The Payne gas furnace has built in diagnostics and is designed to assist with the identification and correction of faults. The furnace utilizes an LED, to describe its condition.This can be viewed through a port on the blower access panel. You can take corrective action in response to any faults indicated by the LED.


The number of short flashes of the LED represents the first digit of the two digit fault code. The number of long flashes of the LED represents the second digit of the fault code.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 11.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY- Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 12.
RESULT: BLOWER CALIBRATION LOCKOUT- Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 13.
RESULT: LIMIT SWITCH LOCKOUT- Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 14.
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours. Refer to #34.

CODE: 21.
RESULT: INVALID MODEL SELECTION- Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 22.
RESULT: SETUP ERROR- Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 23.
RESULT: INVALID BLOWER AIRFLOW SELECTION- Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 24.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind.

CODE: 31.
RESULT: Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch - Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 33.
RESULT: LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 34.
RESULT: IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 41.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE- Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 42.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE- Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 43.
RESULT: PRESSURE SWITCH CALIBRATION FAULT- Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 44.
RESULT: BLOWER CALIBRATION FAULT- Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 45.
RESULT: CONTROL CIRCUITRY LOCKOUT -Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by silvercola from Toronto on Twintech Heating and Cooling

I received three quotes before deciding to choose Twintech. Dave's prices was much more reasonable than the competitors. I most appreciated their honest recommendations. Others tried to oversell their products and services. Thank you Dave!

by Shane from Whitby on Twintech Heating and Cooling

They had the best price and did a great job on the installation. Recommend them to anyone.

by gabnai7 on Twintech Heating and Cooling

It was a amazing and professional high quality job
Friendly and very helpful representatives
Thank you for understanding my concern
And explain very well
Overall we pleased with your service
Tanks

by Linda, Toronto on Twintech Heating and Cooling

My 19 year old furnace stopped working when the cold weather hit in November, and I was left without heat. I interviewed several companies and found TWINTECH HEATING and COOLING to be very knowledgeable, quick to respond to my inquiries and very competitively priced.
Dave provided all of the information and pricing ahead of time and set up the appointment for the installation. Greg and Mitch arrived on time to do the installation and worked quickly and efficiently to complete the job.
After the completion of the installation, Dave followed up to ensure that everything was working well and that I didn't have any concerns.
Overall, this was a low-stress and flawless experience from start to finish. I would highly recommend TWINTECH HEATING and COOLING to anyone that requires a new furnace.

by Sean, Whitby on Twintech Heating and Cooling

Our 20 year old furnace broke down during the first cold weekend this past November and our usual HVAC company never returned our phone call. Their loss, missing out on a sale since we didn't want to spend much fixing an old furnace and our 40 year old air conditioner was also long overdue for replacement. We proceeded in obtaining three different quotes for furnace and air conditioner replacement, and proceeded with the one we received from Twintech.


Dave was friendly, knowledgable and accommodating to our schedule and provided with us with a price that fell in the middle of the three quotes that we had. We felt that the Amana furnace and air conditioner he quoted us on were the best products and value offered to us and felt most comfortable with the professionalism and reputation of Twintech.


Greg, Grant and Mitch were at our house for installation the day after we decided to proceed. The guys were friendly and informative, the job was completed efficiently and workmanship appears excellent. Our house is certainly much more comfortable with the new two-stage variable speed Amana furnace compared to the old clunker! And, we're looking forward to enjoying the new air conditioner once summer rolls around again. Thanks Twintech!

by Bill, Oshawa on Twintech Heating and Cooling

We are very happy with our new furnace. The service was excellent the guys worked 6 hours straight through and there was no mess at all they took the old furnace box’s etc with them they then explained everything to us they were very helpful and pleasant , when we need a new air conditioner we know who to call!

by Ken, Bomanville on Twintech Heating and Cooling

The crew from sales to installation was very professional and had great attention to detail

by Tracy, Pickering on Twintech Heating and Cooling

We couldn’t have been more impressed with Twintech - from our first service call with Mitch who took the time to thoroughly diagnose the issue with our furnace, to Dave who proposed a well thought out solution to meet our needs and finally Greg and team who acted quickly to install given we had no heat.


We did our due diligence by soliciting quotes from alternate providers and were shocked and disappointed by the aggressive and manipulative tactics used.


Twintech was honest in their approach, detailed in their product knowledge, reasonably priced, diligent in their follow-up and valued our business.


Well done Twintech! You made this a positive experience for us and our new furnace works beautifully!

by Skapoor, Ajax on Twintech Heating and Cooling

We recently purchased an Amana high efficiency furnace and humdifier through Twintech. The work was completed very professionally and the quality of the workmanship was high. There was some additional sheet metal work required to complete the installation, which they were able to complete themselves. Overall I am very pleased with the work and would highly recommend Twintech for a furnace replacement.

by Steve, Oshawa on Twintech Heating and Cooling

We were very pleased with every aspect of the work that was done. They were very professional and polite. They arrived when they said they would and job was completed on estimated time


We would highly recommend them to whoever needed a recommendation


We have a very large dog and they were very understanding and respectful of him being around