In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by nicole.el.thorn on Twintech Heating and Cooling

The work was done quickly and professionally. Workers were really polite and easy to work with.
Product works great!

by Gary in London on Twintech Heating and Cooling

Furnace broke down on a Wednesday, shopped around for prices and Friday Twintechs name came up from a referral from my wife's work. Called Dave 11 am, he came over around 1 pm. Gave me a very good price, I accepted. The guys were there two hours later to take the old furnace out and install the new one. All finished by 6:30pm. Finally heat.
They were very pleasant and helpful. As a result we are doing our A/C later this year with this company.

by Shawn L in Whitby on Twintech Heating and Cooling

After some extensive research, we settled on Twintech for our new furnace. The service - from Dave's initial visit - through to the installation was absolutely fantastic.

Dave was super-patient with our many questions, did not try to "up-sell" us into buying things we don't need, knowledgeable, friendly and all-around an excellent Advisor.

I've forgotten the names of the installers but they were superb as well. They showed up on-time, did all the work with no mess or intrusion, removed the old furnace and installed the new one in one day; all with no impacts to our day-to-day life.

I cannot recommend Twintech enough, especially over any of 'bigger guys' who tried to sell us a bunch of thing we don't need. Twintech were fantastic and my wife and I are very pleased with our purchase.

by Stephen from Pickering on Twintech Heating and Cooling

From the minute I met Dave and discussed my new furnace needs I knew I was in good hands. He was patient, knowledgeable and very professional through the quotation process.

Grant and Greg did an outstanding job on the install. They did a great job of explaining the defects with my old furnace. The quality of the installation was excellent and the attention to detail was on another level. The old adage “You get what you pay for” couldn’t be more true as I feel I received great value, skilled expertise and high quality customer service. I highly recommend Twintech for all your heating and cooling needs.

by Arthur on Twintech Heating and Cooling

Glad to have found a not-too-big local firm that provided the needed expertise, quality workmanship, and competitive pricing as well. In and out in one day, removed the old units, did a nice job installing all of the new units, and left no debris. Even have a service contract that far outshined the big company offerings. Would definitely recommend them.

by Leriksen on Twintech Heating and Cooling

Appreciated a quick response to my request. Dave and Greg were very professional and made the experience seamless.

by petesalmon938 from Pickering on Twintech Heating and Cooling

Very professional through the entire process. Installation and removel was done on a sloppy winter day, they put down runners on the floors and stairs and when they left, there wasn;t any sign of someone being in our house. Furnace works great as promised.

by alenahawco from Whitby on Twintech Heating and Cooling

Dave was very pleasant to deal with and Twintech responded quickly when our furnace needed to be replaced ASAP. Installation was done on time and the crew were neat and tidy. We now have a great furnace that suits the needs of our family.

by Isatta From Pickering on Twintech Heating and Cooling

When your furnace kicks in over the holidays and you're not sure where to turn.. I'm so thankful that this company returned my phone call. I appreciated their transparency and clarity which allowed me to make an informed decision. With various quotes thrown at you, it can be difficult to make the right decision and trust the solutions offered by different companies. TwinTech spoke the truth and delivered on their word. Neat, timely and clean service; the peace of mind I needed during a very cold holiday season. I highly recommend them!

by eryna from Oshawa on Twintech Heating and Cooling

Pulling a old unit out and installing a modern heating system! Required drilling holes in the wall for the newer pipes. We went from 70% (I am willing to bet it was far less due to lack of maintenance and just old) to 96% newer . It now feels warmer and more pressure and we use to run extra heaters and feel as though they are not necessary!