In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Jennifer in Toronto on Twintech Heating and Cooling

I had cold and hot spots all over my 70 yr old home. My furnace is quite new and Greg optimized the fan and furnace. The original installer just took it out of the box with factory settings and installed it- basically running at 50% of capacity. Greg also routed heat into my laundry room, yeah - so now I can renovate laundry room - thanks Greg. He is honest, professional and knowledgeable. I will be calling him back in the spring to optimize my AC as well.

by Happy Homeowner in Toronto on Twintech Heating and Cooling

Wonderful from beginning to end. I tend to fret and worry about home improvements but the excellent team at TwinTech put my mind as ease. They listen, they are patient and best of all ... the work they did is amazing! I chose the Goodman 80K BTU 2 stage furnace and the matching Goodman air conditioner. Greg, Grant and Poitr "Peter" arrived on time, took great care, explained everything to me and they answered all of my questions. They carefully adjusted the factory settings to optimize the furnace for my house and they also checked the duct work in the basement. Dave, the Sales Manager, came by to say "hello" and to see if I was happy. YES, I am happy with the work! The furnace is very quiet. I have it running on low just to circulate the air in the house and it's so much quieter than my old furnace. When I need new duct work for an upcoming basement renovation TwinTech will be my first choice. I highly recommend TwinTech. PS. They were even nice to my dogs.

by Les G. from Pickering on Twintech Heating and Cooling

Greg was prompt on the scheduled day of installation and the work was done well within the time estimated beforehand. Installation was neat and the equipment and scope of work was as specified in the quote. One item I must point out is that we were faced with a "No Heat" situation the day before the scheduled installation and Greg came out to address it free of charge. Not only that, but he also corrected an installation fault with our smart thermostat that was not part of the original job, again free of charge.

by one19 in North york on Twintech Heating and Cooling

Greg came by to do a routine furnace checkup. He was very knowledgeable and professional, letting me know what's being checked/adjusted and giving me tips to ensure everything runs smooth. Very honest and upfront about what's working fine vs. what may need to be fixed/replaced. He didn't attempt to up sell anything that wasn't necessary. I'm glad to have finally found someone I can trust and rely on for all my HVAC needs - furnace, A/C, and hot water tank.

by Paul M. from Toronto on Twintech Heating and Cooling

I'm very happy with the work that was done. Everyone from salesperson to the installers were friendly and professional. They were on time and cleaned up the job site after it was installed. They also answered all my follow up questions promptly. I wouldn't hesitate to work with them or recommend them again.

by Kathy D.in Ajax on Twintech Heating and Cooling

Thanks to the team at Twin Tech for a great job installing my new heat pump/ac unit. The guys were very polite and professional. When they left you would never have known they had been there except for the new Mitsubishi unit on the wall!! would highly recommend the Twin Tech team.

by varga p. in Pickering on Twintech Heating and Cooling

Installed professionally, no delays, no rework needed. Very reliable contractor and sales person. Also installed BBQ gas line and some duct work.

by Private User on Twintech Heating and Cooling

Greg and Grant are friendly, reliable, and knowledgeable HVAC professionals. The twins, Dave and the entire team provided efficient top quality service. Our family plns to use Twintech for all of our future HVAC needs.

by peter in Whitby on Twintech Heating and Cooling

Very impressed with this company. They show up on time , kept my place clean and after they left it looks like they were never there. Very professional team. Those people know what they doing . Their installation was on the highest standard. They are very knowledgeable especially they're worker Peter. I strongly recommend this company to everybody. After the installation I receive the call making sure I'm satisfied with their products and their job. Bravo!!!

by James in Bowmanville on Twintech Heating and Cooling

Greg and his brother were referred to us by a friend. They arrived when they said they would, did an exceptional job and left the place as tidy or tidier then they found it. Their professionalism is only surpassed by their kind and friendly demeanor. Even after several calls to help me with my high tech thermostat I feel that I could always call with any concern (No one responds to my texts as quickly as Greg) and have a friendly helpful response. I found out their grandfather started the company and now as a 3rd generation company, they are doing their grandfather proud. I would highly recommend Twintech over any other hvac company out there.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Why Won't My Furnace Heat Up My House?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 26, 2023

There could be several reasons why your furnace is not heating up your house properly. Here are some common troubleshooting steps to help you identify and potentially fix the issue: Thermostat Settings: Check if your thermostat is set to the

Read More

What Are the Different Kinds of Heat Pumps?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 31, 2023

Heat pumps are devices that transfer heat from one place to another, typically from a lower-temperature space to a higher-temperature one. There are several types of heat pumps, each designed for specific applications and environmental conditions. Th

Read More

Why is My Panasonic Heat Pump Leaking?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 22, 2023

A Panasonic heat pump leaking water can be attributed to several potential issues. Here are some common reasons why a heat pump might be leaking: Condensate Drain Blockage: Heat pumps produce condensate as a byproduct of the heating and cool

Read More

How do Water Heaters Work?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 9, 2019

Have you ever wondered how a water heater works How does it heat the water in your home and make your showers warm At Twintech Heating & Cooling, we carry two types of water heaters: tank and tankless heaters.A tank water heater works by collec

Read More