The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Founded in 1874, YORK has been an industry leader since the beginning. A revolutionary YORK "air washing" system installed in 1914 was the precursor to modern-day air conditioning. In 1924, the world's first air-conditioned office building used YORK equipment. And today, YORK products are heating and cooling iconic structures, including the Empire State Building, the English Chunnel, the U.S. Capitol Building and the Sydney Opera House.


York Furnace error codes are seen in three colors, red, green, and amber/yellow. Each color will also flash a specific number of times to signify a specific error. Breaking down each color, and number of flashes, will help you solve the problem you are having with your York Furnace.


CODE: SLOW GREEN FLASH
RESULT: Normal operation

CODE: SLOW AMBER FLASH
RESULT: Normal operation with call for heat

CODE: RAPID RED FLASH
RESULT: Twinning error, incorrect 24V phasing.
FIX: Check twinning wiring. Flame sense current is below 1.5 microamps

CODE: RAPID AMBER FLASH
RESULT: Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

CODE: 4 AMBER FLASHES
RESULT: The control is receiving a "Y" signal from the thermostat without a "G" signal, indicating improper thermostat wiring.

CODE: 1 RED FLASH
RESULT: This indicates that flame was sensed when there was not a call for heat.
FIX: The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.

CODE: 2 RED FLASHES
RESULT: This indicates that the normally open pressure switch contacts are stuck in the closed position.
FIX: The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. This indicates the normally open pressure switch contact did not close after the inducer was energized.

CODE: 3 RED FLASHES
RESULT: This could be caused by a number of problems: faulty inducer, blocked vent pipe broken pressure switch hose or faulty pressure switch.

CODE: 4 RED FLASHES
RESULT: This indicates that the main limit switch has opened its normally closed contacts.
FIX: The control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 5 RED FLASHES
RESULT: This fault is indicated if the normally closed contacts in the rollout switch opens.
FIX: The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 6 RED FLASHES
RESULT: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat.
FIX: If the main blower is in a "Delay on" mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

CODE: 7 RED FLASHES
RESULT: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
FIX: Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

CODE: 8 RED FLASHES
RESULT: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle.
FIX: This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

CODE: 9 RED FLASHES
RESULT: Indicates reversed line voltage polarity or grounding problem.
FIX: Both heating and cooling operations will be affected. check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

CODE: 10 RED FLASHES
RESULT: Flame sensed with no call for heat.
FIX: Check gas valve and gas valve wiring This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes.

CODE: 11 RED FLASHES
RESULT: This condition is usually caused by a failed blower motor or blower wheel.
FIX: Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

CODE: 12 RED FLASHES
RESULT: This code indicates an open igniter circuit.
FIX: This could be a disconnected or loose wire or a cracked or broken igniter.

CODE: STEADY ON RED
RESULT: Control failure.
FIX: Replace control board.

CODE: 60-MINUTE AUTOMATIC RESET FROM LOCKOUT
RESULT: This control includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7, 8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.

CODE: IGNITION CONTROL FLAME SENSE LEVELS
RESULT: Normal flame sense current is approximately 3.7 microamps DC Low flame signal warning starts at 1.5 microamps. Low flame signal control lockout point is 0.1 microamps DC.


See What Our Customers Are Saying:

by Robert, Pickering on Twintech Heating and Cooling

Had new furnace installed and ran into some difficulties but the contractor responded in a timely and efficient manner - after further service calls were made, a reasonable resolution was found.

by Brian Burns, Whitby on Twintech Heating and Cooling

The work was done quickly efficiently neatly and professionally. Pleased with the service, information, product, and the company.

by Geoff, Port Perry on Twintech Heating and Cooling

Great sales member named Dave came in told us some amazing items and how they would be priced installed an all. We couldn’t believe it! The next day the ac was installed, that day one employee named Greg told us that our furnace was working way to hard and was causing us to use way too much gas. So two days later they came in an installed a new furnace!

by MB, Ajax on Twintech Heating and Cooling

Installation was done quickly and professionally. The new furnace is quiet and provides even heat.

by Richard from Oshawa on Twintech Heating and Cooling

They removed and discarded old furnace. Installed new furnace. Installed air intake pipe, that had never been installed by builder, no charge. Replaced loose hose on floor with hard pipe and rerouted it to drain, no charge. Almost 33% cheaper then quote from Enercare, which was the company we dealt with and had insurance with for 8 years. No yearly fee for cleaning/insurance, saves 300 a year. Courteous, professional, fast, and friendly. My wife and I have been recommending them to everyone we know and meet, and will continue to do so. Thanks for everything, Twintech!!!

by Darcy from Pickering on Twintech Heating and Cooling

This company was great to deal with. Our furnace went down and they installed a new furnace the next day with a lot of professionalism!

by gillian hooton from Uxbridge on Twintech Heating and Cooling

Finally! An honest company with highly knowledgeable and informative staff. Had a furnace service and found multiply errors in our system from an amateur installer. Very fair price to correct problems and will definitely use again.

by dflynn in Ajax on Twintech Heating and Cooling

Had to replace the heating & a/c unit in a condo apartment dwelling. this company recommended by the property manager and president of the condo building. found their workmanship and attention to details very good and very thorough. were able to resolve small problems and situations and happy to feel the heat in my unit. it's pricey, but happy was done by a very professional service. thank you.

by alisiena from Toronto on Twintech Heating and Cooling

Fantastic team. Completed the job as per the specifications and in under 3 hours. Highly recommended Twintech.

by David from Toronto on Twintech Heating and Cooling

During the summer, I previously hired TwinTech to replace my air conditioner when it failed. They did an excellent job so when I decided to proactively replace the furnace I contacted them. The furnace I had was 22 years old and showed signs of internal leakage. It still worked but rather than wait to have it fail in cold weather, I decided to purchase a higher efficiency model before it failed and take advantage of energy efficiency rebates. TwinTech offered very useful advice on the make and model of furnace to choose including high efficiency and variable speed motor. The price was reasonable, TwinTech arrived at the allotted time, installed the new furnace (including some re-routing of exhaust lines since the existing ones were too close to other vents), removed the old furnace, tested the installation and cleaned everything up. Overall, it was a good experience, they did a great job and the new furnace is working well.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Keeping Warm This Fall: Things to Remember

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 5, 2016

We can feel it in the air – the cold season is fast approaching. Keeping a home warm is not as easy as 1,2,3 especially if the home is older and doesn’t really have very good insulation. Here are some tips on how you can save money while you are

Read More

Why Buy a Heat Pump For My Whitby Home

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 27, 2025

When it comes to keeping your Whitby home comfortable year-round, choosing the right HVAC system is crucial. One of the most efficient and versatile options available today is the heat pump. At Twintech Heating and Cooling, we believe a heat pu

Read More

Optimal Use of Your Furnace Unit

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 8, 2024

Here are some key points to consider: Regular Maintenance: Stress the importance of annual maintenance to keep the furnace running efficiently. This includes cleaning filters, checking for leaks, and ensuring proper ventilation. Prop

Read More

Twintech - Trusted Heat Pump Sellers and Consultants in Pickering

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 21, 2025

When it comes to energy-efficient, year-round comfort in the Town of Pickering, more and more homeowners are turning to heat pumps. And when you're looking for a trusted expert to guide you through the process of selecting, installing, and mai

Read More