In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Tina - Whitby in Whitby on Twintech Heating and Cooling

The people from Twintech were very friendly and personable...from the salesman to the installers. The installation was done as scheduled. I love my new air conditioner. My neighbour has a York and that thing is so noisy compared to my Goodman!! Thanks Twintech!!

by Cathy f. from Pickering on Twintech Heating and Cooling

Thank you, Twintech. They installed an A/C in my home in the middle of a heat wave which we appreciated very much. I found the team good, not overly friendly, other than the brothers. Dave, the salesperson was awesome, and, it's because of him that I was sold on using Twintech. I had other questions about additional work I am curious about and would have liked them to follow up and provide a quote. Other than that, which ultimately is not related to the great work they did, I would definitely recommend them, although I don't believe they go outside of Durham (check with them).

by Linda from Durham Region on Twintech Heating and Cooling

We have used this company a few times so I can't remember exactly what we paid but I do know that their fees are always very reasonable.

The first time we called Greg was when our furnace conked out while we were away. He came right away, showed me the problem and fixed it immediately.

The second time was when we needed an air conditioner moved and lifted to a platform. Again, he showed up on time, completed the job quickly (including a new gas line) and the fee was very reasonable.

We have received a quote from Greg to replace the air conditioner and furnace and when we are ready to move ahead, we will be calling him.

I have no hesitation in recommending TwinTech!

by AS from Pickering on Twintech Heating and Cooling

Our rating for Twintech is 5/5 stars. They are very professional and efficient, and the transparency they maintain right from the preliminary assessment till the day of the work is a testament to their experience in the field. We had Twintech replace our air conditioning and furnace, and we appreciate the efforts taken by Greg.

by Raymond from Toronto on Twintech Heating and Cooling

After 18 years my Air conditioner died in the middle of a heat wave. I entered my information on Home Stars and within the hour Dave from Twin Tech responded and offered to meet me as soon as possible depending on my availability. Dave was very knowledgeable about the products Twin Tech offered and even though this was the first quote I received . I felt very comfortable in giving Twin Tech my business. maybe it was the professional approach. Needless to say that the crew with Greg and Grant arrived promptly at the time they committed to were very professional and within a few hours had the place cool. They cleaned up and one would never know that I had work done . I know that the System is new and I probably wont need to worry about it for some time. However with the professionalism displayed by the crew I feel assured that should I need to call for service Twin Tech will respond. I also know that should I need a new Heating system I will go with Twin Tech. Keep up the good work.

by gerard harrington from Ajax on Twintech Heating and Cooling

Greg and team were amazing! All interaction via email and text 100% professional. From consult to product recommendation their service was phenomenal!

Installed a Napoleon furnace (ecm dc drive variable 2-stage) and it was a game changer for the whole house. Blended air temperature through and through the entire house and it’s saving us money by cutting down our utility bill by ALOT!

by D &. from Whitby on Twintech Heating and Cooling

We purchased a new cooling & heating system from Twintech and the team was fantastic. From sales to installation, the team were great to work with. Friendly (our dog even enjoyed having them over), professional and accommodating. I’d recommend Twintech in a heart beat to anyone. Superb customer service.

by Anonymous from Pickering on Twintech Heating and Cooling

End to end service. From quote, overseeing installation, contacting and making arrangements for energy audit. Warranty program is comprehensive. Cleaned up mess of assistant walking through my place without proper indoor foot covering when I pointed out that I was not happy about footprints on my floors.

by Bob S in Pickering on Twintech Heating and Cooling

In April we hired Twintech Heating & Cooling to replace our 20 year old water tank & 35 year old air conditioner. We got 5 estimates for the job & decided to go with Twintech for the following reasons.

- The Sales Manager, Dave, was very personable & knowledgeable as all of our questions were answered. (We had a list of questions we asked each of the contractors when we got the estimates)
- We got 5 estimates for the job. All contractors verbally told us they had the required qualifications but Dave was the only one to physically show us their license & insurance documentation.
- Twintech carried the Napoleon air conditioner & we wanted to support Canadian industry as it is assembled in Barrie On.

Safety is important at Twintech as demonstrated when we discussed with Dave, the need to change our install date because of freezing rain. Access was required by navigating a set of outside steps & Dave identified that safety took precedence.
On the installation date, Greg, Peter & Grant showed up on time & methodically accomplished the removal & installation of both units. The guys did a great job cleaning up as well.

When the job was completed we mentioned to Greg that we were pleased with the work they had done & were going to have them come out & do our furnace inspection in Sept. Greg said we can save our money as he had inspected the heat exchanger on the furnace while doing the job & there was no need to have another inspection in Sept. We were very impressed with Greg’s initiative. This is top shelf service. Thank you Greg.

As the weather was too cool to complete a functional test of the air conditioner on the installation date, Dave made a follow-up call to us to see how things were going & Greg also came out to check the operation. No problems.

We are very happy we hired professionals like Dave, Greg, Grant & Peter & have no hesitation in recommending Twintech Heating & Cooling. They will now be our "go to" guys.

by ted diplock in Toronto on Twintech Heating and Cooling

These guys are the best. From start to finish they exceeded my expectations and delivered a great product. They accommodated the nuances of my 100 year old home which was really appreciated. The install was easy to schedule and done fantastically. I’m so excited to have an efficiently heated and cooled home.