The Payne gas furnace has built in diagnostics and is designed to assist with the identification and correction of faults. The furnace utilizes an LED, to describe its condition.This can be viewed through a port on the blower access panel. You can take corrective action in response to any faults indicated by the LED.


The number of short flashes of the LED represents the first digit of the two digit fault code. The number of long flashes of the LED represents the second digit of the fault code.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 11.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY- Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 12.
RESULT: BLOWER CALIBRATION LOCKOUT- Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 13.
RESULT: LIMIT SWITCH LOCKOUT- Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 14.
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours. Refer to #34.

CODE: 21.
RESULT: INVALID MODEL SELECTION- Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 22.
RESULT: SETUP ERROR- Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 23.
RESULT: INVALID BLOWER AIRFLOW SELECTION- Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 24.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind.

CODE: 31.
RESULT: Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch - Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 33.
RESULT: LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 34.
RESULT: IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 41.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE- Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 42.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE- Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 43.
RESULT: PRESSURE SWITCH CALIBRATION FAULT- Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 44.
RESULT: BLOWER CALIBRATION FAULT- Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 45.
RESULT: CONTROL CIRCUITRY LOCKOUT -Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by stan.marosek from Ajax on Twintech Heating and Cooling

Class Act ! These guys were professional right from the quote stage through to installation. They know their stuff and took their time to help educate me. They take pride in their work and it shows. I would recommend TwinTech Heating and Cooling to anyone. Keep up the great work !!!

by W. Lacombe in Pickering on Twintech Heating and Cooling

This Company is terrific. No high pressure sales and they deliver exactly what they promise to deliver. The new furnace is great and we now get consistent temperatures throughout the house. The installers were great and very efficient and completed the work on schedule on the promised day. Everyone representing this company was very aware of their presence in our house and worked diligently to keep our home as uninterrupted and as clean as was humanly possible. We did not need to go around the house to clean up after they left, what a nice surprise. We have had follow up by the company to ensure everything is to our satisfaction. How unusual in today's environment. The impression left by Twintech is that they care about us and our home. This is so refreshing in today's high tech world. Out thanks go out to Dave in sales and G, G, and P (the installers).

by jiinyiong in Ajax on Twintech Heating and Cooling

They were Timely and professional. They were very Knowledgeable with answering all of my questions.

by Connie in Pickering on Twintech Heating and Cooling

The entire process was prompt and professional, from the initial quote to the installation of the new furnace. The team installed the new furnace and removed the old one in approx. 4 hrs. The guys were very knowledgeable and gave me lots of information. I have used Twintech before for a new A/C installation and new I was in good hands.

by Valentine in Pickering on Twintech Heating and Cooling

The overall experience dealing with this company was great from start to finish when getting a new furnace and ac this year. Everything was clearly explained to us during our consultation with Dave and there were no surprises with added costs. The work was done as expected and their response time to inquiries were very timely generally within a few hours or less. They are all very professional and was a pleasure to do business with them. Highly recommend to anyone looking for honest quality professional service.

by Jiri in Toronto on Twintech Heating and Cooling

From the initial contact we had an excellent experience with this company and all its personnel. Dave Gergley was an excellent, helpful, sales person and solicitous of our needs. He recommended only what was required and did not up sell or make any suggestions for products that we did not need, such as a new A.C. He explained the rebate process and basically outlined how to get the best furnace at the lowest price. When it was time for installation, the technicians could not have been more considerate, careful, attentive to detail, obviously committed to safety and optimum functioning of the appliance they were setting up. We have been perfectly satisfied with the functioning of the furnace and all aspects of acquiring it from the initial contact with Dave through to the installation process and follow ups inquiring about our satisfaction. Also they initiated the rebate process and contacted the appropriate inspection agency to carry it out. We highly recommend this company for all heating and cooling needs and we will contact them again when it is time to replace our A.C.

by Drew in Pickering on Twintech Heating and Cooling

Twintech was excellent from the initial quote and throughout the install. They had a competitive rate for hot water tank and ended up buying the tank from them, had them remove the old tank and install the new one. The day of install they were prompt and out in about 2 hours. Professional , courteous really great guys. We took a look at my 30 year old furnace and they were able to offer some suggestions for future there too.

by Harry in Toronto on Twintech Heating and Cooling

Ever since I turned on my furnace on Oct 2018 I hear a humming sound when the furnace fan kicks in. I called Adamson Air System who installed my furnace 7 years ago and couldn't figure it out the problem. I just wasted money to the guy who couldn't figure it out. I found Twin Tech via Amana / Goodman website. I checked the reviews from previous Twin Tech customers. I called Greg and was onsite on time this morning Sunday, Nov 25 2018. He figured it out what's wrong with the furnace and explained what the previous installer (adamson air system) did wrong when they installed it. His knowledgeable about his job. He recommend to replace the fun motor because the sound is not normal when it's running. Looking forward to see him again to replace the fan motor.

by Roger in Pickering on Twintech Heating and Cooling

Our house is over 22 years old and I had been researching furnaces and A/C brands for a while and thought it was time to take the plunge. After calling three different companies to come in and quote the job, this one won me over. From the first visit from Dave all the way to the end of the install by Greg, Grant, and Piotr, I was glad to have picked this company. Dave was very knowledgeable and really took the time to explain what kind of quality installation I was going to get as well as showing me some of their previous work and certificates.

I was also surprised at how quick the installation took and how nice everything looked afterward, I mean it's only a furnace right? They even re positioned the furnace so that I have easier access to my filter and humidistat, awesome! If you are looking for a company that cares about their customers and is proud about the quality of work they do, along with a great and competitive price, then stop right here because you found it.

by Louis in Pickering on Twintech Heating and Cooling

Once our AC Unit started to fail, I called our past Heating & Cooling provider for support. The response was we needed a new motor for our Furnace. It was time to check their Quote against the marketplace, I reached to other providers online. One of the owner of Twintech (Greg), called me and offered a preliminary Quote and recommendation online. The others needed to set an appointment and came to measure and spend 1 hour before offering a quote. Then I asked Twintech to come finalize their quote to make sure their recommendation was aligned and met our needs.

Twintech was professional throughout the process, easy to deal with (Web, Phone and in Person), price right and met their commitment. Their team expedited the process and installation, arranged for a energy assessment for available rebates and most importantly, delivered on their commitment and managed to do a few extras. They installed a New Furnace, AC unit and Nest thermostat in a day, remove all older units, left the house and outdoors clean and without any debris. Great to be able to support a Local Company, Neighbour and Professional team - Well Done Team Twintech !!!