sizing options and why the 2 stage furnace was the best option for me. Greg did a great job installing, clean and on time. Finished work looks great but the best part is how it works. The 2 stage heating is so much more comfortable. I run the fan continuously to keep the indoor air clean. Great investment! Would highly recommendTwintech!

by Anthony Silva on Twintech Heating and Cooling

I’m going to start this by saying I’m a very particular customer. My background is in mathematics and mechanical engineering so I have an eye for detail and a respect for technical knowledge.
Greg had already done an AC inspection and replaced a water heater tank and there was no question in my mind who to deal with replacing my rickety old furnace after it got pooched.
Bob dropped in ahead of time and clearly (and knowledgeably) outlined all technical, price and operational options.
Greg showed up on time, on the agreed date and did a fantastic job. (The OLD furnace was a house of horrors and was installed in a keystone cops sort of way- careless.)
The work Greg did was HIGHLY PROFESSIONAL and FAR MORE FUNCTIONAL than what I had.
I’m also a musician with many instruments so maintaining predictable humidity/temperature is extremely important to me. Greg recognized this as did Bob. You NEVER feel like you’re being brushed off.
In summary, if you’re looking for PROFESSIONAL, QUALITY results by an EXPERIENCED, THOUGHTFUL team
(that also happen to be FRIENDLY and ATTENTIVE ) then you’ve come to the right page!!

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Panasonic Heat Pump Specialists in Ajax

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 16, 2025

As more homeowners across the Durham Region and Toronto switch to high-efficiency heat pumps, Panasonic has emerged as a trusted leader in cold-climate performance, advanced technology, and long-term reliability. But choosing the right brand is on

Read More

Simple Furnace Maintenance Even You Can Do

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 6, 2025

Here's a simple guide on furnace maintenance that anyone can do: Simple Furnace Maintenance Even You Can Do A well-maintained furnace keeps your home warm and energy-efficient while preventing costly repairs. Here are a few easy maintenance

Read More

Can my AC Accommodate Home?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 22, 2024

Determining whether your air conditioning (AC) system can adequately accommodate your home size depends on several factors: Size of the AC unit: AC units are rated based on their cooling capacity, typically measured in British Thermal Units

Read More

What Kind of Furnace Suits My Home?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 9, 2025

Choosing the right furnace for your home depends on several factors, including climate, home size, energy efficiency, and budget. Here’s a guide to help you decide: 1. Fuel Type Gas Furnace – Most common and efficient for colder

Read More