In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Patrick, Toronto on Twintech Heating and Cooling

The blower on our furnace stopped working leaving us with a cold house. Dave from TwinTech responded immediately to our HomeStars service request. From beginning to end Dave was nothing but helpful, friendly and professional, he did a great job of walking us through the quote and scope of work.


The replacement of the furnace went smoothly. The Guys did a great job, everyone was very friendly and polite. There were no hiccups, or unexpected costs. The only surprise was they left the work area cleaner than it was before they started.


Was a great experience with the whole TwinTech team. Its been a couple of months since the new furnace has been installed and its working great!

by Ed, Whitby on Twintech Heating and Cooling

I heard about TwinTech when researching new furnaces at furnaceprices.ca. After contacting them about my broken down furnace, Dave came to my house the next day to assess my situation and requirements for a new furnace. He recommended one that had stainless steel heat exchangers which sold me since my previous furnace had issues with a rusted secondary heat exchanger that had to be replaced. Dave also set me up with an appointment with an energy audit company so that I could take advantage of a rebate to help improve the energy efficiency of my home and get some money back. A few days later, Greg, Grant, and Mitch came to install the new furnace and remove the old one. When delivering and removing the furnaces, they were very careful not to damage my floors and walls, and even laid out red carpeting to protect the floors. They were very friendly and professional. The installation was completed in the time they said it would take and they cleaned up their work areas. Within a week, Dave called to follow-up to see how everything was going. I have already recommended them to several friends and family members who may need new furnaces soon.

by Fred, Toronto on Twintech Heating and Cooling

Twintech did a great job, from Dave the Sales Rep to the Office staff and The Professional Technicians who did the installation. They were professional, courteous, knowledgable and informative. From beginning to follow up we were completely satisfied with everything. Thanks Again. Sincerely The Laytons

by Elle, Oshawa on Twintech Heating and Cooling

Great product, great service, great follow-up. The Twintech Heating and Cooling arranged removal of my existing oil tank and they installed the new gas furnace Amana (made in USA). I am very happy with the final result and support I received throughout the process. My thanks go to the entire Twintech team for their professionalism, great communication and follow-up.

by John & Linda, Ajax on Twintech Heating and Cooling

We've had Twintech provide us with work in the past, for an inground pool heater and required rough-in for a new gas stove. More recently they provided the same friendly, professional, timely and clean installation of our new furnace.

by Bill, Whitby on Twintech Heating and Cooling

Reasonable price and the workmanship was prompt and timely and the employees were great to deal with.

by Nadia, Toronto on Twintech Heating and Cooling

The sales process was friendly, informative, and very consultative. They worked hard to earn our business by taking a careful look around our home to assess our needs, providing a lot of information about the product, and answering all our questions and finding the right solution for our home at a competitive price. They prepared us very well for what to expect on installation day, and the installation went very smoothly - no surprises, all very professional! They gave us a call after installation to ensure we were happy with the work. We're very happy that we chose to work with TwinTech to get our new furnace.

by Private User on Twintech Heating and Cooling

Twintech promptly responded to request for quotation. They were thorough and helpful in explaining options. The quote was very competitive. Installation of new furnace was very professionally completed. Excellent work.

by Rita, Scarborough on Twintech Heating and Cooling

When our old oil furnace finally broke down we decided it was time to finally convert to natural gas and finally install central air conditioning at the same time. Knowing it was going to be a significant investment for us, we wanted to make the right choice. Twintech came highly recommended by a friend and we were not disappointed. From the first contact with the salesperson, until the final touches on the installation, we were so pleased with their service. Everyone from the company was so friendly, efficient and a pleasure to deal with. Best of all, the cost was very competitive. We would certainly recommend Twintech to anyone requiring HVAC work in their home.

by Bob S, Pickering on Twintech Heating and Cooling

Mitch from Twintech came out for our annual furnace inspection. We found him to be friendly, conscientious & he left the work area clean. We were also very impressed with the thoroughness of the job he did. This is the 2nd job we’ve had Twintech do for us & have been very happy with the results for each. We highly recommend this company. Thank you, Mitch, Dave & Greg.